Revision Indication
PROJECT SPECIFICATION
UOP LLC 25 East Algonquin Road Des Plaines, Plaines, Illinois 60017-5017 USA USA
943025 - 806 REV
STRAINERS
DATE
BY
APVD
0
17MA 17MAY Y07 DM
TC
1
02NO 02NOV0 V07 7 ADD ADD
TLC
REV
DATE
UOP Naphtha Hydrotreating Process Unit Description
Sheet
Standards
1
General Notes
2
Y - Type Strainers
2
Basket Type Strainers
2
T - Type Strainers
2
Manufacturers
3
Standards
Strainers shall be in accordance with the standards listed below:
Other specifications referenced in this specification: Form QUA-04-4
8-11
UOP Standard Specification - Piping
ASTM E 674
Industrial Perforated Plate and Screens (Round Opening Series)
ASTM E 2016
Industrial Woven Wire Cloth
UOP Standard Specification: 8-11-11 UOP Standard Drawing: UOP Project Specification: 806-4
806-200-6
SHEET
1
BY
APVD
Revision Indication
PROJECT SPECIFICATION
UOP LLC 25 East Algonquin Road Des Plaines, Illinois 60017-5017 USA
943025 - 806 REV
STRAINERS
DATE
BY
APVD
0
17MAY07 DM
TC
1
02NOV07 ADD
TLC
REV
DATE
SHEET
2
BY
APVD
General Notes
1. Strainers shall be designed to accommodate an acceptable level of clogging. 2. Manufacturer’s names, catalog and/or drawing numbers for strainers specified in this project specification are intended only to indicate quality, design, materials and construction requirements for the particular service and shall not be construed as a preference of manufacturer(s). Equivalent items may be substituted; however, it is the responsibility of both the Owner and Contractor to ensure equivalency. 3. Screens specified for strainers shall be in accordance with ASTM E 674 or equal. 4. Mesh specified for strainers shall be in accordance with ASTM E 2016 or equal. Y - Type Strainers
Strainers shall be furnished with a plugged blow-off outlet. Cast carbon steel, ASTM A 216 Grade WCB, ASME Class 600, socket weld connections. Screens shall be a minimum of 24 gauge (0.0239 inch) perforated type 304 stainless steel plate with 5/32 inch (4 mm) diameter staggered holes at 3/16 inch (5 mm) centers and 63 percent open area, lined with 30 mesh (567 micron) and 0.011 inch (0.28 mm) diameter type 304 stainless steel mesh and 45 percent open area. Mueller Model No 862-CS, Titan Model No. YS82-CS-UOP or equal for the following: 1 - * inch
Fuel Gas (Continuous Purge) to the Relief Header (P&ID 943025-120-02-A1)
Basket Type Strainers
Strainer shall be furnished with a blow-off outlet. Cast carbon steel, ASTM A216 Grade WCB body and cover, spiral wound cover gasket, type 316 stainless steel and graphite, ASME Class 300 RF flanged, perforated 16 gauge (0.0598 inch) type 316 stainless steel plate with 1/8 inch (3 mm) diameter staggered holes at 3/16 inch (5 mm) centers and 40 percent open area, lined with 40 mesh (381 microns) and 0.010 inch (0.25 mm) diameter wire type 304 stainless steel and 36 percent open area. The effective area of the screen assembly shall not be less than 400 percent of the pipe cross sectional area including the application of the wire mesh liner. Mueller Model No. 126F-CS or equal for the following: 2 - 1 ½ inch
Fuel Oil to Charge Heater Burners (P&ID 943025-120-18-A1)
T - Type Strainers
Strainers for centrifugal pumps and compressors not specified above shall be T - Type. Refer to UOP Standard Specification 8-11 for additional requirements.
Manufacturer (or Equal): Form QUA-04-4
806-4
806-200-6
Revision Indication
PROJECT SPECIFICATION
UOP LLC 25 East Algonquin Road Des Plaines, Illinois 60017-5017 USA