INSPECTION & TESTING REQUIREMENTS
REVISION: 06/15/2011
CODE NUMBER:
SAUDI ARAMCO FORM-175
REPLACES: 05/05/2007
IR120100
SCOPE:
PAGE:
1 of 2
STEEL STRUCTURES(Excludes Offshore Structures and Pre-engineering Metal Buildings).
TEST AND INSPECTION PER: 12-SAMSS-007, and Specifications as Noted Below. (1) VISUAL INSPECTION WITNESSING BY INSPECTOR (Note 1) (2) CERTIFICATES / RECORDS TO BE CHECKED BY INSPECTOR (3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER
* * *X 0010 X
0010
Pre-Fabrication/Production Requirements
Specification Details / Notes:
Pre Inspection Meeting
Verify Company approval of Manufacturer Inspection and test Plan.
0020
X
Material Certificates (MTR’s)
Per ASTM requirements and as defined in 12-SAMSS-007
0030
X
Material Heat Numbers
Heat Numbers shall be transferred by supplier to all steel members.
0040
X
Erection and Shop Drawings
Verify approval Per 12-SAMSS-.007, Eng. Dwg., P.O requirements, and associated S. Aramco Standard Drawings.
Verify valid personnel qualification and procedures.
*** 0010
In process inspection & test requirement
Specification Details / Notes:
Workmanship, Components and Dimensions:
Per 12-SAMSS-007
0020
X
a) Grating and Stair Treads
Per 12-SAMSS-007.
0030
X
b) Galvanizing
12-SAMSS-007: Steel shapes and plates to ASTM A123. Bolts
0070
X
0020
nuts and washers to ASTM B695 or A153
0040
X
c) Welding Inspection
12-SAMSS-007 & AWS D1.1. All welds shall 100% visual inspection. In addition to AWS D1.1 inspection requirements, no surface porosity is allowed in strength or seal welds.(See note
0050
X
d) Verification of Seal Welding Performed
12-SAMSS-007: continuous seal welding or Company approved equal is required in places that are not self-draining or where crevice corrosion is likely to occur.
0060
0070
Nondestructive Testing (When Applicable):
X
X
a) Radiography
AWS D 1.1: 100% RT on all butt-welded flange section for all primary load-bearing members. members. 100% RT on all lifting lugs.
IR120100
Continued...
INSPECTION & TESTING REQUIREMENTS
REVISION: 06/15/2011
CODE NUMBER:
SAUDI ARAMCO FORM-175
REPLACES: 05/05/2007
IR120100
PAGE:
2 of 2
(1) VISUAL INSPECTION WITNESSING BY INSPECTOR (Note 1) (2) CERTIFICATES / RECORDS TO BE CHECKED BY INSPECTOR (3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER 0080
X
b) Ultrasonic Inspection
AWS D 1.1: UT can be used where RT is impractical or fails to provide a clear interpretation of weld (As defined by Company Inspector).
0090
X
*** 0010 X 0030
c) Other NDT, e.g. PT or MT
AWS D1.1
Final inspection & test requirements
Specification Details / Notes:
Shop Assembly & Fabrication Tolerances
12-SAMSS-007, AWS D1.1 and AISC Code of Standard Practice.
0020
X
Protective Coatings
12-SAMSS-007: For fireproofing and steel embedded in concrete see SAMSS for further details
0030
X
Marking, Handling and shipment
Per 12-SAMSS-007
Notes: (1) May only be waived by the responsible Saudi Aramco, ASC, AOC Inspection Offices. (2)100% witnessing by Manufacturer Inspector, Random by Company Inspector unless otherwise specified by the responsible Inspection Office. (3)See form SA175 000003 for instructions on using this form. (4)Min fillet weld sizes are in SAMSS. Lifting lugs shall be full penetration welds where possible.