Marshalling Cabinet or Marshalling Panel
Search This Blog Search
As discussed in the Typical Architecture of Instrumentation and Automa tion System, System, the automation automat ion architecture of the plant is having a marshalling cabinet in between the junction box and the system cabinet. This marshalling cabinet function is to interface the incoming field cable (which is no rmally a multipair cable) and the I/O (Input/Output) card connection. Without marshalling cabinet, we can sure (for large number of
Follow by Em Email ail
I/O) that there will be a trouble for operation personnel to maintain and operate and operate the cabling.
Email address...
One of the important interface function of the marshalling cabinet is the cross wiring function. Cross wiring is always necessary since the incoming field signal and the channel quanti ty of the I/O card is always different. For example let’s say we have a 24 pair incoming field cable that carry 20 field analogue signal. This field signal will be split at least into two analogues 16 channel I/O card. The First 16 I/O will be in the first 16 channel I/O card and the other 4 will be in the next 16 channel I/O card. To have this split wiring (cross wiring) in the system cabinet is not a good practice from the operation and maintena nce point of view. Thus t he marshalling cabinet is needed.
Another cause of the cross wiring is the mixed of I/O signals that coming from coming from the field. The i ncoming multipair cable can have mixed AI (Analaogue Input) and AO (Analogue Output) signal in the same multipair cable. This mixed signal will be split in the marshalling cabinet so that the AI signal will be terminated in the dedicated AI termination board and so do the AO signal.
In some application such as voting application for safety system (i.e. 2oo3 voting) there is a requirement to have the I/O signal allocated in the different I/O card so that the common fault cause can be avoided. This application ofcourse once again need a cross wiring in the marshalling cabinet.
In typical application, the marshalling cabinet is having t he following cable routing.
1.
The multipair field cables enter the marshalling cabinet thro ugh the bottom bottom part of the cabinet.
2.
Then each wire of the incoming multipair field cable is terminated in the surge protection devices or surge arrester. If there is no requirement of such surge protection devices, each wire is terminated in the terminal block.
3.
From the surge protection devices, in Non IS application, there will be a cross wiring that match the field signal and the I/O address assignment in the termination board. If the system is IS, then before cross wiring, each wire connection is routed first to the IS Barrier.
4.
Popular Posts Earthing System of Instrument Equipment Instrument earthing system shall consist of the following earth type: · Electrical earthing (also called dirty earthing or Pr... Marshalling Cabinet or Marshalling Panel As discussed in the T ypical Architecture of In strumenta tion and Automation System , the automation architecture of the plant is having a ... Valve Manifold for Pressure Transmitter Valve manifold is a standard accessory for pressure transmitter and differential pressure transmitter. By providing a valve manifold in t... Flow Direction of Control Valves Flow direction of control valves has a relationship with a failure action, High Delta Pressure, Cavitation, and % opening of the valve. ... The Difference Between API and ASME Pressure Pressure Safety Valve ( PSV) In the vendor data sheet, calculation calculation sheet, and or catalogue of the PSV, it was stated two different terms which is API and ASME PSV PSV th...
The dedicated system cable that has a ‘plug and play’ connection is then routed from the termination board to the I/O card in the system cabinet.
5.
Submit
Some termination board may require a dedicated DC power supply that can be taken from the DC power supply in the marshalling cabinet.
As an illustration, see below drawing that shows the simplified marshalling cabinet arrangement in the oil and gas industries. In actual marshalling cabinet arrangement, the equipment arrangement may vary from each automation vendor, but in typical they will have more or less the same equipment as below drawing.
2 Wires, 3 Wires, or 4 Wires RTD (Resistance (Resist ance T emperature Detector)? RTD is a temperature sensiti sensitive ve metal. The resistance of the RTD metal is gradually changed with the changed of temperature. In applicati applicati... ... Typical Architecture of Instrumentation & Automation System In general applicati application, on, the instrumentation instrumentati on and automation architecture is consist of field instruments, individual & multicore cabl...
Labels Commissioning Instrument Maintenance
http://ongengi neer i ng.bl ogspot.fr /2013/03/m ar shal l i ng- cabi net- or - m ar shal l i ng- panel .htm l
1/3
11/17/2014
Oil and Gas Engineering: Marshalling Cabinet or Marshalling Panel Material Piping safety
+1 Recommend this on Google
Labels: Instrument
No comments: Post a Comment
http://ongengineering.blogspot.fr/2013/03/marshalling-cabinet-or-marshalling-panel.html
2/3
11/17/2014
Oil and Gas Engineering: Marshalling Cabinet or Marshalling Panel
Enter your comment...
Comment as:
Publish
Newer Post
Google Accou
Preview
Home
Older Post
Subscribe to: Post Comments (Atom)
Awesome Inc. template. Powered by Blogger .
http://ongengineering.blogspot.fr/2013/03/marshalling-cabinet-or-marshalling-panel.html
3/3