IWC IWCF Opera Operati tion ons s Lim L imit ite ed
Practica ractic al Asse Ass essor sso r Ha Handbo nd book ok
Name
Funct ion
Rae Archibald
Signatu re
Author
George Galloway
Reviewer
Kerrie Moffat
Approver
Date
02/03/2017
George Galloway
03/03/2017
09/03/2017
Practical Assessor Handbook
Contents 1. 2. 3. 4.
5.
6.
7. 8.
9. 10. 11. 12. 13. 1.
Purpose............................... ................................................. .................................. ................................. ................................. ................................. ............................... .............. 3 Scope................................ ................................................. ................................. ................................. .................................. ................................. ................................. ................. 3 Practical Assessor Responsibilities Responsibilities ............................... ................................................ .................................. ................................. ...................... ...... 3 The simulator .................................. ................................................... ................................. ................................. ................................. ................................. .................... ... 3 The simulator environment environment ....................................... ....................................................... ................................. ................................. ......................... ......... 3 Simulator exercises............................................ ............................................................. ................................. ................................. ............................... .............. 4 Before the practical assessment............................... ................................................ ................................. ................................. ............................ ........... 4 Pre-assessment Pre-assessment checks ................................ ................................................ ................................. ................................. .................................. .................... .. 4 Pre-assessment Pre-assessment briefing briefing................................ ................................................ ................................. ................................. .................................. .................... .. 5 Permitted materials ................................. .................................................. ................................. ................................. .................................. ......................... ........ 5 The practical assessment procedure ..................... ...................................... ................................. ................................. ............................... .............. 6 The plot/graph plot/graph ................................. ................................................. ................................. .................................. .................................. ............................... .............. 20 Calculating Calculating the final scores ................................ ................................................. ................................. ................................. ............................. ............ 20 Debrief the candidates candidates ............................... ............................................... ................................. .................................. .................................. .................... ... 20 Re-sit options for the practical assessment ............................................ ............................................................. ............................. ............ 20 20 Completing Completing the paperwork.................. .................................. ................................. .................................. ................................. ............................... ............... 21 Paperwork sent to IWCF .................................... ..................................................... ................................. ................................. ............................. ............ 21 Retention Retention of candidate candidate records................................. ................................................. ................................. ................................. ....................... ....... 21 Grading sheets ............................... ................................................. .................................. ................................. ................................. ................................. ................... 21 Assessor accreditation accreditation .................................. .................................................. ................................. .................................. .................................. .................... ... 23 Auditing ............................... ................................................. .................................. ................................. ................................. ................................. ............................. ............ 23 Reference documentation documentation ................................ ................................................ ................................. ................................. .................................. ..................23 Contacting Contacting IWCF ............................... ................................................ .................................. .................................. .................................. ............................... .............. 23 Appendix 1 – Practical assessment assessment re-sit options................................. ................................................. ............................... ............... 24
August 2017
AC-0018
Version 1.0
Page 2 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility responsibility to verify printed material against the controlled document
Practical Assessor Handbook
1. Purpose The purpose of this document is to provide practical assessors with a handbook that explains the practical assessment procedure. This document should be used as a guidance document to assist practical assessors to conduct IWCF practical assessments to IWCF standards.
2.
Scope
This document applies to all IWCF accredited practical assessors.
3. Practical Assessor Respon sibi lit ies Only an IWCF accredited practical assessor can conduct practical assessments. The practical assessor must:
be accredited at the centre location where the practical assessments are conducted. be competent in the operation and programming of the simulator. understand the content and procedure for carrying out IWCF practical assessments. conduct practical assessments in accordance with IWCF procedures. be able to perform the role of the Level 3 (Driller) and Level 4 (Supervisor) candidates when required. not coach, advise or help candidates in any way during the practical assessment.
4. The sim ulator The centre is responsible for ensuring the simulator has been approved for use by IWCF. The practical assessor must ensure the simulator is set up for use according to IWCF requirements.
The simu lator environment The simulator environment must meet the following requirements:
The only people allowed in the simulator room during IWCF practical assessments are the candidates being assessed, the IWCF accredited assessor, any assessors undergoing training and an IWCF Auditor (if present). Only one practical assessment at a time can take place in any simulator room. During the kill phase of the practical assessment, the Level 3 candidate must operate the pump while the Level 4 candidate must operate the choke. When portable simulators are used, the pump control panel and the remote choke control panel must be-angled. This is so that the Level 3 candidate cannot see the remote choke panel and the Level 4 candidate cannot see the pump control panel. Panels/displays must be positioned so that the assessor can discreetly observe the activity of the Level 3 and Level 4 candidates. The assessor must be able to make adjustments to the simulator during the assessment without the candidates seeing what changes are being made such as initiating the problem during the kill. Therefore, the assessor must position the instructor station so that the candidates cannot see any changes he/she makes. The following notices must be displayed in the simulator room: a) Practical Assessment – Notice to Candidates b) Practical Assessment – Notice to Assessors
August 2017
AC-0018
Version 1.0
Page 3 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook Simulator exercises All exercises loaded on the simulator must meet IWCF requirements, which are outlined in the IWCF Well Design Rules. In summary these are:
Exercise wells used for practical assessments must be different to those used for training and practice sessions. There must be at least three different exercise wells for each stack type to use during practical assessments. Each exercise well must meet the minimum design rules with respect to depths, configuration, formations and pressures.
5. Before the practi cal assessment Pre-assessment checks Before the start of a practical assessment the assessor must:
check the candidate’s photographic identification and write the candidate’s name on the front page of the grading sheet in accordance with the identification provided. must confirm the candidate’s identification has been checked by completing the ‘Candidate’s ID checked’ box on the front page of the grading sheet. ensure the combination of candidates is one of the following:
a) One Level 3 candidate with one Level 4 candidate assessed as a pair b) One Level 3 candidate with the assessor acting as the Level 4 candidate c) One Level 4 candidate with the assessor acting as the Level 3 candidate The above combinations of candidates are the only acceptable combinations. Please note: it is not acceptable to assess two or more Level 3 candidates together or two or more Level 4 candidates together. Candidates being assessed together must be assessed on the same stack type.
ensure the simulator environment is set up according to Section 4 of this handbook. load an appropriate exercise on the simulator according to the IWCF Well Design Rules ensuring that re-sit candidates get a different exercise to any they have already failed. ensure the simulator line-up is set up as follows: a) b) c) d) e)
ensure the simulator plotting has been set to record from the start of the exercise and that the parameters below are in different colours from one another on the plot. The minimum parameters to be recorded are: a) b) c) d) e) f)
The standpipe manifold is not correct for drilling The choke manifold is not correct for drilling The remote choke is half open The Blow Out Preventer (BOP) is not correctly lined-up for drilling Manifold and/or Annular pressures are too low.
The time on the x axis (horizontal axis) The formation pressure on the y axis (vertical axis) The Bottom Hole Pressure (BHP) on the y axis to the same scale as the formation pressure The drill pipe pressure on the y axis The casing pressure on the y axis to the same scale as the drill pipe pressure The pit gain or pit level.
ensure the following details are printed on the graph: a) b) c)
August 2017
The name(s) of the candidate(s) The name of the assessor The date of the assessment. AC-0018
Version 1.0
Page 4 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
ensure the correct grading sheets below are ready and have been completed with the appropriate centre, candidate and assessor details for the practical assessments: a) Practical Assessment Grading Sheet – Surface BOP Operations b) Practical Assessment Grading Sheet – Subsea BOP Operations
Pre-assessment bri efing Before the start of a practical assessment the assessor must advise the candidates that:
the assessment will be conducted under exam conditions. the assessor will not coach, advise or help them in anyway but he/she may instruct them on the operation of the simulator if they know what they want to do but cannot remember how to do it. For example, the candidate wants to reset the stroke counter but cannot find the stroke counter reset button. If this happens, the candidate must directly ask the assessor where the stroke counter reset button is and then the assessor can show them. they cannot ask the assessor what they should do next in the assessment. the assessor must not prompt them at all. the Practical Assessment is a role-play scenario and they will be playing the role of Driller (Level 3) or Supervisor (Level 4) as detailed in the form Practical Assessment – Notice to Candidates. they cannot bring written instructions of any kind into the simulator room. before the assessment begins the assessor and Level 4 candidate must agree how the Level 3 candidate will be given instructions during the assessment. Acceptable methods are: a) Verbal after the assessment has started b) Written down on paper after the assessment has started c) Written on a whiteboard/flipchart after the assessment has started d) Or a combination of the above.
the assessment must be conducted as a single non-stop exercise. If the assessment being conducted is for a Level 4 candidate only, the pre-drilling preparation stage must still be completed up to the time the Supervisor leaves the simulator room. Once the pre-drilling preparation has been completed, the assessor can load a snapshot with the well shut in and pressures stabilised. Before loading the new snapshot, a simulator plot/graph must be printed off showing the preparation stages, the exercise will then continue. The assessor may, however, choose to go through the drilling phase in which case there will only be one plot/graph. a problem will be given at some time during the kill but only one problem will be given per assessment. the simulator must run at normal speed (real time) until after the problem and can run at an accelerated speed from then on. The simulator must be returned to real speed at least 100 strokes before the gas reaches the BOP.
Permit ted m aterials During the assessment candidates may only use the following materials:
Blank paper, pens, pencils, ruler and non-programmable calculator. Devices with internet capability are not allowed. The Level 4 candidate may be given a pre-kick data sheet completed with volumes and strokes for the exercise depth (equivalent to page one of the IWCF kill sheet) and a blank kill sheet for use when the well has been shut i n (equivalent to page two of the IWCF kill sheet), all kill/kick sheets must be approved by IWCF prior to use. In some cases, the pre-kick data sheet and the kill sheet will be the same document. For clarity, the only details that can be given on the pre-kick data sheet are: a) The current mud weight b) The shoe MD/TVD c) The well MD/TVD at the start of the exercise d) Leak-off test information/shoe fracture pressure or gradient/maximum mud weight/Maximum Allowable Annulus Surface Pressure (MAASP) - any or all e) String, open hole, annular, total well and surface line volumes and strokes for the depth at the start of the exercise
August 2017
AC-0018
Version 1.0
Page 5 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook f) Riser and choke line lengths, volumes and strokes (for subsea exercises only). g) The driller parameters i.e. Pump Speed, RPM and Weight on bit may also be given.
The Level 3 (driller) candidate may be given a drilling trend/log sheet. A well kill trend/log sheet may be provided for use during the kill phase. A whiteboard/flipchart and pens.
Note: It is not a requirement to provide all of the above.
6. The practi cal assessment proc edure This section details the running order of a practical assessment from start to end. The running order assumes it is a double assessment with a Level 3 (driller) candidate and a Level 4 (supervisor) candidate. Comments are made for single candidate assessments when applicable. Subsea elements are clearly shown as being such. Surface candidates do not have to meet the subsea elements. Each step must be scored on the appropriate grading sheet as it happens. The practical assessment procedure details the points that must be awarded for each step. Please refer to these grading notes throughout the assessment. Assessors have no flexibility to adjust the scoring. The Practical Assessment procedure starts on the next page.
August 2017
AC-0018
Version 1.0
Page 6 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
NOTES Notes
Grading
(4) 1. Prepare the drill floor
Not on drill floor during this stage.
The Driller must ensure the BOP stack and manifolds are ready for drilling operations.
1 1 2
The line-up must be incorrect at the start of the exercise (please refer to section 5.1 above).
Line up standpipe manifold ‘Y/N Grading’ . Line up choke manifold ‘Y/N Grading’ . Set up BOP Panel including accumulator gauges (1pt for BOP position and 1pt for gauges). (3) 1. Check the drill floor set up The Supervisor is called to the drill floor and is expected to check that the line-up is correct.
1 1 1
Choke manifold. BOP Panel – Position of BOPs and Valves. BOP Panel – All gauges. Supervisor either checks by himself/herself or asks driller for positions/values.
The assessor must not correct any mistakes that are not noticed.
Please Note: Supervisor has to perform steps 1-4 below before he/she leaves the floor, whatever order he/she uses. If line-up problems are only corrected after the pumps have been started for the first KRCP, then zero (0) score.
(1) For subsea assessments, the Supervisor must also confirm the choke and kill line contents.
1
Confirm choke and kill line contents ‘Y/N Grading’ .
The Supervisor must ask the Driller what is in the choke and kill lines. The assessor can confirm it is current mud in both but only when the Driller has been asked. The Supervisor can only ask this question up to the time the Choke Line Frictions (CLF) are taken. If asked following CLF, then zero (0) score.
August 2017
AC-0018
Version 1.0
Page 7 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
2. Set the choke position The Driller must set the choke according to the shut-in method given and/or confirm that the position is correct.
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
(1) 1
2. Give instructions The Supervisor must give the Driller instructions about well control awareness.
‘Y/N Grading’ .
If Driller does not receive instructions to place the choke in the correct position, then the Driller must do it on their own initiative before the pumps are operated for the first time (when KRCP is taken). If adjusted after this time, then zero (0) points.
NOTES Notes
(10) 4
NOTE: These instructions can be given to the Driller at any time up to the point when the Driller is about to place the Bit on bottom. After that, then zero (0) points. NOTE: If the Supervisor does not give the Driller instructions on actions to take in the event of a drilling break or influx, the assessor must do so when the Supervisor has left the rig floor.
Grading
2
4 pts – procedure to follow to shut the well in, BOP and Failsafe/HCR valves to use, and choke position are given. 2 pts – procedure to follow to shut the well in and choke position, but no mention of which BOP or Failsafe/HCR to use. 0 pts – If no procedure to shut the well in or checking of choke. Reason for choice of shut-in procedure. ‘Y/N Grading’ . One good reason. For example: Company Policy. Hard shut in – minimise influx size, minimise number of actions. Soft shut in – Deep well, highdensity mud, liquid influx.
4
Action to take 4 pts – If full instructions for drilling break and influx. 2 pts – if only partial instructions given. 0 pts – If incorrect or no instructions given.
Shut-in procedure should comply with industry best practise for the Hard or Soft shut-in procedure. The assessor must ask the Supervisor why they chose the shut-in method if the Supervisor does not give it as part of the instructions. Standard instructions are: Pick up to space out position. Shut down Rotary and pumps. Check for flow. If not flowing, call Supervisor. If flowing shut-in as per procedure then: Check well is secure and call Supervisor. It is not acceptable for the Driller to be given instructions which prevent him conducting a flow check or detecting a drilling break. For example: “When you detect a drilling break, drill a further ten feet”.
(2) For subsea assessments details must be included on spacing out the tool joint.
August 2017
AC-0018
2
Hang-off procedure, space out ‘Y/N Grading’.
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Supervisor must state reason for correct space-out for both shut in and hang-off. Also agree correct space-out position with Driller.
Page 8 of 24
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
2. Set the choke position
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
(1)
The Driller must set the choke according to the shut-in method given and/or confirm that the position is correct.
1
2. Give instructions The Supervisor must give the Driller instructions about well control awareness.
‘Y/N Grading’ .
If Driller does not receive instructions to place the choke in the correct position, then the Driller must do it on their own initiative before the pumps are operated for the first time (when KRCP is taken). If adjusted after this time, then zero (0) points.
Pts
Notes
(10) 4
NOTE: These instructions can be given to the Driller at any time up to the point when the Driller is about to place the Bit on bottom. After that, then zero (0) points. NOTE: If the Supervisor does not give the Driller instructions on actions to take in the event of a drilling break or influx, the assessor must do so when the Supervisor has left the rig floor.
NOTES Grading
2
4 pts – procedure to follow to shut the well in, BOP and Failsafe/HCR valves to use, and choke position are given. 2 pts – procedure to follow to shut the well in and choke position, but no mention of which BOP or Failsafe/HCR to use. 0 pts – If no procedure to shut the well in or checking of choke. Reason for choice of shut-in procedure. ‘Y/N Grading’ . One good reason. For example: Company Policy. Hard shut in – minimise influx size, minimise number of actions. Soft shut in – Deep well, highdensity mud, liquid influx.
4
Action to take 4 pts – If full instructions for drilling break and influx. 2 pts – if only partial instructions given. 0 pts – If incorrect or no instructions given.
Shut-in procedure should comply with industry best practise for the Hard or Soft shut-in procedure. The assessor must ask the Supervisor why they chose the shut-in method if the Supervisor does not give it as part of the instructions. Standard instructions are: Pick up to space out position. Shut down Rotary and pumps. Check for flow. If not flowing, call Supervisor. If flowing shut-in as per procedure then: Check well is secure and call Supervisor. It is not acceptable for the Driller to be given instructions which prevent him conducting a flow check or detecting a drilling break. For example: “When you detect a drilling break, drill a further ten feet”.
(2) For subsea assessments details must be included on spacing out the tool joint.
August 2017
2
AC-0018
Hang-off procedure, space out ‘Y/N Grading’.
Version 1.0
Supervisor must state reason for correct space-out for both shut in and hang-off. Also agree correct space-out position with Driller.
Page 8 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
3. Prepare to drill The Driller must measure and record the kill rate circulating pressure losses.
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
(2) 2
Record ‘kill rate circulating pressures’ (KRCP). As requested by Supervisor or on Driller’s own initiative. Driller to suggest taking kill rate circulating pressures if Supervisor asks him to drill ahead without them.
3. Instruct the Driller to record the kill rate circulating pressure at given pump speeds. The Supervisor must give the Driller kill rates that are to be measured/recorded on both pumps.
(4)
1 1 1 1
(2)
4. Set the alarms
2
0 pt – If Supervisor forgets and Driller has to remind him. Pump 1 1st KRCP Pump 1 2nd KRCP Pump 2 1st KRCP Pump 2 2nd KRCP ‘Y/N Grading’. The Supervisor should ask for a minimum of two kill rate circulating pressures for at least two pumps, else penalise accordingly.
2 pts – If done with 2 pumps, 2 KRCPs and remote choke panel gauges. 1 pt – If mistake (only 1 pump or flow rate or use of incorrect gauge). 0 pts – If 2 mistakes.
The Driller must measure and record Choke Line Friction (CLF) for subsea assessments at the same rates as KRCP on the same pumps.
Grading
NOTES Notes Evidence that these measurements were taken must appear on the simulator printout/graph and on the kill sheet. If the pump speed is not plotted, then the graph must show that the drill pipe pressure is increasing for each kill rate chosen and for each pump. If KRCP’s are not taken before Driller starts drilling, then zero (0) score.
(1) Determine Choke Line Friction for kill rate circulating pressures ‘Y/N Grading’.
For subsea assessments, the Supervisor must instruct the Driller on which method is to be used to measure/record CLF.
(6)
1
Instruct Driller on method to use to record CLF for KRCP ‘Y/N Grading’.
Separate lines on the plot must show where CLF was measured and added to the kill sheet. If CLF’s not taken before Driller starts drilling, then zero (0) score.
(2) 4. Check the alarm settings
Set alarms according to Supervisor instructions. Ensure the audible alarm has been switched on/activated.
3
3
August 2017
Adjust and activate flow indicator alarms, can be done with the help of the Supervisor ‘Y/N Grading’. Adjust and activate PVT alarms, can be done with the help of the Supervisor ‘Y/N Grading’ .
AC-0018
Give the Driller the alarm settings and ensure they have been set accurately.
1
Give Driller alarm settings ‘Y/N Grading’ .
1
Physically check Driller has set alarms accurately ‘Y/N Grading’ .
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
If not set by the time the Driller starts drilling, then zero (0) score.
Page 9 of 24
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
3. Prepare to drill
SUPERVISOR (LEVEL 4) Grading
(2)
The Driller must measure and record the kill rate circulating pressure losses.
2
Record ‘kill rate circulating pressures’ (KRCP). As requested by Supervisor or on Driller’s own initiative. Driller to suggest taking kill rate circulating pressures if Supervisor asks him to drill ahead without them.
Pts
Grading
Notes
3. Instruct the Driller to record the kill rate circulating pressure at given pump speeds.
(4)
0 pt – If Supervisor forgets and Driller has to remind him.
Evidence that these measurements were taken must appear on the simulator printout/graph and on the kill sheet. If the pump speed is not plotted, then the graph must show that the drill pipe pressure is increasing for each kill rate chosen and for each pump.
The Supervisor must give the Driller kill rates that are to be measured/recorded on both pumps.
1 1 1 1
(2)
4. Set the alarms
2
Pump 1 1st KRCP Pump 1 2nd KRCP Pump 2 1st KRCP Pump 2 2nd KRCP ‘Y/N Grading’. The Supervisor should ask for a minimum of two kill rate circulating pressures for at least two pumps, else penalise accordingly.
2 pts – If done with 2 pumps, 2 KRCPs and remote choke panel gauges. 1 pt – If mistake (only 1 pump or flow rate or use of incorrect gauge). 0 pts – If 2 mistakes.
The Driller must measure and record Choke Line Friction (CLF) for subsea assessments at the same rates as KRCP on the same pumps.
NOTES
L4 Supervisor
If KRCP’s are not taken before Driller starts drilling, then zero (0) score.
(1) Determine Choke Line Friction for kill rate circulating pressures ‘Y/N Grading’.
For subsea assessments, the Supervisor must instruct the Driller on which method is to be used to measure/record CLF.
(6)
1
Instruct Driller on method to use to record CLF for KRCP ‘Y/N Grading’.
Separate lines on the plot must show where CLF was measured and added to the kill sheet. If CLF’s not taken before Driller starts drilling, then zero (0) score.
(2) 4. Check the alarm settings
Set alarms according to Supervisor instructions. Ensure the audible alarm has been switched on/activated.
3
3
Adjust and activate flow indicator alarms, can be done with the help of the Supervisor ‘Y/N Grading’.
Give the Driller the alarm settings and ensure they have been set accurately.
Adjust and activate PVT alarms, can be done with the help of the Supervisor ‘Y/N Grading’ .
August 2017
AC-0018
1
Give Driller alarm settings ‘Y/N Grading’ .
1
Physically check Driller has set alarms accurately ‘Y/N Grading’ .
Version 1.0
If not set by the time the Driller starts drilling, then zero (0) score.
Page 9 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
Grading
NOTES Notes
The Supervisor may help the Driller in running to bottom but must leave the drill floor when the Driller has tagged bottom. The Driller must now drill ahead with agreed drilling parameters of Weight on Bit, RPM and SPM.
If there is no L3 (Driller) candidate, the assessor can load a snapshot with the well shut in on approximately ten barrels of kick with the pressures stabilised. In this case, print out a plot/graph of the drill floor preparation stage before loading the new snapshot. This graph must be signed off in addition to the graph of the kill at the end of the assessment. This will be an extra graph as two snapshots will be used. If the assessor chooses to continue with the same snapshot and drill into the kick, then there is no need to print a graph off at this stage. The final end of assessment graph will be enough. (13) 5. Drilling break The Driller must recognise and respond correctly to a drilling break.
5
Recognise drilling break ‘Y/N Grading’ .
5
Take correct action 5 pts – If done as per Supervisors instructions. 2 pts – If any one failure to fulfil Supervisor’s instructions. 0 pts – If Driller makes more than one failure from Supervisor’s instructions.
The correct action will be to: Pick up. Stop rotating (optional for flow check). Space out. Turn pumps off. Flow check and call the Supervisor.
3
Rest flow alarms ‘Y/N Grading’ .
The assessor can tell the Driller to continue drilling rather than bringing the Supervisor to the drill floor.
Not on the drill floor during this stage.
The Flow alarms must be reset when returning to drilling, including activating the audible alarm. NOTE: If the Driller takes no action on the drilling break, then award the points for resetting the alarms.
August 2017
AC-0018
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Page 10 of 24
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
Pts
NOTES Grading
Notes
The Supervisor may help the Driller in running to bottom but must leave the drill floor when the Driller has tagged bottom. The Driller must now drill ahead with agreed drilling parameters of Weight on Bit, RPM and SPM.
If there is no L3 (Driller) candidate, the assessor can load a snapshot with the well shut in on approximately ten barrels of kick with the pressures stabilised. In this case, print out a plot/graph of the drill floor preparation stage before loading the new snapshot. This graph must be signed off in addition to the graph of the kill at the end of the assessment. This will be an extra graph as two snapshots will be used. If the assessor chooses to continue with the same snapshot and drill into the kick, then there is no need to print a graph off at this stage. The final end of assessment graph will be enough. (13) 5. Drilling break The Driller must recognise and respond correctly to a drilling break.
5
Recognise drilling break ‘Y/N Grading’ .
5
Take correct action 5 pts – If done as per Supervisors instructions. 2 pts – If any one failure to fulfil Supervisor’s instructions. 0 pts – If Driller makes more than one failure from Supervisor’s instructions.
The correct action will be to: Pick up. Stop rotating (optional for flow check). Space out. Turn pumps off. Flow check and call the Supervisor.
3
Rest flow alarms ‘Y/N Grading’ .
The assessor can tell the Driller to continue drilling rather than bringing the Supervisor to the drill floor.
Not on the drill floor during this stage.
The Flow alarms must be reset when returning to drilling, including activating the audible alarm. NOTE: If the Driller takes no action on the drilling break, then award the points for resetting the alarms.
August 2017
AC-0018
Version 1.0
Page 10 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
Grading
NOTES Notes
(12) 6. Kick detection and well shut-in Follow the correct procedure before shutting in the well.
Not on the drill floor during this stage. 5
Bit at Bottom ?
Shut in the well.
5
5 pts – If Supervisor’s instructions are followed correctly. 3 pts – If bit kept at bottom. 2 pts – If pump stopped before pulling the string. 0 pts – If more than one failure to follow Supervisor’s instructions. 5 pts – If done correctly. 2 pts – If Driller hesitates or takes more than 15 seconds before taking proper action, after a positive flowcheck or shuts the well in but not following the proper method according to instructions i.e. does not open side outlet valve. Note: See possible failure scenarios in NOTES column.
Inform the supervisor.
August 2017
2
First thing to be done once it is confirmed the well is shut in and flow has stopped. If BOP failure incident has been selected then Supervisor should be called, after closing another BOP and confirming flow has stopped. ‘Y/N Grading’.
AC-0018
Correct procedure is to pick up to space-out positon, stop rotation, turn the pumps off and recognise flow.
15 seconds One minute How we know the kick is to large Do we need to calculate ? Do the Supervisor need to calculate ? What action if to large ?
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
The Driller fails if drilling is continued for one minute after the kick is taken OR the Driller shuts in with the pumps running OR the kick taken is too large to circulate out without fracturing the formation OR the well is not shut in. The Driller must call for the Supervisor immediately after the well has been shut in and it has been confirmed that the flow has stopped. The assessor should wait for a period of time before calling the Supervisor to the rig floor. This is to allow time to assess whether the Driller starts to record the build-up of shut in pressures.
Page 11 of 24
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
Pts
NOTES Grading
Notes
(12) 6. Kick detection and well shut-in
Not on the drill floor during this stage.
Follow the correct procedure before shutting in the well.
5
Bit at Bottom ?
5
Shut in the well.
5 pts – If Supervisor’s instructions are followed correctly. 3 pts – If bit kept at bottom. 2 pts – If pump stopped before pulling the string. 0 pts – If more than one failure to follow Supervisor’s instructions. 5 pts – If done correctly. 2 pts – If Driller hesitates or takes more than 15 seconds before taking proper action, after a positive flowcheck or shuts the well in but not following the proper method according to instructions i.e. does not open side outlet valve.
Correct procedure is to pick up to space-out positon, stop rotation, turn the pumps off and recognise flow.
15 seconds One minute How we know the kick is to large Do we need to calculate ? Do the Supervisor need to calculate ? What action if to large ?
Note: See possible failure scenarios in NOTES column.
2
Inform the supervisor.
First thing to be done once it is confirmed the well is shut in and flow has stopped. If BOP failure incident has been selected then Supervisor should be called, after closing another BOP and confirming flow has stopped. ‘Y/N Grading’.
August 2017
AC-0018
Version 1.0
The Driller fails if drilling is continued for one minute after the kick is taken OR the Driller shuts in with the pumps running OR the kick taken is too large to circulate out without fracturing the formation OR the well is not shut in. The Driller must call for the Supervisor immediately after the well has been shut in and it has been confirmed that the flow has stopped. The assessor should wait for a period of time before calling the Supervisor to the rig floor. This is to allow time to assess whether the Driller starts to record the build-up of shut in pressures.
Page 11 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
Grading
NOTES Notes
(5) Problem. 5 - BOP failure 3 The Driller recognises that the BOP has failed and closes another BOP. 2
Not on the drill floor during this stage.
Recognise BOP does not seal Driller has to recognise that the well is flowing. ‘Y/N Grading’ .
This problem can be given in a number of ways: i) No reaction when the Driller operates close function, in other words there is no light change, no pressure drop and no flow count.
Activate another BOP and inform Supervisor of the problem. ‘Y/N Grading’.
ii) Partial reaction when the Driller operates close function. In other words, the light changes, but there is no pressure drop or flow count. iii) The BOP closes but leaks.
If the Driller fails to shut in the well as described above, and there is a Supervisor candidate, then the assessor takes over as Driller. If a new snapshot has to be loaded to continue the exercise, then a plot/graph must be printed out before the new snapshot is loaded. Checking and instructions
Not applicable to the Driller.
Line up to trip tank and check for leaks
For subsea assessments, the Supervisor must check the tool joint space-out position.
(4) 7. Collect shut-in data The Driller records shut-in data.
Most important check MAASP and inform supervisor if approch
1
2
Positioning drill string, hang off checking, BOP closing pressure adjustment if required.
The Supervisor must check the tool joint position and give instructions for hanging off the drill string.
2
Physically check hole depth ‘Y/N Grading’.
The Driller record must show the pressures recorded over time.
2
SIDPP 2 pts- If checked with evolution 1 pt – If just collected from Driller and not physically checked.
(8) Correctly record pressure readings.
3
(2)
3 pts – If properly recorded following pressure evolution on correct gauge. 1 pts – If taken too soon or too late or on wrong gauge. 0 pts – If not taken at all.
5. Collect and check data The Supervisor must collect and check the shut-in data.
Read the correct SIDPP delta P
2
Correctly record gain ‘Y/N Grading’ .
SICP 2 pts – If collected and checked. 1 pt – If just collected from Driller and not physically checked.
The Supervisor must check the data and not just take the figures from the Driller. Permeability setting has to allow a proper study of pressure build up.
Check depth and compare with the depth when SCR where taken
2 Physically check Pit Gain ‘Y/N Grading’ .
August 2017
AC-0018
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Minimum every minute important
Page 12 of 24
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
Pts
NOTES Grading
Notes
(5) Problem. 5 - BOP failure 3 The Driller recognises that the BOP has failed and closes another BOP. 2
Not on the drill floor during this stage.
Recognise BOP does not seal Driller has to recognise that the well is flowing. ‘Y/N Grading’ .
This problem can be given in a number of ways: i) No reaction when the Driller operates close function, in other words there is no light change, no pressure drop and no flow count.
Activate another BOP and inform Supervisor of the problem. ‘Y/N Grading’.
ii) Partial reaction when the Driller operates close function. In other words, the light changes, but there is no pressure drop or flow count. iii) The BOP closes but leaks.
If the Driller fails to shut in the well as described above, and there is a Supervisor candidate, then the assessor takes over as Driller. If a new snapshot has to be loaded to continue the exercise, then a plot/graph must be printed out before the new snapshot is loaded. Checking and instructions
Not applicable to the Driller.
Line up to trip tank and check for leaks
For subsea assessments, the Supervisor must check the tool joint space-out position.
(4) 7. Collect shut-in data The Driller records shut-in data.
Most important check MAASP and inform supervisor if approch
1
2
Positioning drill string, hang off checking, BOP closing pressure adjustment if required.
The Supervisor must check the tool joint position and give instructions for hanging off the drill string.
2
Physically check hole depth ‘Y/N Grading’.
The Driller record must show the pressures recorded over time.
2
SIDPP 2 pts- If checked with evolution 1 pt – If just collected from Driller and not physically checked.
(8) Correctly record pressure readings.
3
(2)
3 pts – If properly recorded following pressure evolution on correct gauge. 1 pts – If taken too soon or too late or on wrong gauge. 0 pts – If not taken at all.
5. Collect and check data The Supervisor must collect and check the shut-in data.
Read the correct SIDPP delta P
2
Correctly record gain ‘Y/N Grading’ .
SICP 2 pts – If collected and checked. 1 pt – If just collected from Driller and not physically checked.
The Supervisor must check the data and not just take the figures from the Driller.
Minimum every minute important
Permeability setting has to allow a proper study of pressure build up.
Check depth and compare with the depth when SCR where taken
2 Physically check Pit Gain ‘Y/N Grading’ .
August 2017
AC-0018
Version 1.0
Page 12 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
8. Monitor BHP
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
(3) 3
The Driller must record the pressure on a trend sheet or blank paper and report it regularly to the Supervisor.
6. Monitor BHP Monitor surface pressures and report to Supervisor. Driller has to do it whether or not he/she receives instructions from Supervisor. ‘Y/N Grading’ .
Surface pressure
The Supervisor must instruct the Driller to monitor and record pressures and to advise Supervisor regularly.
Grading
NOTES Notes
(8) 5
NOTE: These instructions must be given before starting to complete the kill sheet. The Supervisor must complete a useable kill sheet. 3
5 pts – Instruct Driller to monitor pressure changes on both gauges, to avoid possible losses at the shoe and state why, e.g. to monitor for migration that may cause MAASP to be exceeded. 3 pts – If just asked to check that annular pressure is not reaching MAASP.
Complete a useable kill sheet 3 pts – If a useable kill sheet is completed within 15 minutes of collecting the shut in kick data.
Intervall must be given
Failure – If more than 15 minutes needed to complete a kill sheet, whether useable or not.
Check surface line number of strokes if WW
step down is a must if WW
and inform supervisor if close to MAASP
The Supervisor fails if a useable kill sheet is not completed within 15 minutes. The Supervisor can request an extra five minutes to correct a problem they notice on the kill sheet before it is handed to the assessor.
Kill mud weight, Initial Circulating Pressure (ICP), Final Circulating Pressure (FCP) and a Step down chart (a graph is optional). The assessor must check the kill sheet before the assessment continues. At this time there is to be no well control instructions communicated between the Driller and Supervisor.
Continue using the same snapshot.
AC-0018
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
5 minutes
A useable kill sheet shows the correct calculations for:
If the Supervisor fails at this point the assessor must take the role of Supervisor to allow the Driller to complete the assessment.
August 2017
15 minutes
Page 13 of 24
???? Realistic
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
8. Monitor BHP
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
(3) 3
The Driller must record the pressure on a trend sheet or blank paper and report it regularly to the Supervisor.
6. Monitor BHP Monitor surface pressures and report to Supervisor. Driller has to do it whether or not he/she receives instructions from Supervisor. ‘Y/N Grading’ .
Surface pressure
The Supervisor must instruct the Driller to monitor and record pressures and to advise Supervisor regularly.
Pts
NOTES Grading
Notes
(8) 5
NOTE: These instructions must be given before starting to complete the kill sheet. The Supervisor must complete a useable kill sheet. 3
5 pts – Instruct Driller to monitor pressure changes on both gauges, to avoid possible losses at the shoe and state why, e.g. to monitor for migration that may cause MAASP to be exceeded. 3 pts – If just asked to check that annular pressure is not reaching MAASP.
Complete a useable kill sheet 3 pts – If a useable kill sheet is completed within 15 minutes of collecting the shut in kick data.
Intervall must be given
Failure – If more than 15 minutes needed to complete a kill sheet, whether useable or not.
Check surface line number of strokes if WW
step down is a must if WW
and inform supervisor if close to MAASP
The Supervisor fails if a useable kill sheet is not completed within 15 minutes. The Supervisor can request an extra five minutes to correct a problem they notice on the kill sheet before it is handed to the assessor.
15 minutes
5 minutes
A useable kill sheet shows the correct calculations for: Kill mud weight, Initial Circulating Pressure (ICP), Final Circulating Pressure (FCP) and a Step down chart (a graph is optional). The assessor must check the kill sheet before the assessment continues. At this time there is to be no well control instructions communicated between the Driller and Supervisor.
???? Realistic
If the Supervisor fails at this point the assessor must take the role of Supervisor to allow the Driller to complete the assessment. Continue using the same snapshot.
August 2017
AC-0018
Version 1.0
Page 13 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
7. Well control instructions
(14)
Not applicable to Driller. The Supervisor gives the Driller well control instructions.
2
NOTE: All well control instructions must be given before beginning the Start-Up procedure.
10
Grading
Kill Method and specific instructions. 2 pts – If kill method given and satisfactory explanation of choice. 1 pt – If kill method given, but unsatisfactory explanation of choice e.g. Company policy W & W Method – Shoe position (open hole volume compares to internal string volume) Driller’s Method – Time to prepare kill mud. For the next five instructions ‘Y/N Grading’. Prepare Kill Mud ‘Y/N Grading’ . Start-Up procedure ‘Y/N Grading’ . Pump Follow Up (constant flow rate) ‘Y/N Grading’ . Driller to monitor pit gain during circulation ‘Y/N Grading’ . Instruct Driller to record pressures on a regular basis ‘Y/N Grading’ .
2
Reset Stroke Counters and record start time. 2 pts – If both actions performed. 1 pt – If only one action performed. 0 pts – If no actions performed.
August 2017
AC-0018
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
NOTES Notes The kill method and reason for choosing it must be given.
The Supervisor must tell the Driller the mud weight to be prepared in order to kill the well. Supervisor must give clear instructions as to Drillers role in the start-up procedure. Supervisor must inform Driller of the kill rate and that this is to be held constant following Start-up. Supervisor must inform Driller to maintain a log of pit level or gain during the kill. This must include how often e.g. every 100 strokes. Supervisor must inform Driller to maintain a log of drill pipe and casing pressures during the kill. This must include how often, e.g. every 100 strokes. The driller must be instructed to record the time and not just reset strokes at start of the kill. The Supervisor or Driller must reset the Remote Choke Panel Stroke Counter. Page 14 of 24
and pump
and action to take if leaking
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
Pts
7. Well control instructions
(14)
Not applicable to Driller. The Supervisor gives the Driller well control instructions.
2
NOTE: All well control instructions must be given before beginning the Start-Up procedure.
10
NOTES Grading
Notes
Kill Method and specific instructions. 2 pts – If kill method given and satisfactory explanation of choice. 1 pt – If kill method given, but unsatisfactory explanation of choice e.g. Company policy W & W Method – Shoe position (open hole volume compares to internal string volume) Driller’s Method – Time to prepare kill mud. For the next five instructions ‘Y/N Grading’. Prepare Kill Mud ‘Y/N Grading’ .
Pump Follow Up (constant flow rate) ‘Y/N Grading’ . Driller to monitor pit gain during circulation ‘Y/N Grading’ . Instruct Driller to record pressures on a regular basis ‘Y/N Grading’ . Reset Stroke Counters and record start time. 2 pts – If both actions performed. 1 pt – If only one action performed. 0 pts – If no actions performed.
August 2017
AC-0018
The Supervisor must tell the Driller the mud weight to be prepared in order to kill the well. Supervisor must give clear instructions as to Drillers role in the start-up procedure.
Start-Up procedure ‘Y/N Grading’ .
2
The kill method and reason for choosing it must be given.
Supervisor must inform Driller of the kill rate and that this is to be held constant following Start-up. Supervisor must inform Driller to maintain a log of pit level or gain during the kill. This must include how often e.g. every 100 strokes. Supervisor must inform Driller to maintain a log of drill pipe and casing pressures during the kill. This must include how often, e.g. every 100 strokes.
and pump
and action to take if leaking
The driller must be instructed to record the time and not just reset strokes at start of the kill. The Supervisor or Driller must reset the Remote Choke Panel Stroke Counter.
Version 1.0
Page 14 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
9. Start the kill procedure Check the line-up of the circulating system, adjusting if necessary.
Co-ordinate the start up with the Supervisor.
Inform the Supervisor when the kill rate is reached.
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
(7) 3
3
1
8. The kill procedure
Grading
NOTES Notes
(15) 3
Check circulating system in preparation for the kill method ‘Y/N Grading’ .
The Driller and Supervisor must check the manifolds.
Co-ordinate the start up with the Driller.
3
‘Y/N Grading’ .
The Supervisor must give instructions for the start-up and the Driller must follow them.
Maintain correct pressure.
5
Maintain correct pressure 5 pts – If good manipulation with reference to correct gauge. 3 pts – If constantly opening and closing the choke to maintain correct start-up pressure, or BHP falls below formation pressure during the start up. 0 pts – If not referring to the correct gauge.
For subsea assessments, CLF must be accounted for correctly.
Make allowance for any time delay.
4
Line up circulating system in preparation for the kill method ‘Y/N Grading’.
Check the line-up of the circulating system.
3 pts – If done according to Supervisor’s instructions with full communication. 1 pt – If done too quickly or with no communication. 0 pts – If Driller stops or decreases the pump speed without instructions.
check SL WW
‘Y/N Grading’.
4 pts – for steady choke. 2 pts – if constantly manipulating the choke. 0 pts – if BHP fluctuates above and below the formation pressure, without stabilising above the formation pressure. The Supervisor fails if the formation fractures at any time during the assessment. This usually happens during start up and shut down phases and when handling problem No. 4. The failure is first recorded at the point on the grading sheet where it happened and again at the end of the grading sheet where the point score is normally calculated. All sections in between must be left empty. Print off the plot/graph, have the failed candidate (Supervisor) sign the plot/graph and explain reason f or failure. The failed candidate then leaves the assessment room. The assessor now explains to the remaining candidate that the assessment will continue. Reload a new snapshot. The assessor takes the role of Supervisor to allow the Driller to complete the assessment. On completion of the assessment the remaining candidate (Driller) will need to sign both plots/graphs.
Why not continue ?
There must be a problem initiated during each assessment. If it is an L3 (Driller) candidate on their own with the assessor acting as the L4 (Supervisor), then BOP failure is the most applicable. If it is an L3 (Driller) only assessment and BOP failure has been used, then there is no need for an additional problem to be initiated during the kill phase.
or when not opening the choke when gas is evacuated
If there is an L4 (Supervisor) candidate, then a problem must be initiated during the kill phase. The simulator must be run at ‘real time’ speed until after the problem has been dealt with. A minimum of 250 strokes must be pumped in the kill phase before the problem is given.
August 2017
AC-0018
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Page 15 of 24
250 stokes before the problem is given
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
9. Start the kill procedure
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
(7)
Check the line-up of the circulating system, adjusting if necessary.
Co-ordinate the start up with the Supervisor.
Inform the Supervisor when the kill rate is reached.
3
3
1
Pts
8. The kill procedure
NOTES Grading
Notes
(15) 3
Check circulating system in preparation for the kill method ‘Y/N Grading’ .
The Driller and Supervisor must check the manifolds.
Co-ordinate the start up with the Driller.
3
‘Y/N Grading’ .
The Supervisor must give instructions for the start-up and the Driller must follow them.
Maintain correct pressure.
5
Maintain correct pressure 5 pts – If good manipulation with reference to correct gauge. 3 pts – If constantly opening and closing the choke to maintain correct start-up pressure, or BHP falls below formation pressure during the start up. 0 pts – If not referring to the correct gauge.
For subsea assessments, CLF must be accounted for correctly.
Make allowance for any time delay.
4
Line up circulating system in preparation for the kill method ‘Y/N Grading’.
Check the line-up of the circulating system.
3 pts – If done according to Supervisor’s instructions with full communication. 1 pt – If done too quickly or with no communication. 0 pts – If Driller stops or decreases the pump speed without instructions.
check SL WW
‘Y/N Grading’.
4 pts – for steady choke. 2 pts – if constantly manipulating the choke. 0 pts – if BHP fluctuates above and below the formation pressure, without stabilising above the formation pressure. The Supervisor fails if the formation fractures at any time during the assessment. This usually happens during start up and shut down phases and when handling problem No. 4. The failure is first recorded at the point on the grading sheet where it happened and again at the end of the grading sheet where the point score is normally calculated. All sections in between must be left empty. Print off the plot/graph, have the failed candidate (Supervisor) sign the plot/graph and explain reason f or failure. The failed candidate then leaves the assessment room. The assessor now explains to the remaining candidate that the assessment will continue. Reload a new snapshot. The assessor takes the role of Supervisor to allow the Driller to complete the assessment. On completion of the assessment the remaining candidate (Driller) will need to sign both plots/graphs.
Why not continue ?
There must be a problem initiated during each assessment. If it is an L3 (Driller) candidate on their own with the assessor acting as the L4 (Supervisor), then BOP failure is the most applicable. If it is an L3 (Driller) only assessment and BOP failure has been used, then there is no need for an additional problem to be initiated during the kill phase.
or when not opening the choke when gas is evacuated
If there is an L4 (Supervisor) candidate, then a problem must be initiated during the kill phase. The simulator must be run at ‘real time’ speed until after the problem has been dealt with. A minimum of 250 strokes must be pumped in the kill phase before the problem is given.
August 2017
AC-0018
Version 1.0
Page 15 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
250 stokes before the problem is given
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
Problem 1 - Total pump failure Inform the Supervisor and shut down on his instruction.
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
(5)
Problem 1 - Total pump failure
3
Driller has to recognise the pump has failed and inform the Supervisor, if not 0 pts.
2
2 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If he/she stops or decreases the pump speed without instructions.
Co-ordinate the restart with the Supervisor.
Take the correct action.
5
Recognise any sudden change in the pump pressure, inform the Supervisor and follow instructions.
Stop pump as requested by Supervisor and coordinate restart of operations with Supervisor.
(5)
2
2 pts – If additional influx less than 800 I (5 bbl). 0 pts – If additional influx greater than 800 I (5 bbl).
3
N/A
August 2017
Problem 2 - One bit nozzle plugged ‘Y/N Grading’.
Identify the problem and take the correct action.
3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions. If Supervisor doesn’t stop, deduct these three points for Driller from total maximum points.
AC-0018
Supervisor’s reaction has to be quick enough not to let BHP drop below formation pressure. 5 pts – If reaction of Supervisor doesn’t allow BHP to drop below formation pressure.
Give the appropriate instructions and co-ordinate the re-start with the Driller.
2
2 pts – Supervisor has to give instructions correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given.
(7)
5
Driller must and the supervisor must decide and descuss the new ICP Give appropriate instructions and co-ordinate the restart with the Driller.
NOTES Notes
(7)
Its unfare if the driller is the supervisor/assessor that he can not comunicate. Not realistic
Problem 2 - One bit nozzle plugged
Grading
2
Identify the problem and take the correct action (the Supervisor has to stop the circulation and review the cause of the problem). 5 pts – If reaction of Supervisor doesn’t allow BHP to drop below formation pressure and problem is correctly identified. 2 pts – If BHP is allowed to fall below formation pressure during reaction to problem. 0 pts – If problem is not identified correctly.
The Supervisor loses marks if the BHP drops below the formation pressure.
5 BBL
All this can not be done in real time if assessor is the driller
NOTE: Drill pipe pressure should increase by at least 100 psi. The correct action is to shut down and marks are lost if the Supervisor does not shut down. The Supervisor loses marks if the BHP drops below the formation pressure.
Give appropriate instructions 2 pts – Supervisor has to give instruction correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given. Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Page 16 of 24
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
Problem 1 - Total pump failure
(5)
Inform the Supervisor and shut down on his instruction.
SUPERVISOR (LEVEL 4) Grading
3
Driller has to recognise the pump has failed and inform the Supervisor, if not 0 pts.
2
2 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If he/she stops or decreases the pump speed without instructions.
Co-ordinate the restart with the Supervisor.
L4 Supervisor
Pts
Problem 1 - Total pump failure
(7)
Take the correct action.
5
Recognise any sudden change in the pump pressure, inform the Supervisor and follow instructions.
2
3
Stop pump as requested by Supervisor and coordinate restart of operations with Supervisor.
N/A
Problem 2 - One bit nozzle plugged ‘Y/N Grading’.
Identify the problem and take the correct action.
3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions. If Supervisor doesn’t stop, deduct these three points for Driller from total maximum points.
August 2017
Supervisor’s reaction has to be quick enough not to let BHP drop below formation pressure.
2 pts – If additional influx less than 800 I (5 bbl). 0 pts – If additional influx greater than 800 I (5 bbl). Give the appropriate instructions and co-ordinate the re-start with the Driller.
(5)
Notes
5 pts – If reaction of Supervisor doesn’t allow BHP to drop below formation pressure.
Its unfare if the driller is the supervisor/assessor that he can not comunicate. Not realistic
Problem 2 - One bit nozzle plugged
NOTES Grading
2
(7)
5
Driller must and the supervisor must decide and descuss the new ICP Give appropriate instructions and co-ordinate the restart with the Driller.
2 pts – Supervisor has to give instructions correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given.
2
Identify the problem and take the correct action (the Supervisor has to stop the circulation and review the cause of the problem). 5 pts – If reaction of Supervisor doesn’t allow BHP to drop below formation pressure and problem is correctly identified. 2 pts – If BHP is allowed to fall below formation pressure during reaction to problem. 0 pts – If problem is not identified correctly.
The Supervisor loses marks if the BHP drops below the formation pressure.
5 BBL
All this can not be done in real time if assessor is the driller
NOTE: Drill pipe pressure should increase by at least 100 psi. The correct action is to shut down and marks are lost if the Supervisor does not shut down. The Supervisor loses marks if the BHP drops below the formation pressure.
Give appropriate instructions 2 pts – Supervisor has to give instruction correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given.
AC-0018
Version 1.0
Page 16 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
Problem 3 - Choke wash-out
(5)
Stop the pump when instructed by the Supervisor and restart when instructed by the Supervisor.
2
Stop pump ‘Y/N Grading’ .
3
Co-ordinate restart 3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions.
inform
Problem 4 - Choke plugging Stop and restart the pump when instructed by the Supervisor.
Should warn the supervisor
Problem 3 - Choke wash-out Identify the problem and take the correct action.
(5) 2
Stop pump ‘Y/N Grading’ .
3
Co-ordinate restart 3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions.
AC-0018
5
Give appropriate instructions and co-ordinate the restart with Driller.
2
Problem 4 - Choke plugging
(7)
Identify the problem and take the correct action.
NOTES Notes
(7) Identify the problem and take the correct action (the Supervisor has to stop the circulation and review the cause of the problem). 5 pts – If reaction of Supervisor doesn’t allow BHP to drop below formation pressure and problem is correctly identified. 2 pts – If additional influx less than 800 I (5 bbl). 0 pts – If additional influx greater than 800 I (5 bbl).
The choke must wash out gradually and cause a steady reduction in casing and drill pipe pressures. The Supervisor loses marks if the BHP drops below the formation pressure.
5 BBL
2 pts – Supervisor has to give instruction correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given.
5
Identify the problem and take the correct action (the Supervisor has to stop the circulation and review the cause of the problem. 5 pts – If detected before opening choke by ¼ more and problem is correctly identified. 2 pts – If choke opened by more than ¼, or if BHP increases more than 500psi above pre-plugging value, or if BHP falls below formation pressure. 0 pts – If problem not identified.
Give appropriate instructions and co-ordinate the re-start with the Driller.
August 2017
Grading
2
2 pts – Supervisor has to give instruction correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given. Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
The choke should plug gradually and cause a steady increase in casing and drill pipe pressures. The Supervisor loses marks if the BHP increases more than 500 psi above the formation pressure or BHP falls below formation pressure.
1/4 500 psi
Page 17 of 24
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
Problem 3 - Choke wash-out
(5)
Stop the pump when instructed by the Supervisor and restart when instructed by the Supervisor.
2
Stop pump ‘Y/N Grading’ .
3
Co-ordinate restart 3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions.
inform
Problem 4 - Choke plugging Stop and restart the pump when instructed by the Supervisor.
Problem 3 - Choke wash-out Identify the problem and take the correct action.
(5) 2
Stop pump ‘Y/N Grading’ .
3
Co-ordinate restart 3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions.
Should warn the supervisor
NOTES Grading
Notes
(7) 5
Identify the problem and take the correct action (the Supervisor has to stop the circulation and review the cause of the problem). 5 pts – If reaction of Supervisor doesn’t allow BHP to drop below formation pressure and problem is correctly identified. 2 pts – If additional influx less than 800 I (5 bbl). 0 pts – If additional influx greater than 800 I (5 bbl).
Give appropriate instructions and co-ordinate the restart with Driller.
2
Problem 4 - Choke plugging
(7)
Identify the problem and take the correct action.
The choke must wash out gradually and cause a steady reduction in casing and drill pipe pressures. The Supervisor loses marks if the BHP drops below the formation pressure.
5 BBL
2 pts – Supervisor has to give instruction correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given.
5
Identify the problem and take the correct action (the Supervisor has to stop the circulation and review the cause of the problem. 5 pts – If detected before opening choke by ¼ more and problem is correctly identified. 2 pts – If choke opened by more than ¼, or if BHP increases more than 500psi above pre-plugging value, or if BHP falls below formation pressure. 0 pts – If problem not identified.
Give appropriate instructions and co-ordinate the re-start with the Driller.
August 2017
Pts
2
AC-0018
2 pts – Supervisor has to give instruction correctly. 1 pt – If this is not done correctly. 0 pts – If no instructions given. Version 1.0
The choke should plug gradually and cause a steady increase in casing and drill pipe pressures. The Supervisor loses marks if the BHP increases more than 500 psi above the formation pressure or BHP falls below formation pressure.
1/4 500 psi
Page 17 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
Grading
NOTES Notes
When the kill has been restarted after the problem has been resolved, the simulator speed can be increased to bring the gas to the surface more quickly. The Supervisor must have the kill under control and confirm this to the assessor before the speed is increased. The simulator must be returned to normal speed at least 100 strokes before the gas reaches the BOP. The assessor must inform the Supervisor that the simulator is running at normal speed. There is no need for the Driller to record pressures during the accelerated phase but this must be resumed when the simulator speed is returned to normal. 10. Monitor circulation (8) 9/10 BHP control since start (5) up 4 Maintain the pump speed, ‘Y/N Grading’. record pressures and pit level. Maintain the BHP, during and 5 5 pts – If BHP greater than or NOTE: The Supervisor loses after evacuation of the influx. equal to formation pressure marks if the BHP drops below 4 Advise the Supervisor. ‘Y/N Grading’ . during evacuation of influx and the formation pressure, immediately after mud returns excluding any start-up and NOTE: The Driller must record to surface. shutdown operations (e.g. data and report to the 2 pts – If any influx less than during a well control Supervisor regularly during the 800 litres (5 bbl). problem). complete kill (except the time 0 pts – If any influx greater when the simulator speed was than 800 litres (5 bbl). NOTE: If the Supervisor increased). fractures the formation when the gas is evacuated or when the mud returns are reestablished, the well must still be shut in under instruction so the Driller can finish off the 5 BBL assessment (see section 11 below). There is no need to reload a snapshot for this.
11. After evacuation of influx
(4)
Shut in under instruction and advise the Supervisor when the pump is off.
3
NOTE: The Driller must shut in, follow the Supervisor’s instructions and advise when the pump is off.
August 2017
1
3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions. Inform Supervisor when pump is stopped ‘Y/N Grading’.
AC-0018
11. After evacuation of initial influx
(10)
Co-ordinate the shutdown with the Driller.
3
Shut the well in. BHP must stay above formation pressure. ‘Y/N Grading’ .
The Supervisor loses marks if the BHP drops below the formation pressure.
Interpret the pressures and explain how to continue.
2
Check pressure and interpretation of gauge readings: 2 pts – Supervisor has to explain the Shut in Drill Pipe and Casing Pressure readings and relate them to any overall difference between actual BHP and formation pressure.
Gauges must be interpreted:
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
The Drillers’ Method Shut In Drill Pipe Pressure (SIDPP) should equal the original SIDPP - if not, the Supervisor must explain why not, (such as trapped pressure or not removing the
Page 18 of 24
I belive its better assessor and supervisor agree on the speed and that the supervisor must not touch the choke if not in real time and ask for real time if he want to make any adjustment
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
Pts
NOTES Grading
Notes
When the kill has been restarted after the problem has been resolved, the simulator speed can be increased to bring the gas to the surface more quickly. The Supervisor must have the kill under control and confirm this to the assessor before the speed is increased. The simulator must be returned to normal speed at least 100 strokes before the gas reaches the BOP. The assessor must inform the Supervisor that the simulator is running at normal speed. There is no need for the Driller to record pressures during the accelerated phase but this must be resumed when the simulator speed is returned to normal. 10. Monitor circulation (8) 9/10 BHP control since start (5) up 4 Maintain the pump speed, ‘Y/N Grading’. record pressures and pit level. Maintain the BHP, during and 5 5 pts – If BHP greater than or NOTE: The Supervisor loses after evacuation of the influx. equal to formation pressure marks if the BHP drops below 4 Advise the Supervisor. ‘Y/N Grading’ . during evacuation of influx and the formation pressure, immediately after mud returns excluding any start-up and NOTE: The Driller must record to surface. shutdown operations (e.g. data and report to the 2 pts – If any influx less than during a well control Supervisor regularly during the 800 litres (5 bbl). problem). complete kill (except the time 0 pts – If any influx greater when the simulator speed was than 800 litres (5 bbl). NOTE: If the Supervisor increased). fractures the formation when the gas is evacuated or when the mud returns are reestablished, the well must still be shut in under instruction so the Driller can finish off the 5 BBL assessment (see section 11 below). There is no need to reload a snapshot for this.
11. After evacuation of influx
(4)
Shut in under instruction and advise the Supervisor when the pump is off.
3
NOTE: The Driller must shut in, follow the Supervisor’s instructions and advise when the pump is off.
1
3 pts – If done according to Supervisor’s instructions. 1 pt – If done too quickly. 0 pts – If Driller stops or decreases the pump speed without instructions. Inform Supervisor when pump is stopped ‘Y/N Grading’.
August 2017
11. After evacuation of initial influx
(10)
Co-ordinate the shutdown with the Driller.
3
Shut the well in. BHP must stay above formation pressure. ‘Y/N Grading’ .
The Supervisor loses marks if the BHP drops below the formation pressure.
Interpret the pressures and explain how to continue.
2
Check pressure and interpretation of gauge readings: 2 pts – Supervisor has to explain the Shut in Drill Pipe and Casing Pressure readings and relate them to any overall difference between actual BHP and formation pressure.
Gauges must be interpreted:
AC-0018
Version 1.0
The Drillers’ Method Shut In Drill Pipe Pressure (SIDPP) should equal the original SIDPP - if not, the Supervisor must explain why not, (such as trapped pressure or not removing the
Page 18 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
L3 Driller
DRILLER (LEVEL3) Pts
SUPERVISOR (LEVEL 4) L4 Supervisor Pts
Grading
Grading
0 pts – If Supervisor does not give this information.
NOTES Notes safety margin when shutting in). The Shut In Casing Pressure (SICP) should equal the SIDPP - if not, the Supervisor must explain why not, (such as further influx). The Wait and Weight Method The SIDPP should be zero if not, the Supervisor must explain why not, (such as trapped pressure or not removing the safety margin when shutting in or wrong kill mud weight).
5 Supervisor must explain how to continue with circulation 5 pts – If well is clean: Continue with 2nd circulation Driller’s Method. If there is some noticeable gas: Either evacuate the gas using 1st circulation Driller’s Method or start Weight & Wait Method. 0 pts – If there is some noticeable gas but candidate wants to continue with 2 nd circulation Driller’s Method. Overall influx
An explanation of how the kill is to be continued: The Drillers’ Method Carry out a second circulation to replace old mud with kill mud. Reference can be made to the step down chart or graph. The Wait and Weight Method Continue pumping until the kill mud returns to the surface and shut in pressures are zero.
(5)
Not applicable to Driller.
8 BBL F
No more than 8 bbl extra influx has been let in since the start of the kill.
5
Check that cumulative additional influx volume does not exceed allowed volume.
The Supervisor is an instant fail if more than 8 bbl of additional influx is let in during the kill operation.
5 pts – If volume is less than 1280 litres (8 bbl). Failure – If volume is greater than 1280 litres (8 bbl).
Advise the candidates that the practical assessment is now finished. Complete the scoring and print out the log/graph before giving the de-brief.
August 2017
AC-0018
Version 1.0
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Page 19 of 24
I belive its better assessor and supervisor agree on the speed and that the supervisor must not touch the choke if not in real time and ask for real time if he want to make any adjustment
Practical Assessor Handbook DRILLER (LEVEL3) L3 Driller
Pts
SUPERVISOR (LEVEL 4) Grading
L4 Supervisor
Pts
NOTES Grading
0 pts – If Supervisor does not give this information.
Notes safety margin when shutting in). The Shut In Casing Pressure (SICP) should equal the SIDPP - if not, the Supervisor must explain why not, (such as further influx). The Wait and Weight Method The SIDPP should be zero if not, the Supervisor must explain why not, (such as trapped pressure or not removing the safety margin when shutting in or wrong kill mud weight).
5 Supervisor must explain how to continue with circulation 5 pts – If well is clean: Continue with 2nd circulation Driller’s Method. If there is some noticeable gas: Either evacuate the gas using 1st circulation Driller’s Method or start Weight & Wait Method. 0 pts – If there is some noticeable gas but candidate wants to continue with 2 nd circulation Driller’s Method. Overall influx
An explanation of how the kill is to be continued: The Drillers’ Method Carry out a second circulation to replace old mud with kill mud. Reference can be made to the step down chart or graph. The Wait and Weight Method Continue pumping until the kill mud returns to the surface and shut in pressures are zero.
(5)
Not applicable to Driller. No more than 8 bbl extra influx has been let in since the start of the kill.
8 BBL F
5
Check that cumulative additional influx volume does not exceed allowed volume.
The Supervisor is an instant fail if more than 8 bbl of additional influx is let in during the kill operation.
5 pts – If volume is less than 1280 litres (8 bbl). Failure – If volume is greater than 1280 litres (8 bbl).
Advise the candidates that the practical assessment is now finished. Complete the scoring and print out the log/graph before giving the de-brief.
August 2017
AC-0018
Version 1.0
Page 19 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook The plot/graph A plot/graph must be printed out and sent to IWCF for every practical assessment. assessment, the assessor must:
At the end of the
print out one colour copy, which covers the complete assessment. if it is a Level 4 candidate only and the assessor loads a snapshot after the drill floor preparation phase, print out a colour graph, which shows the drill floor preparation phase and another, which shows the kill phase, if a candidate is an instant fail and a new snapshot has to be loaded, print out a colour graph before the new snapshot is loaded and another at the end of the assessment,. ensure candidate(s) and the assessor sign all plots/graphs.
Calcul ating the final scores When the assessment has finished, the assessor must determine the final score for each candidate by:
adding up the total marks scored on each page and writing the total at the bottom of each page of the grading sheet in the page total box; alternatively, this can be done during the assessment. adding each page total together to get the total marks scored and writing the total in the exercise total box on the last page of the grading sheet. calculating the total marks scored as a percentage by dividing the total marks scored by the total marks available and then multiply by 100. The percentage scored is rounded down to the nearest whole number:
In addition:
A score of 69.9 is rounded down to 69% A score of 71.2 is rounded down to 71%.
Practical Assessor Handbook The plot/graph A plot/graph must be printed out and sent to IWCF for every practical assessment. assessment, the assessor must:
At the end of the
print out one colour copy, which covers the complete assessment. if it is a Level 4 candidate only and the assessor loads a snapshot after the drill floor preparation phase, print out a colour graph, which shows the drill floor preparation phase and another, which shows the kill phase, if a candidate is an instant fail and a new snapshot has to be loaded, print out a colour graph before the new snapshot is loaded and another at the end of the assessment,. ensure candidate(s) and the assessor sign all plots/graphs.
Calcul ating the final scores When the assessment has finished, the assessor must determine the final score for each candidate by:
adding up the total marks scored on each page and writing the total at the bottom of each page of the grading sheet in the page total box; alternatively, this can be done during the assessment. adding each page total together to get the total marks scored and writing the total in the exercise total box on the last page of the grading sheet. calculating the total marks scored as a percentage by dividing the total marks scored by the total marks available and then multiply by 100. The percentage scored is rounded down to the nearest whole number:
A score of 69.9 is rounded down to 69% A score of 71.2 is rounded down to 71%.
In addition:
The candidate must score 70% or more to pass. The final percentage mark must be written in the appropriate place on the first and last page of the grading sheet. The assessor must sign the first page of the grading sheet when the final score has been added. The assessor has the ability to transfer the marks from the grading sheet to the appropriate section of FORUM.
Debrief the candidates When the assessment has finished and before the candidates leave the assessment room, the assessor must:
give candidates their final score. discuss the assessment exercise with the candidates and use the grading sheet and graph to highlight their strengths and weaknesses. if they fail, give candidates their re-sit options, detailed in Section 7 and answer any questions from the candidates.
7. Re-sit opti ons for the practi cal assessment In order to pass the IWCF practical assessment, a candidate needs to achieve a minimum of 70%. If a candidate fails their first attempt at the practical assessment, then they can take one re-sit before they try the written examinations. If a candidate fails their second attempt, (first re-sit), of the practical assessment, they must try the written examinations and pass at least one component before they try a third and final attempt of the practical assessment. If the candidate fails their second attempt, (first re-sit), of the practical assessment and fails both written examinations, then they cannot progress any further and must re-register as a new candidate.
August 2017
AC-0018
Version 1.0
Page 20 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook If the candidate passes their second attempt, (first re-sit), of the practical assessment, the y must pass at least one of the written examinations or the results of the second attempt will not stand. Please refer to Appendix 1 for further clarification on the re-sit criteria.
8. Completin g the paperwork Paperwork sent to IWCF The following practical assessment documentation must be uploaded to FORUM for each candidate:
A colour copy of the plot/graph signed by candidates and the assessor. A copy of the appropriate practical assessment grading sheet. A copy of the kill sheet if it is an L4 (Supervisor) candidate.
Retention of candid ate records The following practical assessment documentation must be securely stored at the Primary Centre for the duration of the candidate’s certification:
The original copy of the plot/graph signed by candidates and assessor. The original practical assessment grading sheet. The original L4 Supervisor kill sheet.
9. Grading sheets IWCF practical assessments must be scored using the current IWCF grading sheets for each step of the assessment. Scoring must be done as outlined in the guidance given in this document; assessors have no flexibility to adjust the scoring. The most up-to-date versions can be found on the IWCF website. Printed copies cannot be guaranteed as being current. It is the responsibility of the assessor to ensure they are using the correct grading sheet. The current grading sheets are:
Practical Assessment Grading Sheet – Surface BOP Operations Practical Assessment Grading Sheet – Subsea BOP Operations
The following sample page shows how the grading sheet must be scored, marked and completed.
August 2017
AC-0018
Version 1.0
Page 21 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook Pts.
LEVEL 3 (DRILLER)
0
1
(4)
1.
1
Line up stand pipe manifold.
1
Line up choke manifold.
Set up BOP panel (including all gauges).
2
2
3
4
5
Scor e
Pts.
LEVEL 4 (SUPERVISOR)
1
0
2
4
5
Scor e
Not on drill floor 1. Check drill floor set-up
1
Choke manifold.
1
1
BOP panel
- Position of BOPs and valves.
1
- All gauges.
1
(10)
1
Prepare to drill
2
(4)
Record kill rate circulating pressures as requested by Supervisor or on Driller's own initiative.
2.
4
4 3.
3
2
Set chok e posi tion Set remote or manually operated choke in accordance with instructions.
(2)
2
1
1 2.
1
Prepare dril l floor
(3)
(1)
0
1
6
August 2017
Reason for choice of shut-in procedure.
Action to take in case of a drilling break and/or influx detection.
4 2
4
2
PAGE TOTAL
Procedures to follow to shut the well in, and check choke position.
3. Instruct Driller to record kill rate circulating pressure at given pump speeds
1
7
Instructions
Pump n° 1
1st kill rate circulating pressure.
1
2nd kill rate circulating pressure.
0
Pump n° 2
1
1st kill rate circulating pressure.
1
1
2nd kill rate circulating pressure.
0
17
AC-0018
15
PAGE TOTAL
Version 1.0
Page 22 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
10. Assessor accreditation Assessors must maintain their accreditation with IWCF every two years by submitting a Practical Assessor and Instructor Application Form Renewal. The requirements of this are summarised as:
Maintain a current IWCF Drilling Well Control Certificate at level 4 in the highest level programme that they intend to assess, (for example, surface BOP or combined surface and subsea BOP). The assessor must achieve at least 90% in each assessment. Submit evidence they have conducted four practical assessments at level four. Applicants for surface BOP assessor accreditation must submit copies of four surface BOP practical assessments on IWCF candidates. Applicants for combined surface and subsea assessor accreditation must submit four practical assessments of which a minimum of two must be subsea BOP practical assessments on IWCF candidates. Each of the four practical assessments must cover a different one of the four problems set in the IWCF Practical Assessment programme.
The evidence required for each practical assessment is as follows:
A copy of the L4 grading sheet A copy of the signed plot/graph (colour) A copy of the L4 (Supervisors) completed kill sheet.
In addition to the assessment evidence above, the following must also be sent in with the application:
The assessor ’s current Curriculum Vitae A copy of the assessor’s passport page which contains the photograph A current passport style photograph.
The Practical Assessor Application Form Renewal must be submitted within 90 days of the assessor’s certification/accreditation expiry date. If this is received after the 90 days, the assessor must submit a new application. Please allow 20 working days for IWCF to process the renewal. The expiry date of an assessor’s accreditation is governed by the date their IWCF certification expires.
Practical Assessor Handbook
10. Assessor accreditation Assessors must maintain their accreditation with IWCF every two years by submitting a Practical Assessor and Instructor Application Form Renewal. The requirements of this are summarised as:
Maintain a current IWCF Drilling Well Control Certificate at level 4 in the highest level programme that they intend to assess, (for example, surface BOP or combined surface and subsea BOP). The assessor must achieve at least 90% in each assessment. Submit evidence they have conducted four practical assessments at level four. Applicants for surface BOP assessor accreditation must submit copies of four surface BOP practical assessments on IWCF candidates. Applicants for combined surface and subsea assessor accreditation must submit four practical assessments of which a minimum of two must be subsea BOP practical assessments on IWCF candidates. Each of the four practical assessments must cover a different one of the four problems set in the IWCF Practical Assessment programme.
The evidence required for each practical assessment is as follows:
A copy of the L4 grading sheet A copy of the signed plot/graph (colour) A copy of the L4 (Supervisors) completed kill sheet.
In addition to the assessment evidence above, the following must also be sent in with the application:
The assessor ’s current Curriculum Vitae A copy of the assessor’s passport page which contains the photograph A current passport style photograph.
The Practical Assessor Application Form Renewal must be submitted within 90 days of the assessor’s certification/accreditation expiry date. If this is received after the 90 days, the assessor must submit a new application. Please allow 20 working days for IWCF to process the renewal. The expiry date of an assessor’s accreditation is governed by the date their IWCF certification expires.
11. Auditing The practical assessor’s performance and record will be audited during the routine, regular audits of the Asse ssment Centre.
In addition, the assessor may be audited at any time at the discretion of the IWCF. The materials submitted to the IWCF by the assessor on completion of each candidate assessment are subject to audit by the IWCF. If non-conformances are found during an audit, the IWCF assessor will be asked to take corrective action, which may include re-training, suspension or termination of their accreditation. Corrective action requests may also be issued to the accredited centre concerned.
12. Reference documentatio n The following documents can be downloaded from the IWCF website – www.iwcf.org
Practical Assessment – Notice to Candidates Practical Assessment – Notice to Assessors Well Design Rules Practical Assessment Grading Sheet – Surface BOP Operations Practical Assessment Grading Sheet – Subsea BOP Operations IWCF Kill Sheet - Surface and Subsea various units Practical Assessor and Instructor Application Form Renewal.
13. Contacting IWCF All queries relating to IWCF practical assessors and practical assessment procedures must be directed to
[email protected] or call (+44) 01674 678120. August 2017
AC-0018
Version 1.0
Page 23 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document
Practical Assessor Handbook
1. Appendi x 1 – Practical assessment re-sit opti ons
START
Failed initial practical assessment achieving < 70%
N
Applicant can proceed to written papers
Y
Failed first practical assessment re-sit achieving < 70%.
N
Applicant can proceed to written papers
N
Not eligible for a re-sit, must wait 90 days from initial test date. Applicant can then re-register as a new candidate
Applicant must achieve ≥ 70% in at least one written paper for practical assessment re-sit mark to stand
Y
Applicant must proceed to written papers
Passes at least one written paper ≥ 70%
Y Applicant can proceed and attempt the second practical assessment re-sit
August 2017
AC-0018
Version 1.0
Page 24 of 24
Printed copies are UNCONTROLLED: It is the user’s responsibility to verify printed material against the controlled document