Foreword Welcome to value-conscious company. We are proud of the advanced engineering and quality construction of each equipment we manufacture. This manual explains the working of equipment. Please read it thoroughly and have all the occupants follow the instructions carefully. Doing so will help you enjoy many years of safe and trouble free operation. When it comes to service remember that K.C. Engineers knows your equipment best and is interested in your complete satisfaction. We will provide the quality maintenance and any other assistance you may require. All the information and specifications in this manual are current at the time of printing. However, Because of K.C. Engineers policy of continual product improvement we reserve the right to make changes at any time without notice. Please note that this manual explains all about the equipment including options. Therefore you may find some explanations for options not installed on your equipment. You must follow the instructions and maintenance instructions given in the manual carefully to avoid possible injury or damage. Proper maintenance will help ensure maximum performance, greater reliability and longer life for the product.
K.C. Engineers
Flow Control Trainer
1
FLOW CONTROL TRAINER INTRODUCTION: Currently, the PID algorithm is the most common control algorithm used in industry. Often, people use PID control processes that include heating and cooling systems, fluid flow monitoring, flow control and temperature control. In PID control, you must specify a process variable and a set point. The process variable is the system parameter you want to control such as temperature, pressure and flow rate and the set point is the desired value for the parameter you are controlling. A PID controller determines a controller output value, such as the heater power or valve position. The controller applies the controller output value to the system, which in turn drives the process variable towards the set point value.
CONTROL SYSTEM: The control system is that means by which any quantity of interest in a machine, mechanism or equipment is maintained or altered in accordance with a desired manner. Control system is of two types: 1. OPEN LOOP CONTROL SYSTEM:
It is shown in figure1. Any physical system, which doesn’t automatically correct for variation in its output, is called open loop system. In these systems, the output remains constant for a constant input signal provided the external; conditions remain unaltered. The output may be changed to any desired value by appropriately changing the input signal but variations in external or internal parameters of the system may cause the output to vary from the desired value in an uncontrolled fashion. The open loop control is, therefore, satisfactory only if such fluctuations can be tolerated or system components are designed and constructed so as to limit parameter variations and environmental conditions as well c ontrolled. Input
Controller
Plant
Output
Fig. 1: Open Loop
It is important to note that the fundamental difference between an open and closed loop control system is that of a feedback action. Consider, for example, traffic control system for regulating the flow of traffic at the crossing of two roads. The system will be termed open loop if red and green lights are put on by a timer mechanism set for predetermined fixed Flow Control Trainer
2
FLOW CONTROL TRAINER INTRODUCTION: Currently, the PID algorithm is the most common control algorithm used in industry. Often, people use PID control processes that include heating and cooling systems, fluid flow monitoring, flow control and temperature control. In PID control, you must specify a process variable and a set point. The process variable is the system parameter you want to control such as temperature, pressure and flow rate and the set point is the desired value for the parameter you are controlling. A PID controller determines a controller output value, such as the heater power or valve position. The controller applies the controller output value to the system, which in turn drives the process variable towards the set point value.
CONTROL SYSTEM: The control system is that means by which any quantity of interest in a machine, mechanism or equipment is maintained or altered in accordance with a desired manner. Control system is of two types: 1. OPEN LOOP CONTROL SYSTEM:
It is shown in figure1. Any physical system, which doesn’t automatically correct for variation in its output, is called open loop system. In these systems, the output remains constant for a constant input signal provided the external; conditions remain unaltered. The output may be changed to any desired value by appropriately changing the input signal but variations in external or internal parameters of the system may cause the output to vary from the desired value in an uncontrolled fashion. The open loop control is, therefore, satisfactory only if such fluctuations can be tolerated or system components are designed and constructed so as to limit parameter variations and environmental conditions as well c ontrolled. Input
Controller
Plant
Output
Fig. 1: Open Loop
It is important to note that the fundamental difference between an open and closed loop control system is that of a feedback action. Consider, for example, traffic control system for regulating the flow of traffic at the crossing of two roads. The system will be termed open loop if red and green lights are put on by a timer mechanism set for predetermined fixed Flow Control Trainer
2
intervals of time. It is obvious that such an arrangement takes no account of varying rates of traffic flowing to the road crossing from the two directions. If on the other hand a scheme is introduced in which the rate of traffic flow along both directions are measured and are compared and the difference is used to control the timings of the red and green lights, a closed-loop system results. Thus, the concept of feedback can be usefully employed to traffic control. Unfortunately, the feedback, which is the underlying principle of most control systems, introduces the possibility of undesirable system oscillations.
2. CLOSED LOOP CONTROL SYSTEM:
A closed loop control system consists of a process and a controller that automatically adjusts one of the inputs to the process in response to a signal feedback from the process output. The performance of the system can be judged by the transient response of the output to specific changes in the input. The change in the input may be a change in set point or a change in any one of the several load variables. If the purpose of the control system is to make the process follow changes in set point as closely as possible, the operation is called “servo-operation”. The term “regulator operation” is used when the main problem is to keep the output almost constant in spite of changes in load. The designer must be aware of the purpose of the control system, since the system that gives optimum servo-operation will generally not be the best for regulator operation.
DEFINITIONS: th
(Referred from Modern control Engineering By Katsuhiko Ogata, 4 edition, page no.
2 and Control system engineering By I.J Nagrath and M.Gopal, 3
rd
edition, page no. 195)
CONTROLLED VARIABLE & MANIPULATED VARIABLE: The controlled variable is the quantity or condition that is measured and controlled. The-manipulated variable is the quantity or condition that is varied by the controller so as to affect the value of the controlled variable. Normally, the controlled variable is the output of the system. Control means measuring the value of the controlled variable of the system and applying the manipulated variable to the system to correct or limit deviation of the measured value from a desired value.
Flow Control Trainer
3
PLANTS: A plant may be a piece of equipment, perhaps just a set of machine parts functioning together, the purpose of which is to perform a particular operation.
PROCESSES: A process may be defined as natural, progressively continuing operation or development marked by a series of gradual changes that succeed one another in relatively fixed way and leads toward a particular result or end; or an artificial or voluntary, progressively continuing operation that consists of a series of controlled actions or movements systematically directed towards a particular result.
SYSTEMS: A system is a combination of components that act together and perform a certain objective. A system is not limited to physical ones. The concept of system can be applied to abstract, dynamic phenomena such as those encountered in economics. The word system should therefore, be interpreted to imply physical, biological, economic and the like systems.
DISTURBANCES: A disturbance is a signal that tends to adversely affect the value of the output of a system. If a disturbance is generated within the system, it is called internal, while the external disturbance is generated outside the system and is an input.
FEEDBACK CONTROL: Feedback control refers to an operation that, in the presence of disturbance tends to reduce the difference between the output of a system and some reference input and does so on the basis of this difference. Here only the unpredictable or known disturbances can always be compensated for within the system.
DELAY TIME: It is the time required for the response to reach 50% of the final value in first attempt. It is represented by td. It is shown s hown in figure 2.
Flow Control Trainer
4
Tc(t)
e c n a r e l o T e l b a w o l l A
Mp 1.0
0.5
Ttd
Tt
Ttr Ttp Figure : 2
R ISE TIME: It is the time required for the response to rise from 10% to 90% of the final value for over damped systems and 0 to 100% of the final value for under damped systems. It is shown in figure 2.
PEAK TIME: It is the time required for the response to reach the peak of time response or the peak overshoot. It is represented by ts. It is shown in figure 2.
PEAK OVERSHOOT MP: It indicates the normalized difference between the time response peak and the steady output and is defined as: Peak percent overshoot = [C tp – C∞/C∞] x 100% The M p is represented in figure 2.
SETTING TIME: It is the time required for the response to reach and stay within a specified tolerance band (Usually 2% to 5%) of its final value. It is represented by ts in figure 2
Flow Control Trainer
5
INTRODUCTION TO PID CONTROL EQUATIONS: This section will show you the characteristics of the each of proportional (P), the integral (I), and the derivative (D) controls, and how to use them to obtain a desired response. In this section, we will consider the fo llowing feedback system: R
e
Controller
_
+
u
Plant
Y
PLANT: System to be controlled.
CONTROLLER: Provides the excitation for the plant; Designed to control the overall system behavior.
THE THREE-TERM CONTROLLER The transfer function of the PID controller looks like the following:
Kc +
Ti s
+ Tds =
Tds 2 + Kcs + Ti
K c =
Proportional gain
Ti =
Integral gain
Td =
Derivative gain
s
First, let's take a look at how the PID controller works in a closed-loop system using the schematic shown above. The variable (e) represents the tracking error, the difference between the desired input value (R) and the actual output (Y). This error signal (e) will be sent to the PID controller, and the controller computes both the derivative and the integral of this error signal. The signal (u) just past the controller is now equal to the proportional gain (Kc) times the magnitude of the error plus the integral gain (Ti) times the integral of the error plus the derivative gain (Td) times the derivative of the error. u = Kc × e + Ti ∫ edt + Td
de dt
This signal (u) will be sent to the plant, and the new output (Y) will be obtained. This new output (Y) will be sent back to the sensor again to find the new error signal (e). The controller takes this new error signal and computes its derivative and its integral again. This process goes on until the error becomes equal to zero.
Flow Control Trainer
6
THE CHARACTERISTICS OF P, I, AND D CONTROLLERS: A proportional controller (Kc) will have the effect of reducing the rise time and will reduce, but never eliminate, the steady state. An integral control (K i) will have the effect of eliminating the steady-state error, but it may make the transient response worse. A derivative control (K d) will have the effect of increasing the stability of the system, reducing the overshoot, and improving the transient response. Effects of each of controllers Kc, Ti, and Td on a closed-loop system are summarized in the table shown below. Controller Response
Rise Time
Overshoot Settling Time Steady-State Error
K c
Decrease
Increase
Small Change Decrease
Ti
Decrease
Increase
Increase
Eliminate
Td
Small Change
Decrease
Decrease
Small Change
Note that these correlations may not be exactly accurate, because Kc, Ti, and Td are dependent of each other. In fact, changing one of these variables can change the effect of the other two. For this reason, the table should only be used as a reference when you are determining the values for K c, Ti and Td.
GENERAL TIPS FOR DESIGNING A PID CONTROLLER: When you are designing a PID controller for a given system, follow the steps shown below to obtain a desired response.
1. Obtain an open-loop response and determine what needs to be improved. 2. Add a proportional control to improve the rise time. 3. Add an integral control to eliminate the steady-state error. 4. Add a derivative control to improve the overshoot. 5. Adjust each of Kc, Ti, and Td until you obtain a desired overall response. Lastly, please keep in mind that you do not need to implement all three controllers (proportional, derivative, and integral) into a single system, if not necessary. For example, if a PI controller gives a good enough response, then you don't need to implement derivative controller to the system. Keep the controller as simple as possible to obtain the system with no overshoot, fast rise time, and no steady-state error.
Flow Control Trainer
7
VARIOUS TYPES OF CONTROLS: (Referred from Process control By Peter Harriott, page no. 6)
1. PROPORTIONAL CONTROL: The cycling inherent with the on-off control would be objectionable for most processes. To get steady operation when the disturbances are absent, the controlled variable must be a continuous function of error. With proportional control, the most widely used type; the controller output is a linear function of the error signal. The controller gain is the fractional change in output divided by the fractional change in input. P = Kc* e -------------------------(1) Where: P
=
fractional change in controller output,
e
=
fractional change in the error.
Kc
=
controller gain.
The control action can also be expressed by the proportional bandwidth B. The bandwidth is the error needed to cause a 100% change in the controller output, and it is usually expressed as a percentage of the chart width. A bandwidth of 50% means that controller output would go from 0 to 1 for an error equal to 50% of the chart width or from, say, 0.5 to 0.6 for an error of 5%. B = 1/Kc * 100 ------------------(2) Some pneumatic controllers are calibrated in sensitivity units, or pounds per square inch per inch of the pen travel. For a standard controller with a 3 to 15 psi range and a 4-inch chart, the gain and sensitivity are related by equation: S = 3Kc psi/inch ------------------------(3)
2 PROPORTIONAL + INTEGRAL CONTROL: This mode of control is described by the relationship: P = Kc × e +
Kc Ti
∫ edt + Ps − − − − − − − − − − − (4)
Where: Kc
=
gain
Ti
=
integral time, seconds
Ps
=
constant
Flow Control Trainer
8
P
=
output
In this case, we have added to the proportional action term, Kc * e, another term that is proportional to the integral of the error. There is no offset with the integral control, since the output keeps changing as long as any error persists. However, the initial response to an error is slow and proportional control is ordinarily used with integral control. The integral action corrects for the offset that usually occurs with proportional control only, and the effect is similar to manual adjustment or resetting of the set point after each load change. The terms “ reset action” and “reset time” are widely used to characterize the integral action of a proportional – integral controller. P = Kc (e +
1 Ti
∫ dt ) − − − − − − − − − − − − − −(5)
Where: Ti
=
reset time
Kc
=
gain
P
=
output
3. PROPORTIONAL + DERIVATIVE (PD) CONTROL: This mode of control may be represented by: P = Kc × e + KcTd Where:
de dt
− − − − − − − − − − − − (6)
Kc
=
gain
Td
=
derivative time, seconds
P
=
output
In this case, we have added to the proportional term another term, KcTd (de/dt) that is proportional to the derivative of the error. Other terms that are used to describe the derivative action are rate control and anticipatory control . Derivative action is often added to proportional control to improve the response of slow systems. By increasing the output when the error is changing rapidly, derivative action anticipates the effect of large load changes and reduces the maximum error.
Flow Control Trainer
9
DESCRIPTION: FOR FLOW CONTROL TRAINER: The basic objective of this flow controller is to control the flow of li quid in the pipe line. This set up consists of the following components:
SETUP ASSEMBLY: This assembly is used for supporting the various components on the front panel of the equipment i.e. pressure gauges which is used to measure the pressure, Current to pressure converter having a range in between 3 to 15 psi i.e. 3 psi for a current of 4mA and 15 psi for current of 20mA which is given to the I/P converter by DIGITAL INDICATING CONTROLLER. The setup also contains a pneumatic actuator. I/P Converter
Safety Valve
Pressure Gauge
Digital Indicating controller Surge Tank
Pre Re
Flow Transmitter Final Control Element
Moi Sep Air Supply
SCHEMATIC DIAGRAM OF FLOW CONTROL TRAINER
DIFFERENTIAL PRESSURE TRANSMITTER: The flow of the liquid in the pipe line is sensed by the flow transmitter with the help of orifice given in the line and after that is transmitted by the transmitter to the computer through interfacing unit which shows the value of the process variable. This transmitter converts that accordingly into 4-20mA i.e. 4mA for 0% flow and 20mA for 100 % flow.
Flow Control Trainer
10
CONTROL VALVE: A control valve basically performs the function of controlling the flow of the water in the pipe line. It is a diaphragm type pneumatic actuator, which varies the flow of the liquid according to the movement of the stem at a pressure range of 3 to 15 psi, which is received from I/P converter.
INTERFACING UNIT: The interfacing unit is basically a medium for communicating with the equipment from the computer. In case of flow controller, the flow of the liquid is sensed by the flow sensor in the pipe line, which is further transmitted into 4-20 mA which means that the current is 4mA for 0% flow and 20mA for 100% flow and are displayed on the interfacing unit in terms of 0 to 100%. These signals are further transmitted to the computer through this interfacing unit by using a RS-232C where the signals are displayed on the computer screen. The output of the interfacing unit is then transmitted to the I/P converter, which converts it into 3 to 15 psi that means 3 psi for 4mA and 15 psi for 20mA.
CURRENT TO PRESSURE CONVERTER (I/P CONVERTER ): This converter is basically used to convert the current to pressure having a range of 3 to 15 psi, which shows 3 psi at 4 mA and maximum 15 psi at 20 mA. This I/P converter receives the continuous input pressure of more than 15 psi and then converts this pressure into 3 to 15 psi according to the 4 to 20 mA current received by it from the digital indicat ing controller.
INSTALLATION R EQUIREMENTS: This section gives the necessary details regarding the installation of the equipment and the software used for interfacing with the equipment. For the installation of the equipment, following components are required: 1)
Table for support.
2)
Water supply.
3)
Electricity 220V, single phase, 50Hz, 5 Amps socket.
For the installation of the software, following components are required: -
Flow Control Trainer
11
COMPUTER: A computer, which is the basic requirement for installing the software for interfacing with the equipment. But the computer must fulfill the following requirements:-
1.
The Processor must be at least celeron 286 MHZ, Pentium III is recommended.
2.
It must have at least 16 MB RAM.
3.
It must have 30 MB hard disk space.
4.
It must have at least Windows 98 OS or higher version of operating system.
5.
There must be an A4 size printer, which is used to get a hard copy of the stored data required.
SOFTWARE INSTALLATION: 1)
Close all the programs running before inserting the Cd into CD drive.
2)
Insert the provided CD for the software in the CD drive of computer.
3)
It is an AUTORUN CD. Follow the instructions appeared on the computer screen and install the software in desired directory.
4)
After completion of installation, reboot your computer.
5)
Then, Open the software directory and double click the exe file of the software to run the program.
6)
MENUS
Follow the steps according the experimentation.
& BASIC FUNCTIONS: -
This section gives us the detailed information regarding the menus and the basic function of the control software, which is used to control the equipment. It is shown in figure 3.
LOGIN: This menu enables you to start the experiment. In this option, we are given with the User Name i.e. name of the institute and the Password, which is “k.c.engineers”. Here we have
also the option of the entering the “Professors Name” under whose supervision test is going to be performed, “Student’s name” and the “Roll Number” of the student who is performing the experiment , which can be used during the report generation. It is compulsory to select this option first and to fill the correct user name and password to continue the experiment. Without enabling this option and trying to continue the process or to select any Flow Control Trainer
12
other option in the front panel shows the display box indicating that the user must login first for selecting any other option. In this option, password is compulsory for running the software. In case of wrong password the software will not run and a dialogue box will appear with the software. All other options can be skipped off if not desi red.
VIEW DIAGRAM: After LOGIN, we have to select VIEW DIAGRAM. This option, which shows us the complete block diagram of the equipment and tells us how the equipment functions and also helps in preparing the equipment connection. After that we have to choose the BACK option and then decide to choose either the SIMULATION to access data from the simulation logic in order to start the experiment or INTERFACE to access with the real time data .
SIMULATION: Selecting this option accesses data f rom the PID simulation logic. This option doesn’t use any real time data. In this case, the process values and set point are to be entered by the user and then observes the change in the controller output. In this we have the option to put some value of disturbance. Now as the value of the load or the disturbance increases in a process, then the corresponding error between the SP and PV increases. Hence as a result, the output response also increases and vice-versa. Also in case of manual mode in the Simulation, when the controller output is made equal to zero, then the value of PV decreases and finally reaches to zero.
SIMULATION MODE:
Flow Control Trainer
13
INTERFACE: Selecting this option, accesses real time data from using interfacing unit. In order to make the system stable, we have to change the values of P, I, D.
START: By enabling this option, the equipment will be ready to perform the experiment.
LOG: On clicking the LOG button ON or selecting this option enables the data to be logged in some particular file, which can be used later for continuing the experiment. In order to view this saved data-logging file, click VIEW DATA FILE.
OFF: Selecting this option disables the data logging.
FUNCTION GENERATOR: The function generator is basically used to apply the dynamic waveform of some particular period and amplitude to the process. The waveform is applied to the set point in case of the close loop operation and is applied to the output in case of the open loop function.
Flow Control Trainer
14
ON: This option enables the function generator selection and also enables the waveform to be applied to the process.
OFF: Selecting this option disables the function generator so that it stops functioning.
FUNCTION GENERATOR PARAMETERS: SIGNAL TYPE: This function enables you to select one waveform out of the sine, triangular, square and sawtooth waveform to be applied to the process.
R EFERENCE POINT: This function is used to set the reference point equal to set point which helps in making PV equal to the set point.
PERIOD: This function is basically used to provide some time period to a waveform so that the waveform completes its one complete cycle in some particular interval of time.
AMPLITUDE: This function is used to set the amplitude of the waveform, which is selected to be applied to the process.
PROCESS: This function is responsible for either increasing or decreasing the value of PV in the SIMULATION mode.
LAG (MIN): -
It is also known as delay time and is measured in minutes. It is the amount of time required for the response to reach 50% of the final value in first attempt. As the value of the lag time increases, the change in the value of PV also increases.
Flow Control Trainer
15
DISTURBANCE (%): A disturbance is a signal that tends to adversely affect the value of the output of a system. If a disturbance is generated with in the system, it is called internal, while an external disturbance is generated outside the system and is an input.
INITIAL: This is the value of the PV when we continue the process without allowing the process variable to reach its initial state i.e. equal to zero or its ambient temperature.
AMBIENT TEMPERATURE: This is the initial value of PV, or due to the room temperature of the place where the experiment is to be performed.
OUTPUT R ANGE: This corresponds to the maximum and the minimum range of the controller output, which is to be set by the user.
OUTPUT HIGH It corresponds to the maximum limit of the controller output means that the output of the controller never exceeds this limit. This value is set by the user in order to obtain the accurate result.
OUTPUT LOW: It corresponds to the lowest limit of the controller output means that the output of the controller can never be less than this value.
PID GAINS: This corresponds to the various values of the Kc, Ti and Td, which are to be selected by the user in order to make the system stable. In other words, these values are selected in order to make PV equal to SP.
MODE STATUS: This option tells you that in which mode the system is operating i.e. whether the system is operating in P, PI or PID.
Flow Control Trainer
16
P: This option tells you that the system is operating in proportional controller mode. P represents the proportional gain. In order to get the steady operation when the disturbances are absent, the controlled variable must be a continuous function of error. With proportional control, the controller output is a linear function of the error signal.
PD: This option indicates that the system is operating in Proportional + Derivative controller mode.
PID: This option indicates that the system is operating in proportional
+ Integral +
Derivative controller
BIAS: Bias is the value of the normal output of the controller at zero error. This is added to the proportional controller.
Thus, when a process is under P only control and the SP equals the measurement (when error equals zero), some bias value of the controller output must exist or t he measured PV will drift from the set point. This bias value of the controller output is determined from the design flow of operation of the process to be controlled. Specifically, bias is the value of the controller output, which in open loop causes the measured PV to maintain steady state at the design flow of the operation when the process disturbances are at their design.
ACTION: There are mainly two actions for controlling the process variable and controller output. These actions are: 1) INC-INC 2) INC-DEC
Using INC-INC action will cause increase in output with the corresponding increase in process variable. Using INC-DEC action will cause decrease in controller output with increase in process variable. This action should be observed by the user, which will further depend on the final control element functioning. Flow Control Trainer
17
For example: Consider a case of pneumatic actuator, which is open for air and otherwise closed which means that the actuator valve is open for 15 psi pressure and close for 3 psi pressure. So, the final control element sets INC-INC action or INC-DEC action.
SWITCHING BETWEEN AUTO AND MANUAL: Auto and Manual:
There’re two different modes option in this software i.e. Auto and Manual. In case of auto mode, the software automatically controls the output of the process. In this case, user doesn’t do anything to control the output of the process. So, if the output is increasing with increase in the value of the Kc, the controller automatically decreases its output in order to make it stable. But in case of manual control, the user controls the output of the process. Click AUTO to select the AUTO mode and Click again to change the system to manual mode.
EXIT: This option enables you to logout of the simulation or interfacing mode.
VIEW DATA FILE: This option accesses data from the data stored in the stored file using LOG button. Results and data of the experiment conducted are observed .The user can see the data stored in the file in the form of tables as well as graphs. After enabling this option, user enters into a window where user has to open the file in which he has stored his/her data while performing the experiment using the LOG button and this shows the data in the form of table which indicates date and time i.e. which indicates when the experiment was performed and at what time, PV, set point, output, upper and lower range and the limit of the upper and lower hysteresis. This window also indicates the User i.e. the name of the institute which is performing the experiment and also the Professor name i.e. under whose supervision the experiment is going to be performed, Student Name and Roll Number i.e. name and roll number of the student who is performing the experiment.
STOP: This option enables you to logout out of this window.
Flow Control Trainer
18
R UN/PAUSE: This option enables the graph to run or pause to show the waveform according to the data shown the table in that window.
PRINT GRAPH: Use print graph option for printing graphs according to the data that is saved in the data log file. Enabling this option enables you to enter into the print window, which shows the User i.e. the name of the institute, Professor’s Name i.e. under whose supervision test is to
be performed, Student’s Name and Roll number i.e. the name and the roll number of the student who is performing the experiment and the File path i.e. the path of the file which was saved using the LOG button. In this window the user has two options at the top of the window i.e. one option of Print Window, which is used to take out the printout of the window, and the second option is of Stop, which enables the user to come out of the window.
PRINT TABLE: Use print table option to print table from data file that are saved in the data log file. This option opens all the data stored using the log button in the excel file where the user has an option to set the left, right margins of the page.
BODE PLOT: To view this, switch off the start button so as to return back to the front panel and click bode plot.
COMPARE DATA: This option enables you to compare the data between to two experiments having different values of P, I, D. This option also enables you to compare data between the SIMULATION mode and INTERFACING mode.
EXIT: Selecting this option allows you to return back to the desktop or logout you from the software.
Flow Control Trainer
19
VARIOUS PID CONTROL METHODS: 1. COHEN AND COON R ULES (C-C): (Referred from Process systems Analysis and Control By Donald R.Coughanowr, 2
nd
edition,
page no.288) COHEN-COON METHOD
M/S
Uu=0
+
+ Gc
R=0
Gp
Gv
-
C
+ Loop Opened
B H
To Recorder
Block Diagram of a Control loop for measurement of the Process reaction Curve
Tangent Line; Slope S = Bu/T
0
Td Time
M
0
Tt
Figure : 5 Typical process Reaction Curve showing graphical construction to determine first order with Transport lag Model
The open loop method of tuning in which the control action is removed from the controller by placing it in manual mode and an open loop transient is induced by a step change in the signal. This method was proposed by COHEN and COON in 1953 and is often used as an alternative to the Z-N method. Fig shows a typical control loop in which the control action is removed and the loop opened for the purpose of introducing a step change (M/S). The step response is recorded at the output of the measuring element. The step change
Flow Control Trainer
20
to the valve is conveniently provided by the output from the controller, which is in manual mode. The response of the system is called the process reaction curve; a typical process reaction curve exhibits an s-shape as shown in the fig. 5 It is represented by equation: Gp ( s ) =
Kc × e
−Tds
Ts + 1
------------------(7)
The C-C method is summarized in the following steps: 1) After the process reaches steady state at the normal temperature of operation, switch the controller to manual. In modern controller, the controller output will remain at the same value after switching as it had before switching. 2) With the controller in manual, introduce a small step change in the controller output and record the transient, which is the process reaction curve. 3) Draw a straight line tangent to the curve at the point of inflection, as shown in fig .the intersection of the tangent line with the time axis is the apparent transport lag (Td); the apparent first order time constant (T) is obtained from the T=Bu/S ------------------------------(8) Where Bu is the ultimate value of B at large t and S is the slope of the tangent line. The steady state gain that relates B to M in fig is given by K p=Bu/M -----------------------------(9) 4) Using the values of K p, T and T d from step 3, he controller settings are found from the relations as given below:
Flow Control Trainer
21
TYPE OF CONTROL
PARAMETER SETTING
Proportional (P)
Kc =
Proportional – Integral (PI)
Kc =
T KpTd T
(1 +
(
9
KpTd 10
9 + 20
5 Td ( + ) KpTd 4 6T
Td
22 + 3
T ) Td T
4 Td ( + ) TdKp 3 4T
T
32 + 6
Ti = Td ( 13 + 8 td = Td (
Td T ) Td T
4 11 + 2
Flow Control Trainer
) 12T
T
td = Td (
Kc =
Td
+
1
6−2
Proportional – integral-derivative (PID)
)
T ) Td
Ti = Td (
Kc =
3T
Td
30 + 3
Proportional- Derivative (PD)
Td
Td
)
T
22
2. ZIEGLER’S NICHOL’S METHOD: (Referred from Modern Control Engineering By Katsuhiko Ogata) According to Zeigler – Nichol, PID controllers can be classified into two categories: 1) A controller in which the dynamic model of the plant is not known. 2) A controller in which the dynamic model of the plant is known. Zigler-Nichol’s Method
1 PLANT Uu(t)
C(t)
Unit Step Response of a Plant
C(t) Tangent Line at Inflection point K
0 L
Time T
Figure : 6 S Shaped Response Curve
FIRST METHOD: In this method, we obtain experimentally the response of the plant to a unit step input. If the plant involves neither integrator nor dominant complex conjugate poles, then such a unit step response curve may look S-shaped. This method applies if the response to a step
Flow Control Trainer
23
input exhibits an S-shaped curve. Such step response curves ma y be generated experimentally or from a dynamic simulation of the plant. The S-shaped curve may be characterized by two constants, delay time L and time constant T, which is shown in fig. 6 constant are determined by drawing a tangent line at the inflection point of the S-shaped curve and determining the intersections of the tangent line with the time axis and line C (t)=K, as shown in the figure. The transfer function C(s)/U(s) may then be approximated by first order syste m with a transport lag as follows: -
C ( s) U ( s)
=
K × e
− Ls
Ts + 1
----------------------(10)
Zeigler and Nichols suggested to set the values of Kp, Ti and Td according to the formula shown in below table. Type of controller
K c
Ti
Td
P
T/L
∞
0
PI
0.9T/L
L/0.3
0
PID
1.2T/L
2L
0.5L
Notice that the PID controller tuned by the first order method of Zeigler- Nichols rules gives: Gc( S ) = Kc(1 +
1
Tis
+ Tds = 1.2
T L
(1 +
1 2 Ls
+ 0.5Ls )
Thus the PID controller has the pole at t he origin and double zeros at S=-1/L.
SECOND METHOD: It is shown in fig. 7. In the second method, we first set Ti=infinity and Td=0. Using the proportional control action only, increase Kc from 0 to critical value Kcr at which the output first exhibits sustained oscillations, (If the output doesn’t exhibit sustained oscillations for whatever value Kp may take, then this method doesn’t apply). Thus, the critical gain Kcr and the corresponding period Pcr are experimentally determined. Zeigler and Nichols suggested that we set the values of the parameters Kc, Ti and Td according to the formula shown in the table Notice that the PID controller tuned by the second method of Zeigler-Nichols rules gives:
Flow Control Trainer
24
Gc( s) = Kc(1 +
= 0.6 Kcr (1 + = 0.075
1
Tis 1
+ Tds)
0.5 Pcrs
+ 0.125 Pcrs)
KcrPcr ( s + 4 / Pcr )
2
s
Thus the PID controller has the pole at the origin and double zeros at S=-4/Pcr. C(t) Tangent Line at Inflection point K
0 L
Time T
Figure : 7 S Shaped Response Curve
Type of controller
K c
Ti
Td
P
0.5K cr
∞
0
PI
0.45K cr
Pcr /1.2
0
PID
0.6K cr
0.5Pcr
1.25Pcr
Note that if the system has a known mathematical model (such as transfer function), then we can use the root locus method to find the critical gain Kcr and the frequency of the sustained oscillations Wcr, where 2*pi/Wcr=Pcr. These values can be found from the crossing points of the root locus branches with the jw axis. (Obviously, if the root locus branches do not cross the jW axis, this method doesn’t apply).
COMMENTS: Zeigler-Nichols tuning rules (other tuning rules presented in the literature) have been widely used to tune PID controllers in process control system where the plant dynamics are not precisely known. Over many tears, such tuning rules proved to be very useful. ZeiglerFlow Control Trainer
25
Nichols tuning rules can, of course, be applied to plants whose dynamics are known. (If the plant dynamics are known, many analytical and graphical approaches to the design of t he PID controllers are available, in addition to the Zeigler-Nichols tuning rules).
3. QUARTER DECAY R ATIO METHOD: The following controller tuning procedures are based on the work of Zeigler and Nichols, the developers of the Quarter Decay ratio-tuning techniques derived derived from a combination of theory and empirical observations.
CLOSED LOOP (ULTIMATE TUNING) TUNING PROCEDURE: Although the closed loop tuning procedure is very accurate, you must put your process in steady state oscillation and observe the PV on a strip chart. Complete the following steps to perform the closed loop tuning procedure. 1) Set both the derivative time and integral time on your PID controller to zero. 2) With the controller in automatic mode, carefully increase the proportional gain (Kc) in small increments. Make a small change in SP to disturb the loop after each increment. As you increase Kc, the value of the PV should begin to oscillate. Keep making changes until the oscillation is sustained, neither growing nor decaying overtime. 3) Record the controller proportional band (PBu) as a percent, where PBu=100/Kc. 4) Record the period of oscillation (Tu) in minutes. 5) Multiply the measured values by the factors shown in the below table and enter the new tuning parameters into your controller. This table provides the proper values for a quarter decay ratio. If you want less overshoot, increase the gain Kc. Controller
PB (%)
Reset (min.)
Rate (min.)
P
2PBu
---------
--------
PI
2.22PBu
0.83Tu
-------
PID
1.67PBu
0.50Ttu
0.125Tu
Flow Control Trainer
26
Max.
63.2% (Max.Min) PV
Min.
Output Time
Td T Figure :
Output & PV Step Change
OPEN LOOP (STEP TESTING) TUNING PROCEDURE: The open loop tuning procedure assumes that you can model any process as a first order lag and a pure dead time. This method requires more analysis than the closed loop tuning procedure, but your process doesn’t need to reach sustained oscillation. Therefore, the open loop tuning procedure might be quicker and the PV on a strip chart that shows time on the X-axis. Complete the following steps to perform the open loop tuning procedure. 1.
Put the controller in manual mode, set the output to a nominal operating value and allow the PV to settle completely. Record the PV and output values.
2.
Make a step change in the output. Record the new output values.
3.
Wait for the PV to settle. From the chart, determine the values as derived from the sample displayed in the given figure.
4.
Multiply the measured values by the factors shown in fig (a) and enter the new tuning parameters into your controller. The table provides the proper values for a quarter decay ratio. If you want less overshoot, reduce the gain, Kc.
Flow Control Trainer
Controller
PB (%)
Reset (min)
Rate (%)
P
100KTd/T
---------
----------
PI
110KTd/T
3.33Td
----------
PID
80KTd/T
2Td
0.50Td
27
VARIOUS STABILITY METHODS: 1. BODE PLOT: (Referred from Process Control By Peter Harriot, Page no. 91) A convenient method of presenting the response data at various frequencies is to use a log –log plot for the amplitude ratios, accompanied by a semi log plot for the phase angles. Such plots are called “ Bode diagrams”, after H.W Bode, who did basic work on the theory of feedback amplifiers. By using wT as a parameter, a general plot for first order system is obtained. Since the amplitude ratio approaches 1.0 at low frequencies and 1/wT at high frequencies, the straight line portion of the response if extended would intersect at wT = 1.0. The frequency corresponding to the wT = 1 is called the “corner frequency” and the amplitude ratio is 0.707 at this point. The phase lag is 45 degree at the corner frequency and the phase curve is symmetrical about this point. The system shown in fig. 6 has a gain of 1, which means that the output equals the input as the frequency approaches zero. If the system gain K is greater than 1, the output amplitude is greater than the input amplitude at low frequencies and a more comprehensive definition of amplitude ratio is needed. The amplitude ratio is defined as the ratio of output amplitude to input amplitude at a given frequency, divided by the ratio of the amplitudes at zero frequency. This is equivalent to dividing the measured ratio by B/A by the gain K, which makes the amplitude ratio dimensionless and makes equation and curves applicable to the first order process. Sometimes, the amplitude ratio is defined just as B/A, or output over input, which leads to amplitude ratios, which may not be dimensionless. There is nothing unsound about this procedure but the use of different units for each process element makes it somewhat harder to plot the overall response of the system. Whenever a sinusoidal input is applied to a linear system, the output has steady state and transient terms. After a few cycles, the transient dies out and the output is a sine wave of the same frequency. This eventual response can be characterized by the amplitude ratio and the phase angle. Typical curves for a first order process are shown below. At low frequency, the output is almost equal to the input, and there is only a slight phase lag. At high frequency, the fluctuations in the input are severely damped because of the capacity in the system and the output lags the input by almost 90 degree.
Flow Control Trainer
28
A.R
1
=
1
(1 + w T ) 2 2
2
The phase angle is always negative for a first order system and the negative angle is called “ phase lag”. The phase lag is 360(dt/p) in fig. And approaches a limit of 90 degree at high frequencies.
2. R OUTH‘S ALGORITHM METHOD: (Referred from Problems and Systems of control systems By A.K. Jairath, 3
rd
edition, page
no. 6.1) The Routh test is a purely algebraic method for determining how many roots of the characteristics equation have positive real parts; from this it can also be determined whether the system is stable, for if there are no roots with positive real parts, the system is stable. The test is limited to the systems that have polynomial characteristic equations. As per Routh’s stability criterion the necessary conditions for a system to be stable are: 1) None of the co-efficient of the characteristics equations should be missing or zero. 2) All co-efficient should be real and should have same sign. The sufficient condition for a system to be stable is that each and each term of t he first column of Routh’s array should be positive and should have same sign. Routh’s array for the characteristic equation A0 s*n + A1 s*n-1 +A2 s*n-2 + ------------------An-1s + An = 0 -------------(11) Where n=7 is formed as given below A0
A2
A4
A6
A1
A3
A5
A7
B1
B3
B5
C1
C3
D1
D3
E1 F1
Flow Control Trainer
29
Where A1A2 – A0A3 B1
=
-----------------A1 A1A4 – A0A5
B3
=
----------------A1 A1A6 – A4A7
B5
=
--------------A1 B1A3 – A1B3
C1
=
-----------------B1 B1A5 – A1B5
C3
=
-----------------B1 C1B3 – B1C3
D1
=
----------------C1 C1B5 – B1 0
D3
=
----------------C1
If we study the array successive rows have one term fewer than the preceding row, and hence the array is triangular. The following are the limitations of the routh’s stability criterion: It is valid only if the characteristic equation is a lgebraic. 1) If any co-efficient of the characteristic equation is complex or contain power of ‘e’, this criterion can’t be applied. 2) It gives us information as to how many roots are lying in the right hand side of the s plane. Values of the roots are not available. Also, it cannot distinguish between real and complex roots.
Flow Control Trainer
30
CONDUCTING EXPERIMENT: DESCRIPTION: This section gives the functional details of the product, which is used to conduct the experiment. Functional details and control loop description enables us to understand the working principle of the product.
FLOW CONTROL TRAINER (SCADA): The SCADA is basically an interfacing unit and is a medium for communicating with the equipment from the computer. In case of flow controller, the flow of the liquid is sensed by the sensor in the pipe line, which is further transmitted into 4-20 mA which means that the current is 4mA for 0% flow and 20mA for 100% flow and are displayed on the interfacing unit in terms of 0 to 100%. These signals are further transmitted to the computer through this interfacing unit by using a RS-232C where the signals are displayed on the computer screen and the error signals, which are produced by the controller, are displayed on the interfacing unit. The output of the interfacing unit i s then transmitted to the I/P converter, which converts it into 3 to 15 psi that means 3 psi for 4mA and 15 psi for 20mA.
START UP: 1.
Drain should be closed.
2.
Fill the sump tank with 3/4 of water and avoid the presence of foreign particles.
3.
Switch on the main supply.
4.
Switch on the pump and observe that the water is properly circulating.
5.
Check whether all the valves are properly working or not.
6.
Switch on computer and the interfacing unit.
7.
Select the Auto mode to perform the experiment automatically and in Manual mode to
th
change the values manually. 8.
Connect the equipment with compressed air supply of minimum 3 bar.
Flow Control Trainer
31
SHUT DOWN: 1.
Exit from the software.
2.
Switch off the interfacing unit.
3.
Switch off the pump and air supply from the compressor.
4.
Clean the tank.
Flow Control Trainer
32
Following experiments can be conducted with the product.
Experiment No. 1.
To study the open loop or manual control.
Experiment No. 2.
To study the Proportional control.
Experiment No. 3.
To study the Two mode (P+I) control.
Experiment No. 4.
To study the Two mode (P+D) control.
Experiment No. 5.
To study the Three mode (PID) control.
Experiment No. 6.
To study the tuning of controller (Open loop method) using Zeigler-Nichols method.
Experiment No. 7.
Flow Control Trainer
To study the stability of the system using the BODE PLOT.
33
EXPERIMENT NO. 1: OPEN LOOP (MANUAL) CONTROL. OBJECTIVE: To study the open loop or manual control.
THEORY: In these systems, the output remains constant for a constant input signal provided the external; conditions remain unaltered. The output may be changed to any desired value by appropriately changing the input signal but variations in external or internal parameters of the system may cause the output to vary from the desired value in an uncontrolled fashion. The open loop control is, therefore, satisfactory only if such fluctuations can be tolerated or system components are designed and constructed so as to limit parameter variations and environmental conditions as well as controlled, whereas in case of closed loop system, the controlled variable is measured and compared with reference input and the difference is used to control the elements.
EXPERIMENTAL PROCEDURE: 1.
Start up the setup as mentioned in the starting.
2.
Select the manual mode.
3.
Set the controller output to 100%.
4.
Apply a step change of 10% to the controller output and wait for the PV to reach the steady state.
5.
Repeat the above steps i.e. 2 and 3 until the output of the controller reaches to 0% temperature
6.
Shut down the apparatus as mentioned in the starting..
Flow Control Trainer
34
OBSERVATIONS & CALCULATIONS: S.No.
Controller Output (%)
1.
100
2.
90
3.
80
4.
70
5.
60
6.
50
7.
40
8.
30
9.
20
10.
10
PV (%)
Set the output of the controller to some predicted value and apply some steady state load change and then verify the result.
Flow Control Trainer
35
EXPERIMENT NO. 2: PROPORTIONAL CONTROL OBJECTIVE: To study the proportional control (P control).
THEORY: In order to get steady operation when the disturbances are absent, the controlled variable must be a continuous function of error. With proportional control, the most widely used type; the controller output is a linear function of the error signal. The controller gain is the fractional change in output divided by the fractional change in input. P = Kc* e -------------------------(1) where, P
=
fractional change in controller output,
E
=
SP-PV =
K c
=
controller gain.
fractional change in the error.
Whereas the equation of the proportional controller output is given by P = Kc (SP – PV) + P0 -----------------------(13) Where P0 = bias i.e. the value of the controller output at ze ro error. In this experiment, the measured process value (PV) and set point (SP) is compared And the output of the controller is proportional to the resulting error signals.
EXPERIMENTAL PROCEDURE: 1. Start up the set up as mentioned previously. 2. Select the controller in AUTO mode. 3. Set the value of Kc as high as possible. 4. Observe the process and the output response. 5. If output response doesn’t shows cycling, adjust the value of Kc to half of its previous value. 6. Repeat steps 4 and 5 until cycling is observed. 7. Then, increase the value of Kc to twice its value and observe the Output response. 8. Repeat step 7 until cycling is observed. Flow Control Trainer
36
9. Record the value of Kc at which you observe the oscillations and record the overshoot. 10. Now increase the value of Kc in st eps and observe the corresponding overshoots. 11. Compare the relative overshoot with the value of Kc.
OBSERVATIONS & CALCULATIONS: 1.
Observe that as the value of Kc increases, then the error or the difference between the SP and PV increases. In other words, as the error decreases, the proportional band decreases.
2.
In case of proportional controller, the control system is able to arrest the rise of the controlled variable and ultimately bring it to rest at a new steady state value. The difference between this new steady state value and the original value is called OFFSET. There is always some offset present in case of proportional controller. PV
Kc=1
Tt
PV
Kc=10
Tt
PV
Kc=15
Tt
PV
Kc=20
Flow Control Trainer
Tt
37
EXPERIMENT NO. 3: TWO MODE (P+I) CONTROL OBJECTIVE: To study the steady state and transient response to a proportional + Integral control.
THEORY: This mode of control is described by the relationship: P = Kc × e +
Kc Ti
∫ edt + Ps − − − − − − − − − − − −(14)
Where: Kc
=
gain
e
=
error
Ti
=
integral time, seconds
Ps
=
constant
P
=
output
=
(SP-PV)
In this case, we have added to the proportional action term, Kc * e, another term that is proportional to the integral of the error. There is no offset with the integral control, since the output keeps changing as long as any error persists. However, the initial response to an error is slow and proportional control is ordinarily used with integral control. The integral action corrects for the offset that usually occurs with proportional control only, and the effect is similar to manual adjustment or resetting of the set point after each load change. The terms “ reset action” and “reset time” are widely used to characterize the integral action of a proportional – integral controller. P = Kc (e +
1 Ti
∫ edt ) − − − − − − − − − − − − − − − − − (15)
Where: Ti
=
reset time.
Kc
=
gain
e
=
error
=
(SP-PV)
A small reset time corresponds to an increase in the integral action. With P action the measured value will not necessarily become equal to the set point and a deviation will usually be present. The control algorithm that applies changes in output as long as deviation exits, so Flow Control Trainer
38
as to bring the deviation to zero is called integral action. With integral action the parameters that determines how fast the output will change in corresponding to some amount.
EXPERIMENTAL PROCEDURE: 1. Start up the setup as mentioned previously. 2. Select auto mode option for control. 3. Select a set point. 4. Select some value of Kc as described in proportional controller and Ti as high as possible. 5. Observe the response of the system. If over damped oscillations are occurring, then increase or decrease the corresponding values of Kc or Ti so as to make PV equal to SP. 6. Then, observe the output response curve. If on decreasing the value of either Ti or Kc makes the PV equal to SP, then continue decreasing the value until PV becomes nearly equal to SP. 7. After experimentation, switch off the apparatus as mentioned previously.
OBSERVATIONS & CALCULATIONS: 1.
The addition of integral action nearly eliminates the offset and the controlled variable Ultimately returns to the original value.
2.
It is shown the fig., that the addition of integral action introduces an oscillatory motion in the system and with the increase in the value of the integral time, the difference between the SP and PV decreases. PV
Tt
Kc=10 Ti=1 PV
Kc=10
Tt
Ti=5 PV
Kc=10
Tt
Ti=10
Flow Control Trainer
39
EXPERIMENT NO. 4: TWO MODE (P+D) CONTROL OBJECTIVE: To study steady state and transient response to a proportional + derivative control.
THEORY: This mode of control may be represented by: P = Kc* e + Kc Td de/dt --------------(16) Where Kc = gain Td = derivative time, seconds In this case, we have added to the proportional term another term, KcTd (de/dt) that is proportional to the derivative of the error. Other terms that are used to describe the derivative action are rate control and anticipatory control . Derivative action is often added to proportional control to improve the response of slow systems. By increasing the output when the error is changing rapidly, derivative action anticipates the effect of large load changes and reduces the maximum error. Larger the derivative time larger is the action. Smaller is the proportional band the larger is the derivative action.
EXPERIMENTAL PROCEDURE: 1. Start up the setup as mentioned previously. 2. Select auto mode option for control. 3. Select a set point. 4. Select some value of Kc as described in the proportional controller and the value of Td to the minimum value. 5. Observe the response of the system. If over damped oscillations are occurring, then reduce the value of Td to half of its previous value so as to make PV equal to SP. 6. Then, observe the output response curve and double the value of Td in order to make PV equal to SP, then continue decreasing the value until PV becomes equal to SP. 7. After experimentation, switch off the apparatus as mentioned previously.
Flow Control Trainer
40
OBSERVATIONS & CALCULATIONS: 1. The derivative action is added to improve the response of the slow system. 2. The addition of derivative action to the PI action gives a definite improvement in the response. The rise of controlled variable is arrested more quickly and it is returned rapidly to the original value with little or no oscillations.
Flow Control Trainer
41
EXPERIMENT NO. 5: THREE MODE (PID) CONTROL OBJECTIVE: To study the steady state and transient response to a Proportional + Integral + Derivative.
THEORY: This mode of control is described by the relationship P = Kc × e +
Kc Ti
∫ edt + Kc × eTd
de dt
+ Ps − − − − − − − − − − − − − (17)
Where: e
=
error
K c
=
gain
=
(SP-PV)
Td is derivative time, Ti is integral time and Kc=proportional gain
EXPERIMENTAL PROCEDURE: 1. Start up the setup as mentioned earlier. 2. Select auto mode option for control. 3. Select a set point. 4. Select some value of Kc, Ti and Td. 5. Observe the response of the system. If over damped oscillations are occurring, then increase or decrease the corresponding values of Kc, Ti and Td so as to make PV equal to SP. 6. Then, observe the output response curve. If on decreasing the value of either Kc, Ti, Td makes the PV equal to SP, then continue decreasing the value until PV becomes equal to SP. 7. After experimentation, switch off the apparatus 8. Using trail and error, select the proportional gain and integral time, which gives a satisfactory response to step change in set point. 9. Set the derivative time to a non-zero value and carry out the above steps for different derivative time values. 10. After experimentation shut down the setup as mentioned earlier. Flow Control Trainer
42
OBSERVATIONS & CALCULATIONS: The addition of derivative action to the PI action gives a definite improvement in the response. The rise of controlled variable is arrested more quickly and it is returned rapidly to the original value with little or no oscillations. PV
Tt
PV
PV
Kc=10 Ti=1 Td=1
Kc=10 Ti=1 Td=5
Kc=10 Ti=1 Td=10
Flow Control Trainer
Tt
Tt
43
EXPERIMENT NO.6: TUNING OF CONTROLLER (OPEN LOOP METHOD) OBJECTIVE: To study the tuning of PID controller by open loop method, using Zeigler- Nichols tuning rules.
THEORY: This method is basically used to calculate the value of P, I, D using the open loop or manual control method. The values of P, I, D are selected in such a way that the error or the difference between the SP and PV should become equal to zero. C(t) Tangent Line at Inflection point K
0 L
Time T
Figure : 7 S Shaped Response Curve
Since we are not given with the plant equation. So the process is assumed to be of first order with steady state gain Kc, integral time Ti and derivative time td. The step response i.e. process reaction curve, allows to obtain the approximate values of each parameter. With the feedback loop open, a step response is applied to manipulated variable and the values of P, I and D are estimated. The delay time L and time constant T are determined by drawing a tangent line at the inflection point of a S-shaped curve and determining the intersections of the tangent line with the time axis and line c (t) = K as shown in the figure obtained by performing the experiment. Flow Control Trainer
44
For P, PI and PID controller the parameters are calculated as foll ows:
Mode
Proportional
Integral
Derivative
P
T/L
INFINITY
0
P+I
0.9T/L
L/0.3
0
P+I+D
1.2T/L
2L
0.5L
EXPERIMENTAL PROCEDURE: 1.
Start up the set up as mentioned.
2.
Select open loop option for control.
3.
Select the value of the set point to some desired value.
4.
Apply a 20-30% change to controller output. Record the step response. Wait for the steady state.
5.
Start data logging and from the readings draw a step response curve.
6.
Calculate the value of Td and L.
7.
From this, calculate the values of PID controller settings from the table.
8.
After experimentation, shut down the set up.
OBSERVATIONS & CALCULATIONS: Tabulate the data from stored file as follows: Observation No.
Time in sec.
Process Value (%)
1. 2. 3. 4.
Calculate the value of the P, I and D from the table given in the theory part of this experiment.
Flow Control Trainer
45 93
EXPERIMENT NO. 7: TO STUDY THE STABILITY OF A SYSTEM OBJECTIVE: To study the stability of the system by plotting the bode p lots.
THEORY: A convenient method of presenting the response of the data at various frequencies is to use a log-log plot for the amplitude ratios, accompanied by the semi log plot for the phase angles. Such plots are called BODE PLOT. Plotting of BODE plot is relatively easier as compared to other methods as the loci of (1 + sT) and K/(1 + sT) can be represented by straight line asymptotes. In case of Bode plot, multiplication is converted into addition, so if G(s) = K/(1 + sT) And putting s = jw, Then 20 log [G (w)] = 20 log K– 20 log [1 + jwt]. In case of Bode plot, study of relative stability is easier as parameters of analysis of relative stability are gain and phase margin, which are visibly seen on the sket ch. The transfer function for a first order system is given by G ( s ) =
ke − Ls Tds + 1
The amplitude ratio of the above equation can be written as A. R. =
1 1
(1 + w T ) 2 2
2
The phase angle is always negative for a first order system and this negative angle is called “phase lag”.
STABILITY CRITERIA: 1. A system is stable if the phase lag is less than 180 degree at the frequency for which the gain is unity.
Flow Control Trainer
46 94