ZETADYN 1DV Control System for Elevators, High-bay Storage and Retrieval Systems, Cranes and Conveyors
SystemDescription
ASK8.T-GB0197
ZETADYN 1DV
ZIEHL-ABEGG ZETADYN 1DV
P
ZIEHL-ABEGG
INTRODUCTION The following equipment is described in this documentation: ControllerSeries ZETADYN1DV fromSerialNo. 39432xxxxx/xxxx with control software as from version 3.02 It contains important information on • • • • • •
Controller construction Connections Operation Control Commissioning Service
of the ZETADYN 1DV controller. The Appendix contains suggested a wiring diagram and a setting data card.
The information contained within this documentation describes the features of our products without guaranteeing the operation. We reserve the right to introduce changes without notice.
It is particularly important that you observe the following for your own safety: Information on safe operation of the equipment.
Important information
Safety information
The electrical equipment and machines described in this documentation are designed for use in industrial heavy current systems. They have parts which move or rotate and carry dangerous voltages during operation. Therefore, danger to health and property may be created if the necessary guards of safety covers are removed where this should not be done or if the necessary maintenance work is neglected. Consequently, those responsible for the safety of the equipment must observe the following rules: -
-
-
Only suitably qualified personnel* may be entrusted with any work which needs to be done on this equipment and machinery. Personnel working on this equipment and machinery must have access to the operating instructions and all product documentation supplied and must observe the relevant instructions contained therein. Unskilled personnel must not be allowed to work on this equipment and machinery or in the vicinity of it.
Notes The information on processes and sections of the circuitry contained in this documentation must be regarded as such without further implications. Their adaptation to other applications must be investigated; ZIEHLABEGG does not guarantee their suitability in such circumstances. The assemblies comprise components which may be electro-statically endangered. The body of the person touching them must first be electrically neutralized, for example by first touching a conductive, earthed object (e.g. bright metal parts of an electrical cabinet or earthing contact of a plug socket).
Written out as: All settings at the unit are carried out with the help of parameters grouped in menus. Example:
(* Definitions as in VDE 105 or IEC 364)
The running speed is determined by the Parameter V_3 in the TRAVELLING menu.
Written out as: /TRAVELLING/ V_3. These safety instructions are not claimed to cover all aspects of safety.
During electrical installation the following rules have to be observed: VDE 0100 - Bestimmung für das Errichten von Starkstromanlagen mit Nennspannung bis 1000V VDE 0113 (EN 60204) - Bestimmung für die elektrische Ausrüstung von Be- und Verarbeitungsmaschinen. VDE 0160 - Ausrüstung von Starkstromanlagen mit elektrischen Betriebsmitteln. In special applications additional rules or directions must be observed.
ZE TA DY N 1DV S ys tem Des cription Contents 0.
Page
Introduction
1. ZE TA DY N 1DV s ys tem informa tion - S ummary ..............................................6 1.1 1.2 1.3
Applications ................. .................. .................. .................. .................. ............... 6 Functions and features ....................................................................................... 6 Requirements ...................................................................................................... 8
2. Mounting ............................................................................................................9 2.1 2.2 2.3
Construction ....................................................................................................... 9 Installing the controller ........................................................................................ 9 Connecting and occupation of terminals ........................................................... 10 2.3.1 Mains .................. .................. .................. .................. .................. .......... 10 2.3.2 Motor ................ .................. .................. .................. .................. ............. 11 2.3.3 Control inputs ............... ............... ............... ................ ............... ............ 12 2.3.4 Control outputs ................ .................. ................. .................. ................. 13
3. Control and controller functions ...................................................................14 3.1 3.2
3.3
Controlling of ZETADYN 1DV ........................................................................... 15 Description of controller functions........................... .................. ................. ........ 16 3.2.1 Switching ON and OFF .................. ....................................................... 16 3.2.2 Start and accelaration .............................................. ............................. 16 3.2.3 Distance-controlled deceleration - Arch travel ............... ................ ......... 17 3.2.4 Time based deceleration ................. .................. .................. .................. 18 3.2.5 Distance-corrected deceleration ............... ................. ................. ........... 18 3.2.6 Normal slow down ................. ................. ................. ................. .............. 19 3.2.7 Quick stop .............................................................................................. 19 3.2.8 Readjustment .............................. ............... ............... ............... ............. 20 3.2.9 Direction reversal .................. ................. .................. ................. ............ 20 3.2.10 Short travel............................. .................. .................. ................. ........... 21 3.2.11 Troubles ............................. ............... ............... ............... ................ ....... 22 To ensure safe operation of the controller ........................................................ 23
4. Operation and settings ...................................................................................24 4.1 4.2 4.3
Operating through keyboard and LCD display .................................................. 24 Remote operation with PC and ZETAMON software ........................................ 26 Summary of parameters ................................................................................... 27 4.3.1 The menu "Monitor" ............................................. ................................. 28 4.3.2 The menu "Distances & Times" ............................................................. 29 4.3.3 The menu "Statistic" ............... ............... ............................. ............... .... 30 4.3.4 The menu "Travelling" ........................................................................... 31 4.3.5 The menu "Accelerating".............. .......................................................... 32 4.3.6 The menu "Decelerating" ....................................................................... 33 4.3.7 The menu "Controller" ............................ ........................................... .... 33 4.3.8 The menu "Operating" ............................ ........................................... .... 34 4.3.9 The menu "Installation" .......................................................................... 35 4.3.10 The menu "Interfaces" ........................................................................... 37 4.3.11 The menu "ZA-Intern" ........................................................................... 38
Contents
Page
5. Commissioning ...............................................................................................39 5.1 5.2 5.3 5.4 5.5
Requirements ................................................................................................... 39 Quick setup for mount ing trav els ....................................................................... 40 Setting of the "Switch off cont acts" in the sha ft.................................................. 41 Adjustment ........................................................................................................ 42 Final of setting up ............................................................................................. 44
6. Service .............................................................................................................45 6.1 6.2 6.3
Maintenance ..................................................................................................... 45 Troubleshooting ................................................................................................ 45 Repair................................................................................................................ 45
see appendix A9
APPENDIX: A1 A2 A3 A4 A5 A6 A7 A8 A9 A10
Technical data Denotation of controller types Dimension sheet Errorlist Error tracing plan Accessories Changes and new functions Schematic diagram HOTLINE-NOTIC Setting data card
1.
ZETADYN 1DV System Information - Summary
1.1
Applications
ZETADYN 1DV controllers are designed for up to 33 KW drives (motor rated current 90A) where high positioning accuracy is required. They are mainly used in • Passenger and goods lifts • High-bay storage and retrieval systems • Cranes and material handling plants. ZIEHL-ABEGG supplies complete AC drives with asynchronous motors, digital encoders and ZETADYN 1DV controllers.
1.2
Functions and features
A microprocessor controls the drive in accordance with the time and distance related programs selected by main control system. Fully digital 4-quadrant motor speed control is accomplished by lowering the voltage at constant frequency. The whole drive cycle is controlled from start to stop. Features of the digital ZIEHL-ABEGG drive control system: • accurate control response with good dynamics and a high positioning accuracy • simple to commission and operate • comprehensive diagnostic system and data protection functions • high level of safety achieved by multiple monitoring systems • in case of maintenance, replacement of the device without new adjustment of the control device
Zetadyn 1DV Power supply
Inputs
PLC
Mains Microprocessor
Outputs
&
Power stage
Software
Motor temperature controlling
RS232C Interface
ZETAMON
Terminal ZIEHL-ABEGG ZETADYN1DV
P
Figure 1.1 Schematic ZETADYN 1DV
6
System information ZETADYN 1DV
↓
↑
Revolution counter
The logic design allows the equipment to be easily adapted to various applications.
1. Controls The superior control system communicates with the controller through floating inputs and outputs. Time and distance related control programs are selected by activating optically coupled inputs. The operating condition of the drive is continually signalled back to the controls through floating relay outputs.
ZIEHL-ABEGG asynchronous motors for variable drives have two electrically separated windings. The AC winding produces the drive torque and the DC winding the braking torque. M
drive
2. Parameterizing Commissioning, service and documentation are supported by digital computer technique: speeds, accelerations and other parameters specific to the system can be entered through text dialogue by using the integral display and operating unit. A password protects the system against misadjustments. It is also possible to parameterize through a PC or the ZETAMON software with user guide, which is available as one of the accessories.
n
brake
Figure 1.2 Torque generation
Both windings in the motor are activated separately, a three-phase thyristor speed controller feeds the AC winding, a semicontrolled DC bridge the DC winding (see Figure 1.3). Zetadyn 1DV drive B T
Encoder
T B
3. Regulation All programs are run at regulated speeds and independent of the load. The regulating control system can be used for speeds up to 3.5 m/s. The regulating range up to 1:100 allows a high degree of positioning accuracy.
PLC
set point generator
Digital 4-Qspeed controller
M 3
brake
Figure 1.3 Schematic diagram control circuit
This ensures perfect running response in all load situations. 4. Drive A high degree of stability of a drive at low load torques can only be achieved by continuous transition of drive and braking conditions.
No brake wear occurs in control operation up to STOP. The drive operates very quietly.
System information ZETADYN 1DV
7
1.3
Requirements
Ziehl-Abegg provides you with an optimally tuned D.C. drive with asynchronous motor, digital speed transmitter and controller ZETADYN 1DV. If you only purchase the controller - for example when retrofitting an old installation - please observe the following.
Motorselection:
Installation of a encoder:
Suitable devices are all pole-changing elevator motors having a pole ratio of 4/16.
Provided that no sleeve shaft encoder (e.g. Ziehl-Abegg -ET3R-1024) can be installed, there are three possibilities:
Pole pair ratios of 4/24 and 6/24 are partly suitable. For these motors, the course of the characteristic line for the d.c. injection brake (low-speed winding) in the range of speed 0 is a bit more unfavourable and there can be a small stopping jerk in the direction "EMPTY UP".
1.
Installation of a encoder linked to the motor shaft by means of a toothed belt. Documentation: LEM6.06.385 and LEM6.06.815. "Installation of an encoder G58H-1024"
Additional balance weights are to be removed, if necessary. An existing massive handwheel should be exchanged against a plastic handwheel. Besides the energy saving, additional reserves are liberated for the speed regulation.
2.
In case of gauges provided for the installation of an analog tacho with Euroflange, it is possible to use an incremental encoder of the same construction G71-xx/30. The tacho can be supplied with a shaft diameter (XX) of 07 and 11 mm.
Prior to the retrofitting (projecting phase) it is necessary to check whether the motor works properly in the pole-changing areas in all operating states. The motor as well as the gear have to work calm, i.e. without out-of-balance and clearance. Mechanical weaknesses cannot be improved by a control but can possibly make a controlled operation impossible.
3.
It is also possible to install an incremental encoder direct to same gears.
Controllerselection: The rated current of the controller has to be higher or equal to the rated current of the highspeed motor winding.
8
System information ZETADYN 1DV
Note: In case of own constructions, you have to pay attention to the fact that the encoder is mounted to the motor (gear) without any clearance, without any axial offset and solid as to the mechanical link. Preferably you have to choose an encoder with a resolution of 1024 increments/track. ZIEHL-ABEGG can be asked for documentation concerning the connection possibilities of encoders of external manufacturers.
2.
Mounting
2.1
Construction
ZETADYN 1DV controllers are designed for easy operation and maintenance. They are built to safety standard IP 00 and fulfil the requirements of VBG 4. The controller consists of the following components - shell - power section - controller circuit board - terminal. The control unit with a two-line illuminated LCD display, p.b. panel and the RS 232 C interface are flushfitted in the front panel. All connection terminals are not covered so that it is not necessary to remove the front plate.
ZETADYN 1DV
ZIEHL-ABEGG ZETADYN 1DV
P
ZIEHL-ABEGG
Figure 2.1 Controller
2.2
ZETADYN 1DV
Installing t he c ontroller
For the ambiance of the device, the conditions mentioned in appendix A1 "Technical Data" are valid. Mount the controller in switchgear cabinets vertically with the terminals at the bottom. -> Dimensions of the controller: see Appendix A3.
It is essential to provide adequate air cooling! The minimum distances shown in Appendix A3 must not be reduced.
Mounting
9
2.3
Connecting and occupation of te rminals
The controller must be connected up in accordance with the wiring diagram (see Appendix A8) Control cables must be separated from power cables. All controller inputs and outputs are floating, suitable for relay controls or memory programmable controls and carried through screw terminal connections. When connecting the control device, please observe the technical data (appendix A1). The controller ZETADYN 1DV corresponds to the safety class 1, of the DIN VDE 0558, Teil 1, Pkt.5.4.3.1.1.
2.3.1 Mains Prior to the connection of the supply voltage, you have to check whether the indications made on the identification plate of the control device are the same as those of the necessary connection values.
The current supply is to be connected according to figure 2.2: "PE-L1-L2-L3"
Connection o f the s upply v oltage of t he p ower sta ge The system can be protected (F1-3) by means of slow-acting fuses to suit the rated current.
"L1-L2-L3"
Connection of the s upply v oltage of the c ontroller b oard As power safety, time-lag fuses (F4-6, rated current > 1A) are to be used.
"11-12"
Connection of the cooling fan Voltage: AC 230V, 50/60 Hz. In case of devices starting with a rated current of 80A, an additional fan for cooling the power stage is incorporated. The fan is switched by means of an integrated thermal contact. Use a slow-acting fuse (rated current >1A) for protection. In case of devices with a rated voltage of 400V, the fuse protection can be effected by one of the fuses F4-F6.
L1 L2 L3 F4
F5
F6
controller board
mains PE 11
N
M 1
12
L1 L2 L3
F1
2
1
F2
3
4
F3
5
6
K0
2
1
L1
3 5
4 6
L2 L3
K0´
main contactor
fan (only 1DV80 &1DV90)
T
power stage ZETADYN 1DV
.
Figure 2.2 Connection of the voltage supply
The employment of an interference filter is disregarded. See figure A8 / schematic diagram and also A6 / accessories. The controller circuit board must be connected in the same phase sequence as the power section! Connection must be made in front of the main contactor "KO".
10
Mounting
2.3.2 Motor Connect terminals on the control unit and the ZIEHL-ABEGG motor with the same coding (see figure 2.3). "U1-V1-W1"
AC winding AC winding in the motor terminal box is marked "2U1-2V1-2W1".
"F1-F2"
DCwinding
"ET 1-ET5"
En c o d e r Connection of the ZIEHL-ABEGG-encoder. Use a five-core, screened cable. The correct connection of the monitor has to be ensured.
"MB1-MB2"
Spring-loaded safety brake This exit switches the spring-loaded safety brake by means of an external contactor relay K*. In order to achieve an optimum start-up and positioning reaction, the control has to open and close the brake without delay via this contact.
"P1-P2"
PT C thermistor Connecting PTC thermistor in accordance with DIN 44 081, for monitoring the motor temperature. If the monitoring is not to be effected via the control device, a jumper has to be installed between these two terminals.
ZETADYN 1DV
MOTOR 1U1
F1
F1
F2
1U2 1V1
1V2
1W1
1W2
F2
power stage
motor windings
W1
2W1
V1
2V1
U1
2U1
The maximum permissible test voltage for the PTC thermistor is 2.5V. Take care when using electrical continuity testing equipment.
controller board fan P1
P2
ET1
ET2 ET4 ET3 ET5
MB1 MB2
M
9U1
1
9U2
encoder ET1 ET2 5
ET3 ET4 ET5 ET6 GU5 GU6
K*
GU7 P2
brown green white yellow grey
ET
pink
brown green
Figure 2.3 Connection of motor,
white
encoder
thermistor
and brake.
N PTC
P1
L1
brake a
K* K* varistor rectifier
+ -
b
U
.
Mounting
11
2.3.3 Control in puts The inputs are coupled optically. For selecting the inputs there are two possibilities (figure 2.4): a) By means of a potential-free contact, the higher control links the terminal of the control voltage "U0" to the corresponding input.
b) The higher control feeds an external voltage of +24V to the input. The terminal "GND" serves as reference potential.
a)
GND
U0
RF
V1
V2
V3
VZ
RV1
RV2
ZE1
ZE2
ZE3
GND
U0
RF
V1
V2
V3
VZ
RV1
RV2
ZE1
ZE2
ZE3
b)
+24V
GND
Figure 2.4 Triggering possibilities
Control inputs: "GND"
Reference po tential
"U0"
C o n tr o l v o l ta g e DC output of approx. 21V for activating the inputs.
"RF"
Controller re lease The input "RF" has to be triggered during running.
"V1" "V2" "V3" "VZ"
P o s i ti o n i n g s p e e d Intermediate speed Travels peed Readjustment s peed
"ZE1" "ZE2" "ZE3"
Additional sp eed V_ ZE1 Additional sp eed V_ ZE2 Additional sp eed V_ ZE3 These inputs are provided for triggering various functions in the controller. The adjustment is effected in the menu /INTERFACES. The additional speeds V_ZE1, V_ZE2 and V_ZE3 of the same name are selected by the manufacturer. Preferably these speeds are to be used for inspection run and restoring control.
"RV1" "RV2"
Predirection 1 UP Predirection 2 DOWN If the controller is connected up as suggested in circuits A8 (in the Appendix), the motor will run (with works setting) anti-clockwise when the "RV1" input is activated and clockwise when the "RV2" input is activated (viewed from the drive end of the shaft).
12
Mounting
2.3.4 Control outputs The relay outputs are in the form of floating change-over contacts or NO contacts. The special contacts "SK1"-"SK3" can be programmed in the menu /INTERFACES in another way than in the factory setting and can be assigned with other functions. In this menu, it is also possible to invert the function of "RB".
"ST"-
Fault Contact ST1-ST2 is closed when no failure occurs.
"SK1"-
Special contact 1 Contact K11-K12 is closed when the speed is higher than 0.3 m/s.
"SK2"-
Special contact 2 Contact K21-K22 is closed when the rated speed is exceeded by 10% .
"SK3"-
Special contact 3 Contact K34-K31 is open when the motor temperature control triggers off.
"RB"-
Controller a ctive When closing the contact RB1-RB2, the control is to switch the main contactor K0 without delay.
"MB"-
Spring-loaded s afety b rake When closing the contact MB1-MB2, the control is to switch the spring-loaded safety brake without delay. ST
SK1
Fault
specialcontact1
SK2
(V>0.3m/s)
ST1
ST2
K14
K11
RB
specialcontact2 (V>1.1*V_NENN)
K12
K24
K21
controlleractive
MB
(main contactor control)
K22
RB1
RB2
SK3
brake
special contact 3
(mot.temp.control)
MB1
MB2
K34
K31
Figure 2.5 Control outputs
Mounting
13
3.
Control and controller functions
The functional equipment of the controller ZETADYN 1DV makes it possible to adapt to the various applications. In the following, we give a short description of the factory presetting. 3.1 gives a general description of the control of the controller. 3.2 gives a detailed description of specific functions of the device.
Table: factory presetting Normal running mode: Run at high running speed "V3" and positioning run at "V1" Run at intermediate speed "V2" and positioning run at "V1" In both cases, the decelerating distance is driven depending on the path, i.e. when the driving command "V3" or "V2" respectively is switched off, it is always the same decelerating distance that is travelled independent from the actual speed achieved at the moment (arch travel). Readjustment: Readjustment possibility with speed "VZ". Manual and service operation: In addition, three speeds "V_ZE1", "V_ZE2" and "V_ZE3" are available which are not regulated depending on the path.
Output: Controller active - "RB" With the output "RB" the control device switches the main contactor to the currentless state. Output: Mechanical brake - "MB" With the output "MB" the control device switches the mechanical stopping brake.
Monitoring functions: Checking the input speed (0.3m/s) by means of output "SK1". Checking of the maximum speed by means of output "SK2". Checking of the motor temperature by means of output "SK3". Fault message: The control device indicates a fault at the output "ST". The following functions are monitored: - power outage - cyclic change - heat sink excess temperature - motor temperature - encoder breakage - start-up monitoring - parameterization - deceleration monitoring Additional functions: The inputs "ZE1", "ZE2" and "ZE3" as well as the outputs "SK1", "SK2" and "SK3" can be programmed with special functions in another way than in the factory setting. Examples:
Changing over between two completely separated parameter sets. Switching off the forced air cooling of the motor with the function of the after-running timerelay. • Switch output for the monitoring of a freely adjustable speed limit. • •
14
Control and controller functions
3.1
Controlling of ZETADYN 1DV
Figure 3.1 shows control of a simple travel between two stops, referred to as observe that the wiring plan shown in appendix A8 is met by the control.
V
NORMAL TRAVEL.
Please
const. speed deceleration
start acceleration
const. speed normal slow down
V3
V1 1
2
3
4
56
7
8
t
inputs RF V1 V3 RV1 RV2 outputs RB MB
Figure 3.1 Normal travel
(1) The higher control sets the direction of motion for the inputs "RV1/RV2" and triggers the inputs for the running speed (in this case "V1" and "V3"). The "controller release -RF" can already be fed. It is also possible to connect it only when the direction and the speed are fed. By means of the output "Controller active RB" the control device indicates that the input signals have been accepted and that it is ready for a new run. When switching "RB" the main contactor K0 has to be closed. When switching the output "Mechanical brake -MB" the control of the brake has to open immediately and without delay.
(2) The drive accelerates until the preset speed is reached. (3) A travel at a constant speed follows, until the activation of the travel speed ("V3") is cancelled. (4) The drive decelerates to the positioning speed "V_1". (5) After a short distance covered, the positioning speed is switched off. (6) The drive continues to decelerate. (7) The control device disconnects the output "MB". The control is to close the brake without delay. (8) The main contactor "K0" has to be switched on until the contactor "RB" is switched off.
The spring-loaded safety brake is to be switched on and off by means of the relay "MB". This is the only guarantee that the control device is able to control start-up and stopping without jerk. The main contactor "K0" is to be switched on and off by means of the relay "RB". This is the only guarantee that the main contactor is switched in the currentless state and enables startup and stopping without jerk. In case of trouble, i.e. when the relay "ST" is released, the control has to make sure that the mechanical brake and the main contactor are immediately switched off.
Control and controller functions
15
3.2
Description of controller functions
3.2.1 Switching on and off The controller switches itself on when the main voltage is applied to the controller circuit board. All three mains phases must be switched on simultaneously. The output relay trouble "ST" switches automatically on about 1 sec after the control device has been switched on. Until now, the state of the control inputs is ignored by the controller.
When the supply voltage of the controller board is switched off, all relay outputs open without delay. The higher control has to close the springloaded safety brake and open the main contactor "K0". The control device blocks the power semiconductors. If the controller is switched off during running, the drive is decelerated because of the braking torque of the spring -loaded safety brake.
L1-L2-L3 controller board outputs RB MB ST t ~ 1s
Figure 3.2 Switching on and off the controller
3.2.2 Start and ac celeration (1) The main control system activates the inputs "Speeds - V_" together with one "Direction Preset - RV_". The controller closes the output relay "Controller ready RB" and the relay "Spring-loaded safety brake - MB".
(2) The main control system opens the springloaded safety brake. The controller accelerates up to the maximum activated speed in accordance with the set acceleration with rounded transitions.
V V3
1
inputs RF V1 V3 RV1 RV2 outputs RB MB
Figure 3.3 Start and acceleration
16
Control and controller functions
2
3
t
3.2.3 Distance-controlled deceleration - Arch travel In case of decelerating runs, the path dependent deceleration is carried out by the driving commands V3 and V2 according to the positioning speed V1. To do this, the parameter /INSTALLATION/ S_ABH has to be ON (factory setting). In case of all other change-overs between speed presettings the running curve is carried out depending on the time.
times (see illustration 3.4), independent from the speed achieved at the decelerating point (4). Functioning: If the final speed set (Figure 3.4) has not yet been reached at the decelerating point (4), the drive continues to accelerate. The control device determines the point X from which the deceleration has to be initiated in order to reach the stop with the positioning speed V1. Now the control device rounds out the running curve and decelerates by means of the deceleration A_NEG set.
Advantages: The path dependent deceleration offers advantages if the final speed (V3 resp. V2) cannot be achieved in case of runs between stops that are close together. In such a case, the control device carries out an arch travel. The control device provides for continuous rat runs and the shortest possible cycle
Because of that, in case of the ARCH TRAVEL and the NORMAL TRAVEL, the decelerating distances S_31(4 -> 5) and the rat runs s_1 (5 ->6) are the same.
V3
V3
X
V
V
S_31
S_31 V1
V1
4
inputs
5
6
t
4
inputs
5
6
V3
V3
V1
V1
NORMAL TRAVEL: V3 is switch off during constant travel.
ARCH TRAVEL: V3 is switch off during the accelaration.
t
Figure 3.4 Comparison normal travel and arch travel
Control: The control has to feed the driving command V1 prior to the removal of the driving command V3 (resp. V2). Side-effects: In case of controls showing a signal running time of more than 10 ms, it islonger possible the rat for ARCH travel is no thethat same as run for NORMAL travel. In addition there is a small error with the total decelerating distances measured (S_30, S_20). The controller is able to compensate this error in case of an almost constant signal operation time. To do this, the signal operation time has to be entered in /INSTALLATION/T_SIG at commissioning.
Control and controller functions
17
3.2.4 Time ba sed dec eleration Except the decelerating transfers from
After switching off the current speed setting, the control device decelerates depending on the time up to the highest speed still controlled and according to the deceleration set with rounded out transfers.
"V3" to "V1" and "V2" to "V1" all other speed transfers are carried out depending on the time.
V V_ZE3 V_ZE2
V_ZE1 t inputs RF ZE3 ZE2 ZE1 RV1 RV2
Figure 3.5 Control DECELERATION (Example Manual control with V_ZE1, V_ZE2 and V_ZE3)
3.2.5 Distance-corrected deceleration of "V3", "V2" and "V1" The control device is able to delay the switching off of the running signals by a distance set. It is possible to delay "V3" by the path "S_DI3",. "V2" by the path "S_DI2" and "V1" by the path "S_DI1" and then switch it off.
ADVANTAGE: In the shaft, the disconnecting tag of "V3" is set as far as possible from the flush "V1". After the desired running curve is available, the remaining rat run is eliminated by introducing this value in parameter S_DI3. Furthermore, it is possible to correct the disconnecting tag for the flush "V1" by means of S_DI1.
V
prerequisite:
V3
/ INSTALLATION / S_ABH = EIN (factory setting)
→ S _DI3
*
V1
4a
inputs
4
5
t
The predirections and the controller release till the end of travelling.
RF
V1 V3 RV1
Figure 3.6
RV2
Example "V3" is delayed by the path "S_DI3" and then
switched off.
18
Control and controller functions
3.2.6 Normal s low do wn The main control system no longer activates the inputs speed "V_" or direction preset "RV_". The controller decelerates down to a standstill in accordance with the set deceleration /DECELERATING/A_NEG with rounded transitions. When the speed drops below the /DECELERATING/V_BR speed, the controller opens the output relay "Spring-loaded safety
brake - MB" so that the spring-loaded safety brake engages at the same moment as that at which the speed 0 is reached. The controller blocks the power semi-conductors and closes the output relay "Controller ready - RB".
V1
V
V _BR 6
inputs
7
t
8
RF V1 RV1 RV2 outputs ST RB MB max.1,5s
Figure 3.7 Controlling NORMAL SLOW DOWN with control signals over time
3.2.7 Quick stop If the higher control swiches the input "RF controller release" off during running, the control device decelerates with the maximum deceleration /INSTALLATION/A_MAX set.
If the value 3.5 m/s2 is set for A_MAX (factory setting), the control device imm ediately switches off the output "MB" and "RB". In this case, the drive is only decelerated by means of the mechanical stopping brake.
V3
/INSTALLATION/A_MAX < 3.5 m/s² V
Figure 3.8 t inputs RF
Quick stop when switching off the "Controller release - RF" .
V1 RV1 RV2 outputs ST RB MB
Control and controller functions
19
3.2.8 Readjustment For the readjustment of the correction of the elongation of a rope when discharging the cabin, the driving command "V_Z" is triggered. For safety reasons, the control device ignores all other speed settings when triggering the input "V_Z". Unlike the normal positioning process
(normal stop), the mechanical brake "MB" engages without delay. In order to avoid oscillations, the control should wait a certain time until the rope is put at rest again.
V
V _Z
t
inputs RF V_Z RV1 RV2 outputs ST RB MB
Figure 3.9 Readjustment with the input "V_Z"
3.2.9 Direction reversal The control device offers the possibility to change the direction set during running. This characteristic is of particular importance in case of manual control. In Figure 3.10, the switching processes between the change of direction are illustrated in detail. V..
V
-V.. inputs RF V.. RV1 RV2 outputs ST RB MB
Figure 3.10 Reverse direction during running
20
Control and controller functions
t
3.2.10 Short travel Use: The SHORT TRAVEL program offers advantages if the final speed (V3 and V2) cannot be activated when travelling between two very close stopping points.
Control: (see figure 3.11). When triggering the controller release RF, the driving command V1, an additional input ZE3 and the direction set RV1/2, the drive is carrying out a distance S_KF set by the operator. The control device itself is optimizing the driving course by means of the acceleration and deceleration set. After having carried out the distance S_KF (1->5), the drive is running at the positioning speed V1. When reaching the flush switch (6), the running signals (V1, ZE3 and the direction set) are switched off.
Example: V3 is switched off 2 m before flush. V2 ist switched off 1 m before flush. But there is a floor distance of only 0.7 m. In this case, it is possible to use the short travel in order to carry out a run depending on the distance and using the optimum time possible.
V
S_KF
V1 1
5
6
t
inputs RF V1 ZE3
RV1 o. RV2 outputs RB MB
Figure 3.11 Short Travel
Requirements: The SHORT TRAVEL is not set by the factory. It is necessary to program an additional input (in this example ZE3) for the function "Short travel": -->/INTERFACES/I_ZE3 = Short travel. After programming this function, the parameter S_KF appears in the menu "TRAVELLING" in which the short travel distance is directly put in in meters: --> /TRAVELLING/S_KF = _.__ m
Control and controller functions
21
3.2.11 Troubles The control device controls - the mains voltage (phase sequence, - outage) - the speed - the heat sink temperature - the encoder signals - the motor start-up - the motor direction - the motor temperature. The run program will be stopped if the controller identifies troubles. The controller blocks the power semi-conductors. The output relay "mechanical brake - MB" and "Fault - ST" are switching off immediately.
The main control system must close the springloaded safety brake and open the main contactor "K0". If an error occurs during running, the drive is delayed because of the braking torque of the spring-loaded safety brake. In order to acknowledge the error, the triggering of the controller release "RF" has to be stopped. After switching the controller release "RF" on again, the fault relay "ST" picks up again.
inputs RF outputs RB MB ST
faultdetection
quitwithinputRF
Figure 3.12 Consequence of the trouble and acknowledgement
Exception: After mains phase outage, excess temperature of the heat sink or of the motor the output relay automatically picks up after the trouble has been eliminated when parameter /INTERFACES/QUIT is switched on (factory setting is OFF). Specific control device monitorings can be switched off in /ZA_INTERN/MASK1 to MASK3 (described in 4.3.11).
22
Control and controller functions
3.3 To ensure safe operation of the controller Basically, electronic equipment is not failure-proof. The user is responsible for ensuring that the drive is in a safe condition in the case of controller failure. It is essential to observe the following three instructions:
The spring-loaded safety brake must be operated without delay through the relay "MB". This is the only way to ensure smooth control actions from the controller. The main contactor "K0" has to be switched on and off without delay together with the relay "RB". This is the only guarantee that the main contactor is switched in the currentless state and enables start-up and stopping without jerk. In case of trouble, i.e. when the relay "ST" is released, the control has to make sure that the mechanical brake and the main contactor are immediately switched off.
Control and controller functions
23
4.
Operation and settings
The user can easily adapt the controller to any particular job. The system can be commissioned and operated by either of the following two very simple methods: 1. Operation through the keyboard and the LCD display with simple text dialog.
The parameter menu structure is the same for both communication methods. The parameters set can be protected against unintentional or unauthorized change by means of a password (numbers ranging vom 1 to 9999).
2. Remote operation with a PC and the ZETAMON software available as an extra.
4.1
Parameters may only be changed when the drive is at a standstill.
Operating through keyboard and LCD display
LCD and the keyboard offer the operator the following direct facilities: - setting all the parameters required for commissioning - performing simple measuring and control operations and - recording the operating states. Programming is very simple, by means of the three push buttons. The parameters available are divided into menus according to whether they are belonging together. The selection of a menu is effected by means of the arrow keys (see figure 4.1). When pressing the key [P], you change to the parameters assigned to the menu. The selection of a parameter is effected by means of the arrow keys. When pressing the key [P], it is possible to change the parameter using the arrow keys. When pressing the key [P], you return to the parameter selection. When pressing the key [↓] and [↑] at the same time, your return to the menu selection.
selection of a menu
P
selection parameter with
with
change parameter P
with
& Figure 4.1 Function of the keys
There are two possibilities in order to change the parameters and two kinds of indication: V_3
1.20 m/s
Adjustment by putting in a numerical value (in this case: 1,20 m/s).
Travel speed ANL
ELEVATOR
Installation type RF RV12 V123 MB N_IST
1200 min-1
Adjustment by selecting among possibilities already set (in this case: ELEVATOR) Indication by means of "beam spot" representation
Indication by means of "bar" and numerical value representation
401
Figure 4.2 Examples
24
Operation and setting
Example of setting the parameters In menu /TRAVELLING, the speed V_3 is to be changed (see figure 4.3). 1. Once the supply voltage has been applied to the controller circuit board, the following will appear on the LCD display:
Parameter explanations will be replaced by the setting box. If no changing-over to the setting field is effected, the input is already protected by a password (see 4.3.8).
ZIEHL-ABEGG ZETADYN 1DV 2. Press any key to make the appear on the display.
MONITOR
3. Press the key [ ↓] to scroll to menu.
TRAVELLING
7. It is possible to change the value by means of the key [↓] or [↑].
menu
8. Acknowledge the value in the setting box by pressing [P]. The setting value will change up on the display. The new value will be accepted. The arrow stops flashing and the parameter explanation reappears in the second line.
4. Activate the list of parameters by pressing (P). The first parameter V_1 will appear on the display.
9. Press [ ↓] and [↑] simultaneously when the TRAVELLING menu will appear on the display again.
5. Press [ ↓] to scroll to parameter V_3. 6. Press [P] to activate the setting box. An arrow will flash on the left, in the second line.
60 minutes after the last key has been actuated, the start indication automatically appears. Furthermore, the lighting of the display is switched off. ZIEHL-ABEGG ZETADYN 1DV any key
selection of a menu MONITOR ********* DIST. & TIMES ********* STATISTIC ******** TRAVELLING ************
&
P
selection of a parameter V1 0.050 m/s >Position V_2 >Inter
0.70 m/s V_3
1.20 m/s
>Travel speed P V_3 1.20 m/s >..............1.19 m/s 402
change of the parameter
Figure 4.3 Example for parameterization
Operation and settings
25
4.2
Remote operation with PC and
ZETAMON
software
The following facilities are available to the operator using a PC and the specially developed ZIEHLABEGG ZETAMON software: - setting all parameters, - commissioning the drive, - evaluating, protecting and copying travel diagrams and data records, and - measuring the controller parameters, travel diagrams and signals. The ZETAMON software is available as an extra accessory. It requires an IBM or an IBM compatible PC with the following minimum equipment: - XT/AT with 640 KB RAM and a disk drive - MS-DOS system, version 3.30 or a subsequent version. The handling of this universal software is described in a concise and clearly arranged manual. The wiring of the connection cable between the control device and the PC is described in this manual.
26
Operation and settings
4.3
Summary of parameters
The parameters are divided into menus (see figure 4.4).Only the four stressed menus are important for commissioning.
Prior to the first run, it is necessary to put in the installation data in the menu "INSTALLATION". If the parameter AUTO is selected in this menu, the parameters are preset according to the installation data. Experience has shown that only small changes are necessary for optimization.
MONITOR **************** DIST. & TIMES **************** STATISTIC **************** TRAVELLING
Indication: State of the inputs and outputs, actual and nominal speed Indication: Distances and times
Indication: Statistic indications and administration of error lists Input:
Travel speeds
Input:
Acceleration ramp and start-up reaction
Input:
Deceleration ramp and brake reaction
**************** ACCELERATING
**************** DECELERATING
**************** CONTROLLER **************** OPERATING **************** INSTALLATION
If necessary: Intervention of the speed regulator
If necessary: Possibility to allocate a password or to change to the national language.
Single input prior to the first travel
**************** INTERFACES **************** EXPANSION **************** ZA-INTERN ****************
If necessary:Change of the factory set function of inputs and outputs This menu only appears in case of control devices disposing of an expansion card Reserved for special applications
Figure 4.4 Menu outline
Operation and settings
27
4.3.1 The menu "MONITOR" Contents: Menu "Monitor" shows the state of the control inputs and outputs. An active control signal is indicated with a "Beam spot". In addition, the controlled sizes actual speed value and nominal speed value as well as the controller output are indicated.
MONITOR ****************
RF:RV12:V123:VZ O O O
Indication of the inputs triggered in the automatic operation. "RF","RV1","RV2","V1","V2","V3" and "VZ"
RF:RV12:V1:ZE123 O O O
Indication of the inputs triggered in the inspection operation. "RF","RV1","RV2","V1" and "ZE1 - ZE3"
RF:RV12:V1:RB:MB O O OO RF:ST: O
:SK123 OOO
N_REAL
300min-1
N_PROG
300min-1
-......CO......+ | Figure 4.5 Menu "Monitor"
28
Operation and settings
Inputs and outputs important for start-up and stopping.
Indication of the trouble relay "ST" and the special contacts "SK1SK3".
Indication of the real speed N_REAL.
Indication of the programed speed N_PROG.
Indication of the controller output CO. - = Brake , + = Drive Normally, the range limits are not to be achieved. In case of constant run, the pointer should only slightly move. In "+" resp. "-" a beam spot appears at "Move" resp. "Brake" in case of saturation. Normally a beam spot is not to be seen.
4.3.2 The menu "DISTANCES & TIMES" DIST. & TIMES ************************** S_GES
Contents:
In menu "Distances & Times", measured and calculated values are indicated.
0.00 m
Total distance driven of the last run
Total distance S_1
0.00 m
Dist. at V_1 S_2
Measured distances at constant speed with "V_1", "V_2" and "V_3".
0.00 m
Dist. at V_2 S_3
0.00 m
Dist. at V_3 S_10
0.00 m
Total decelerating distances after switching off the driving command "V_1", "V_2" and "V_3" until the device stops.
Dist. at V_1 -> 0 S_20
0.00 m
Dist. at V2 -> 0 S_30
0.00 m
Dist. at V3 -> 0 S_21
0.00 m
Calculated dist. V2->V1 S_31
Calculated decelerating distance needed from the time of switching off "V2" resp. "V3" until the positioning speed "V_1" is reached.
0.00 m
Calculated dist. V3->V1 T_GES
0.0 s
Total time driven of the last run.
Total travel time T_MB
0 ms
Measured time from the time the relay "MB" picks up until the first rotation.
.
Figure 4.6 Menu "Distances & times"
Operation and settings
29
4.3.3 The me nu "S TATISTIC" Contents: In menu "Statistics", statistic data are shown and an error list is kept. The data are preserved after having switched off thecontrol device.
STATISTIC ********************** STATO
Error list
Error-List: STAT1
100.50h
Indication of the total working hours
Operating hours total STAT2
10.5h
Operating hours acti STAT3
2303
Indication of the working hours where the drive has actively worked
Indication of the number of runs
Number of travels STAT4
OFF
This parameter enables you to delete the error list.
Reset error list .
Figure 4.7 Menu "Statistic" Note
for STAT0:
The error list is called like a normal parameter. But instead of changing the contents, the keys [↓] and [↑] enable you to scroll between the entries. STATO
P
Error list RV1 / RV2 missing >
2.00h-12-12 Phase failure >
1.00h- 3-12 Power stage ... >
working hour error number .
state of the controller
Bild 4.8 Parameter "STATO"-error list
30
Operation and settings
In total, 255 error messages are administered. If more than 255 messages appear, the oldest ones are deleted.
0.00h-29-12
If the error list is called, the last error is indicated first. Working hour, error number and the state of the controller are indicated as additional information. A description of possible entries is given in appendix A4.
4.3.4 The menu "TRAVELLING" Contents: In menu "TRAVELLING", the running speeds are set. When putting theses data in, you have to pay attention to the fact that V1 < V2 < V3. TRAVELLING ************************** V_1
0.050 m/s
Positioning speed V_2
Positioning speed V_1.
0.80 m/s
Intermediate speed V_3
1.20 m/s
If necessary, intermediate speed for normal operation. High running speed for normal operation.
Travel speed V_Z
0.010 m/s
Additional speed V_ZE1
0.30 m/s
Additional speed ZE1 V_ZE2
In case of installations with readjustment, the additional speed V_Z is to be used. The speeds V_ZE1, V_ZE2 and V_ZE3 are preferably to be used for restoring control, inspection run or manual control.
0.60 m/s
Additional speed ZE2 V_ZE3
0.90 m/s
Additional speed ZE3 .
Figure 4.9 Menu "Travelling"
Operation and settings
31
4.3.5 The menu "ACCELERATING" Contents: In menu "Accelerate", the acceleration ramp is defined. In addition, it is possible to optimize the start-up reaction.
ACCELERATING
Accelerating
V_3
**************************
R_POS2
A_POS
0.70 m/s2
>Acceleration R_POS1
A_POS
40 %
R_POS1 0
>Rounding1
t inputs
R_POS2
RF
50 %
V1
>Rounding 2 T_VB
V3 RV1
100 ms
>Prelimary braking time
RV2 outputs RB
M_VB
25 %
>Pre. braking torque
MB T_VB
motor M0
M_0
"drive"
5% M_VB
>Starting torque
"brake"
AC-motor-winding DC-motor-winding
.
.
Figure 4.11 Effect of the parameters
Description of the parameters:
An optimum start-up reaction requires that the main contactor is switched on with the exit "RB". This is the only guarantee that the main contactor is switched in the currentless state.
A_POS
Presetting of the positive acceleration.
R_POS1 R_POS2
Canging the upper or lower rounding, if necessary. A greater value causes a smoother rounding.
T_VB
Pre-braking period: Maximum time from switching the contact "MB mechanical brake" until the speed regulation starts.
M_VB
Pre-braking torque: Size of the d.c.-"brake"-part during
The control device opens the mechanical brake via the relay output "MB". In order to avoid that the motor works against the brake that opens, the start-up process is decelerated by means of the pre-braking period T_VB. In this period of time, the d.c. winding of the motor is impinged with a direct voltage, the prebraking torque M_VB. In order to avoid that the motor turns back too heavily or to overcome an initial breakaway
the time T_VB.
torque,M_0 it isat possible to connect the starting torque the beginning of the run.
M_0
32
Starting torque: Size of the a.c.-"drive"-part after the time T_VB.
Operation and settings
-> The optimization of the start-up reaction is described in detail in chapter 5 Commissioning.
4.3.6 Menu "DE CELERATING" Contents: In menu "Decelerating", the decelerating ramp is defined. In addition, it is possible to optimize the positioning reaction.
DECELERATING
V
************************** A_NEG
R_NEG1
V3
0.70 m/s2
>Deceleration A_NEG
R_NEG1
60 %
S _DI3
*
>Rounding 1 R_NEG2
R_NEG2
90 %
V1 V_BR
>Rounding 2 V_BR
t
>Brake engagement M_NB
4a
inputs
0.001 m/s
4
5
RF
35 %
V1
>Braking torque
V3
S_DI1
0 mm
RV1
>Dist. correction V1 RV2
S_DI2
0.00 m
outputs
>Dist. correction V2
RB
S_DI3
MB
0.00 m
>Dist. correction V3 Motor-DC-winding
.
M_NB .
Figure 4.12 Menu structure
Figure 4.13 Consequence of the parameters
Description of the parameters: Presetting of the negative acceleration - deceleration. Canging the upper or lower rounding, if necessary. A greater value causes a smoother rounding.
If the speed falls below speed V_BR, relay "MB" switches off. In the period of time until the mechanical brake is really closed, the DCwinding of the motor is supplied with a DCvoltage, the pre-braking torque M_NB.
V_BR M_NB
Speed at which the brake comes in. Size of the after-braking torque.
S_DI1 S_DI2 S_DI3
Distance at which the driving command "V1", "V2" and "V3" is switched off time delayed from the control device.
This voltage is switched off after a preset time (/ZA-INTERN/T_NB) and the relay is released. If the control switches the main contactor with this contact, it is guaranteed that the opening of the main contactor is effected currentless.
A_NEG R_NEG1 R_NEG2
4.3.7 The men u "CO NTROLLER" In menu "Controller" it is possible to adjust the intervention of the speed regulator by means of the parameter DYN. If the value is too low, it is possible to have noticeable standard tolerances at the speed transfers. Normally, the setting range is between 70 and 100 %.
Operation and settings
33
4.3.8 The me nu "O PERATING" Contents: In menu "Operating", it is possible to change the national language, to allocate a password and to carry out an additional parameter saving.
OPERATING ********************** LASP
ENGLISH
>Language PW_E
....
LASP Selection of the national language -Deutsch -English -Espanol
> Password input PW_N
....
> New Password PA_SI
OFF
> Parameter-saving RESET
PW_E If is is not possible to change the parameters when the drive is out of action, first of all the set password has to be put in in this parameter. No password has been allocated by the factory. If a password is unknown, it is possible to ask the manufacturer. To do this, please state the service number in /ZA-INTERN/SE_NR (section INFO).
0
> Reset controller total Figure 4.14 Menu structure
PW_N
Allocation or change of a password with four digits at the maximum ranging from 1 to 9999. A password should only be put in after the commissioning has been completed. Example: Allocation of password with number 12 1. Put in 12 in PW_N 2. Put in 12 a second time in PW_N 3. On the display appears blinking NEW PASSWORD -----> 12 4. After actuating a key, all parameters except PW_E are blocked. 5. In order to be again able to change parameters, the password (in this case 12) has to be put in in parameter/PW_E.
PA_SI
The control device disposes of two parameter sets which can be changed-over by means of one of the inputs "ZE1-3". Besides the active working storage, each parameter set has a security storage. The following parameter set operations are possible: - OFF - W->S - W<-S
Truncate function. Copy the current parameters from the working storage into the security storage. Recopy already stored parameters from the security storage into the working storage. PARA 1->2 Copy parameter set 1 after parameter set 2. RESET
34
With this parameter, it is possible to reset the control device to the initial delivery state. After putting in number 99 and confirming an additional security inquiry, the factory setting is loaded. After finishing this action (about 40 s), the indication appears that the control device is to be switched off for a short time.
Operation and settings
4.3.9 The menu "INSTALLATION" Contents: In menu "INSTALLATION", values depending on the installation have to be put in once prior to the first travel. INSTALLATION ************************ ANL
ELEVATOR
>Installation type N_NENN 1380 min-1 >Nominal speed of motor V_NENN 1.20 m/s >Nominal travel speed GEBER
Direct ? [YES]
P
>Encoder type
V_NENN
AUTO
OFF
[NO]
P
ET3R-1024
1.20 m/s
>
Suspension
1:1
1.20 m/s
>Automatic parameter
Gear ratio
1:38
Part1
Gear ratio
1:38
Part2
P
MO_DR
LEFT
>Direction of motor S_ABH
ON
>Distance dependency A_MAX
D_wheel
3.5m/s2
>Max. deceleration T_SIG
650 mm
P
0.00 s
> .
Figure 4.15 Menu structure
ANL
Selection of the type of installation -Elevator (with counterweight), -running gear, -lifting gear (resp. elevator without counterweight).
N_NENN Input of the nominal motor speed according to the indication on the motor identification plate. V_NENN Input of the nominal speed of the cab at the nominal motor speed N_NENN. When selecting this parameter, there is the inquiry from the control device whether V_NENN is to be put in directly or whether it has to be calculated by means of further installation data. In case of the installation type "ELEVATOR", the suspension, the gear ratio as well as the friction wheel diameter are inquired for calculation. A value can be set by means of the arrow keys and the text can be scrolled by means of the key P. With this conversational inquiry it is not possible to scroll back.
Selection of the type of the encoder installed at the motor. - ET 3R-1024 - ET 3F-64 - ET 3F-48 - EXTERNAL By using an encoder of any other manufacturers with 1024 pulses per revolution you can also use the setting ET3R-1024. You have only to use the parameter EXTERNAL by an encoder with an other number of pulses per revolution. GEBER
Operation and settings
35
In case of the setting "EXTERNAL", the parameter G_AUF with which it is possible to set any transmitter resolution ranging from 64 to 1024 pulses/revolution is faded in after this parameter.
G_AUF 1024 Encoder resolution
AUTO
Automatic parameter pre-assignment: - OFF no effect - ON The parameters in /TRAVELLING, /ACCELERATING and / DECELERATING are preassigned once according to the type of installation, nominal speed and nominal revolution. After the pre-assignment, AUTO is again at "OFF".
MO_DR
Changing the motor direction.
S_ABH
Selection how the arch travel is to be driven: - ON In case of deceleration transfers from V3 -> V1 and V2 -> V1, the arch travel is driven dependent on the distance and using the optimum time possible. - OFF The arch travel is driven time dependent at all speed transfers.
A_MAX
Input of the maximum deceleration in case the controller release "RF" is switched off during running. At a value of 3.5 m/s2 (factory setting), the power unit is immediately switched currentless and the output relay "mechanical brake - MB" and "controller active - RB" are released without delay.
T_SIG
In case of controls where the signal operation time is not to be neglected, the speed dependent distance errors are automatically compensated by the control device when this time is put in here.
36
Operation and settings
4.3.10 The men u "IN TERFACES" Contents: In menu "Interfaces", it is possible to change the factory functions of the programmable inputs and outputs. INTERFACES ************************** I_ZE3
V_ZE3
> Input ZE3 O_SK1
V<0.3m/s
> Output SK1 O_SK2
1.1V_NENN
> Output SK2 O_SK3
Function of the additional input "ZE3" - V_ZE3 The input is used for selecting the speed V_ZE3. The speed "V_ZE3" is put in in menu "TRAVELLING". - 2.PARASET This input switches to the second parameter set. - Short travel The input is activated for the "Short travel"- log.
TEMP.MOT
> Output SK3 O_RB
Function of the special contact O SK 1 Contact K11-14 is closed if ... - TEMP.MOT. Motor temperature okay. - QUIT. ZE3 Input I_ZE3 triggered. - V=KONST. Constant speed. - V < V_G1 Limit value V_G1 is not exceeded. Following this parameter, parameter V_G1 is faded in.
INVERS
V_G1 0.200m/s Speed level of O_SK1
> Output RB QUIT
MANUELL
> Error confirmation
- V<0.3m/s - 1.1*V_NEN
Actual speed is smaller than 0.3 m/s. Actual speed is smaller than 1.1*V_NEN.
.
Function of the special contact O SK 2 Contact K21-K24 is closed if...
Function of the output "Controller active RB"
-- QUIT. TEMP.MOT. ZE3 - V=KONST. - V < V_G2
-- STANDARD INVERS
MotorI_ZE3 temperature okay. Input triggered. Constant speed. Limit value V_G2 is not exceeded. Following this parameter, parameter V_G2 is faded in.
V_G2 0.200m/s Speed level of OSK2 - V<0.3m/s - 1.1*V_NEN
Actual speed is smaller than 0.3 m/s. Actual speed is smaller than 1.1*V_NEN.
FunctionK34-K31 of the special contact Contact is closed if ... O SK 3 - FB Forcedair cooling is to be switched on. - TEMP.MOT . Motor temperature okay. - QUIT. PA2 Second parameter set active. - V<0.3m/s Actual speed is smaller than 0.3 m/s. - 1.1*V_NEN Actual speed is smaller than 1.1*V_NEN.
Relay Relay is is picked pickedup upduring duringstop. running.
Selection of the trouble acknowledgement Relay ST - MANUAL The relay trouble "ST" only switches on again when the controller release "RF" is triggered again. - AUTOMAT. In case of excess temperature of the motor or outage of a mains phase, the relay "ST" is automatically switched on again if the trouble is eliminated. Other troubles have to be
acknowledged by means the controller release "RF"ofas with "MANUAL".
Operation and settings
37
4.3.11 The menu "ZA-INTERN" Contents: In menu "ZA-Intern", controller internal settings are stored. Changes are only to be made on consultation with the manufacturer. ZA-INTERN ********************** Error suppression:
Control functions:
Start-Opti.:
Stop-Opti.:
----------------------------
----------------------------
----------------------------
----------------------------
MASK1
T_GUE
ANF_D
HALT
0
>
2.0s
> MASK2
0
>
>
V_UE
50 %
> MASK3
0
>
EIN
V_DM
1.0%
T_AUS
7.0s
VB_T1
100 ms
Info:
---------------------------MS_1
0
>
S0<=
----------------------------
50 ms
MS_2
0
RS232
4800
50%
T_NB >
SE_NR
ZA
110ms
K_N2
1400
T_N2
110ms
> 5.0cm
> 2
T_N1
> 250ms
BR_F
70%
BR_OF
18%
>
> .....
> Service number
>
S_HALT
1400
>
STATUS >
>
>
0.5 m/s2
>
> ZETAMON:
R_N1
K_N1 >
>
> M0_T1
A10
----------------------------
t-Halt
>
>
>
Controller:
P_T1
300 &
> ......
> ZA manafacture
Figure 4.17 Menu "ZA-Intern"
MASK1 MASK3
It is possible to attenuate three error messages. To do this. the corresponding error number is to be put in.
T_GUE
If no speed transmitter signal appears within the time T_GUE, the control device switches to error and displays the error message "9 No starting" or "14 Encoder trop out". If the actual speed exceeds the value of the rated speed to the nominal speed by more than 50 % or if it falls below more than 50 %, the control device switches to trouble and displays the error message "36 N_PROG << N_REAL" resp. "35 N_PROG >> N_REAL". The control device stops the run in case of running without driving command but with triggered controller release "RF" after the time T_AUS. When the starting attenuation is switched on, the nominal value is kept in a tolerance range V_DM until the actual value follows. A smaller value for V_DM causes a smoother start-up. Determines the return-to-zero period in which the pre-braking torque M_VB returns to zero. Determines the return-to-zero period in which the starting torque M0 returns to zero. Determines the number of speed transmitter pulses attenuated by the rotation direction evaluation at start-up. Setting whether the positioning process (V1->0) is to be effected depending on the time or the distance. If HALT = t-Halt: Decelerating value for positioning process. If HALT = t-Halt: Rounding of V1 ->0 transfer. If HALT = s-Halt: Absolute positioning distance. Determines the time how long the after-braking torque is to be fed after closing the contact "MB".
V_UE
T_AUS ANF_D V_DM VB_T1 MO_T1 S0<= HALT A_10 R_10 S_HALT T_NB K_N1/2 T_N1/2 BR_F BR_OF P_T1 MS_1 MS_2 RS232 STATUS SE_NR ZA
38
For the run with V3, it is possible to adjust the reset time and the amplification of the speed regulator separately. Influencing the effect of the DC-winding. Crossover range between "Drive" and "Brake". Internal value for low-pass filter. Setting of the measuring value storage 1. Setting of the measuring value storage 2. Setting of the baud rate (2400, 4800 and 9600 Baud). Internal state of the control device at the moment. Indication of the current password coded. In case of password loss, please inform the manufacturer of the contents of SE_NR. Ziehl -Abegg specific identification of the control device software.
Operation and settings
5.
Commissioning
5.1
Requirements
When commissioning the device locally, no measuring instruments are required. Before starting the commissioning, the following points have to be checked: 1. The control device is installed and connected according to this description. 2. The operation of the device and the adjustment possibilities are well-known. 3. The control of the device is executed and checked according to this description.
The drive may be put into operation only if these three conditions are fulfilled.
Commissioning can be carried out in accordance with the brief instructions supplied with the equipment. The control parameters must be adjusted to suit the installation before the first run. Observe all instructions contained on these pages. If the controller is of special design, refer to the supplementary instructions before starting the commissioning procedure.
Before moving off, always ensure that no persons or objects are in the way.
Commissioning
39
5.2
Quick s etup for m ounting travels
The control device is preset by the factory. In case an encoder with a resolution of 1024 pulses/revolution is connected, it is possible to immediately carry out a controlled drive. Experience has shown that changes are effected by third parties when the control device is installed in the control cabinet and when tests are carried out outside the location. This is why the following procedure is recommended.
Load the factory setting:
The parameter /OPERATING/RESET enables to reset the control device to the initial delivery state. To do this, the value 99 has to be put in.
Input of the installation data: INSTALLATION
********************** ANL
ELEVATOR
First of all the installation specific data are put in into the menu "INSTALLATION" once. Input of the type of installation.
>Installation type N_NENN 1380 min-1 >Nominal rotation of V_NENN
1.20 m/s
>Nominal speed of the GEBER ET3R-1024 >Encoder type AUTO
AUS
>Automatic parameter
Input of the nominal rotation speed according to the indication on the motor identification plate. Input of the nominal speed of the cabin at the nominal motor rotation N_NENN. Input of the type of encoder. Set parameter to ON. The remaining parameters are preassigned once according to the values in /ANL,/N_NENN and /V_NENN.
Figure 5.1
After the pre-assignment by means of the parameter AUTO, the speeds in menu "TRAVELLING" are adjusted as shown in the table. Parameter V_1 V_2 V_3 V_N V_ZE1 V_ZE2 V_ZE3
Designation Positioningspeed Intermediatespeed Travelspeed Repositioningspeed Servicespeed1 Servicespeed2 Servicespeed3
Pre-assignment 5cm/s 2/3V_NENN 95%V_NENN 3cm/s 25%V_NENN 50%V_NENN 75%V_NENN
If necessary, adjustment to menu "INTERFACES"
If unlike the factory setting, the additional inputs and special outputs are required with other functions, the corresponding chances have to be made in menu "Interfaces".
First test run: -> To check whether the drive works controlled in both directions.
40
Commissioning
5.3
Setting of the "Switch off contacts" in the shaft
Disconnecting tags for the high running speed "V3"
There are two possibilities to determine the length of the required brake path. s [m]
0.5 m/s2 0.7 m/s2
5
0.9 m/s2 4 3
b) The length of the brake path can also be read directly at the control device. To do this, all parameters influencing the decelerating distance dispose of a special function (see figure 5.3). If one of these parameters is selected and changed, then the calculated decelerating distance from V_3 to V_1 is indicated instead of the comment line when returning.
2 V_3
1
1.20 m
V_3
> Travel speed P
P
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 V [m/s]
a) The length of the brake path can be taken from the diagram figure 5.2. But you have to observe that the indicated values are only valid in case the factory setting for the rounding R_NEG1 = 60 % and R_NEG2 = 90 % remain unchanged. Furthermore it is assumed that the control transmits the disconnecting tags to the control device without delay.
V_3
1.20 m
>
1.20 m
1.20 m [1.28][2.56]
Dist. S_31 (V_3 -> V_1) Dist. S_21: (V_2 -> V1)
change
Figure 5.3 Special functions of the parameters V_1, V_2, V_3, R_NEG1, R_NEG2 und A_NEG
Figure 5.2 Diagram of the length of the brake
Recommendation: The disconnecting tag should - if possible - be set to a larger length of the brake path than that determined in order to have free space for the optimization of the performance. Later on, it is possible to abstain from a possible subsequent shortening of the disconnecting tag in the shaft, as with the parameter /DECELERATE/S_DI3 it is possible to shift the disconnecting tag of the control device internally up to the distance S_DI3. In order to achieve a positioning run as short and equal as possible with "V1", the disconneting tags have to be set with an accuracy of +/- 1 cm.
Disconnecting tags for the positioning speed "V1"
The disconnecting tag for "V1" is to be set with an accuracy of +/- 1mm 5 cm before flush.
Disconnecting tags for the average running speed "V2"
If necessary: the disconnecting tags of for the driving command "V2" are set as far as possible from the flush. At first, you only have to check whether the required length of brake path s_21 (figure 5.3) is smaller or equal to the brake path available. If not, the speed "V2" is to be lowered in order to avoid an overrun at commissioning. In case of installations with readjustment, this has to be disconnected from the control at first in order to be able to work without being disturbed. Commissioning
41
5.4 Adjustment Checking the controller reaction
- Control run on several floors - Observe the indications actual speed, nominal speed and the controller output CO in menu "Monitor". N_REAL
300min-1
N_PROG
300min-1
•
•
In direction "Empty Up" with constant run: CO works in the negative range
•
In direction "Em pty Down" with constant run: CO works in the positive range The pointer CO is not to reach the limits of the range. If it exceeds theses limits, this is indicated by means of an additional "+" resp "-" character in the second line.
•
With constant run, the pointer should only slightly move
•
-............CO.............+
Real and programmed speed have to be the same
| Brake Drive Empty Up Empty Down
Checking the distances
In menu "Distances & Times", it is possible to check the accuracy of the disconneting tags set. S_31
1.00m
Decelerating distance required from V_3 to V_1.
Dist. V3->V1 S_30
1.05m
Measured decelerating distance from V_3 to stop.
0.05m
Measured positioning distance with speed "V_1".
Dist. V3->0 S_1 Dist. at V1
General adjustment references
V TRAVELLING
ACCELERATING
DECELERATING
**************
**************
**************
V_3
R_POS2
R_NEG1
A_NEG
A_POS
R_NEG2
V_1
R_POS1
S_1 S_DI3
RF V1 V3 RV1 RV2 RB MB Figure 5.4: Possibilities to change the curve.
42
Commissioning
t
Unlike the AUTO pre-assignment, the running curve can be changed by means of the parameters shown in figure 5.4. Reference if the decelerating distance has to be reduced: - Increase A_NEG or decrease R_NEG1 up to 40 %. - With elevators, leave R_NEG2 generally at 90 %. ? Arch travel in case of several different floor distances. Set R_POS2 to 90 % so that Recommendation: the control device generates an optimally rounded running curve even in the most unfavourable case.
? Balance weight If it is not possible to remove unnecessary balance weights when old installations are retrofitted, it can become necessary to set the
roundings R_POS2 and R_NEG as large as possible. ? Parameter /Controller/DYN The elevator has to work in the setting range of 70 to 100 %. In case of smaller values, the control is increasingly attenuated, i.e. that the reaction of the control is weaker and there can be noticeable standard tolerances at the speed transfers. If - in case of a setting of DYN = 70 % - the controller exit quickly travels with a constant high running speed in the larger range, have to check whether the motor speed is you correctly recorded by the control device. This is of particular importance if you do not use a high wave tacho. The mounting of the incremental speed transmitter has to be effected without clearance and vibration. Possible mechanical defects (e.g. squeezing of a guide shoe) can influence the control in the same way.
Optimization of the positioning distance S_1 - Select parameter /Distances & Times/S_1. - Check whether the rat runs are almost equal on all floors. - With the parameter /DECELERATING/S_DI3 it is possible to shift the disconnecting tag until the rat run is about 5 cm.
Flush setting If the elevator cabin comes to a halt on all floors with the same distance to flush, it is possible to shift the disconnecting tag by means of the parameter /DECELERATING/S_D1. If the distance is not the same, the correction has to be made directly in the shaft.
Setting of the average speed V2 In case of installations where the average speed is used, V2 is increased as far as the rat run is equal to that achieved when the high speed V3 is decelerated. There is also the possibility to disconnect the disconnecting tag for V2 by using the distance /DECELERATING/S_DI2.
Optimization of the start-up reaction A final optimization assumes that the state of the rail guidance, the gear oil level, the cabin suspension etc. are in order. The start-up reaction is determined by the parameters T_VB, M_VB and M0 in menu "ACCELERATING". The procedure depends on the existing type of installation (/INSTALLATION/ANL).
Commissioning
43
Elevator •
Elevator with a good installation efficiency, i.e. when the cabin is empty and the brake is manually opened, the cabin automatically moves up. T_VB = 100 ms M_VB = 0% M_0 = 0% Test runs EMPTY UP: Increase M_VB setting until the cabin starts moving smoothly. Test run EMPTY DOWN: Increase M_0 setting until motor only slightly turns back when started. If the brake is not already open, T_VB should be increased (in steps of 50 ms).
•
Lifting gear First of all check whether the drive moves upward if RV1 is triggered. If not, exchange the connection of RV1 and RV2 and change the direction of the motor /INSTALLATION/MO_DR. Running trials UP: - Increase MO setting until the motor shaft n o longer turns back. Running trials DOWN: - Increase M_VB setting until the lifting gear drives down without sagging.
Running gear
Elevator with a small installation efficiency, i.e. when the cabin is empty and the brake is manually opened, the cabin only moves when driving the handwheel.
In case of running gears, the start-up process is absolutely different from those of the other two installation types. When opening the brake, it is the driver winding that is set under current. The torque which is linearly driven increases until the initial breakaway torque is surmounted. When the motor starts moving, the installation switches to the regulated operation.
T_VB = 200 ms M_VB = 25% M_0 = 0%
T_VB = 100 ms M_VB = 30% M_0 = 0%
Test run EMPTY DOWN: In order to overcome an initial breakaway torque, increase M_0 setting until the drive starts without jerk.
M_0 is adjusted in a way that the drive runs without jerk.The bigger M0 is, the faster the change-over from the controlled to the regulated operation.
5.5 Final of setting up When the commissioning is finished, the current parameter setting has to be noted in the setting card (Appendix A10 or in the short description). The error list can be erased by means of the parameter /STATISTIC/STAT4. When third persons (caretaker) have access too, the input should be protected by means of a password (/OPERATING/PW_N see 4.3.8).
44
Commissioning
6.
Service
6.1
Maintenance
Within the usual maintenance works, the following checks are to be carried out: a)
General visual check concerning possible dust deposits.
b)
The correct fastening of the connections of the control device has to be checked.
c)
Possibly check /STATISTIC/STAT0 in the error storage if troubles have occurred since the last maintenance has been carried out.
6.2
Troubleshooting
Because of the digital construciton of the control device, numerous possible causes of trouble are already displayed as clear text. In general, it is possible to find the cause by means of these messages and by using the explanation given in appendix A4 as well as in the error search plan A5. The following procedure is recommended: a) If a trouble occurs (display blinks, error text and number are displayed), you have to look up the general error explanation in A4.
b) If no trouble is directly displayed by the control device, you have to check in the error storage /STATISTIC/STAT0 whether an error has occurred since the last maintenance has been carried out. The entry first displayed is the error that occurred last.
In order to save costs and money for queries, the questions in appendix A9 have to be answered before phoning the ZIEHL-ABEGG HOTLINE
6.3
Repair
When removing the front plate of the control device, the warranty period granted by the manufacturer lapses. The removal of the front plate is only possible after having asked the manufacturer. If an error in the control device can be proved, it is not recommendable to repair the device locally because of economic reasons.
recommended to have a control device of the biggest construction on stock. After comm issioning, all possible parameter lists of the devices to be possibly replaced are to be added to the control device.In case of production spots of particular importance ("Bottleneck"), it is recommendable to preset the parameters of the replacement device to this function. In the documents TIA94-21, the error search as
We recommend elevator services to have a replacement device with the biggest controller size ready. In case of trouble, you have to carry this device with you. But if you are not sure whether the control device is really the cause for the trouble, this can be found out when quickly replacing the control device (4 fastening screws, 9 locking screws and 6 edgeboard connections). Manufacturing companies or high-lift stocks (with several production streets) are
well as the repair of individual components is explained as a help. These documents also include a list of the replacement parts that are possibly needed.
Service
45
APPENDIX A1 A2 A3 A4 A5 A6 A7 A8 A9 A10
Technical data Denotation of controller types Dimension sheet Errorlist Error t racing p lan Accessories Changes and new functions Schematic d iagram HOTLINE-NOTIC Setting data ca rd
A1
Technical data
Denotation of controller 16 Nominalmainsvoltage Mainsfrequency Nomiminal current Maximumoperationcurrentfor5sec. operationalambianttemperature storingandtransportationtemperature location Protective system
ZETADYN 1DV0xx 25 40 60
80
90
V 3~ 230/400/500 (absolute+15/-10%) Hz 50/60 (automaticchange-over) A 16 25 40 60 80 90 4*Ratedcurrent °C 0bis45 °C -20bis60 NN < 1000 m at rated current IP00, VBG4 is met aggressive media, dust, fog, water or moisture are not
DIN 40050,IEC 144
allowed to penetrate into the device The controller corresponds the safety class 1, DIN VDE 0558, Teil 1, Pkt. 5.4.3.1.1
Relative humidity of air Weight Dimensions H W L Mains fuses terminalcrosssection Others: Mains "L1 L2 L3" Control inputs Relay outputs Speed transmitter
% kg mm
mm
The mains trafos are only partly short-circuit proof according to VDE 0551. Current consumption: typ. 15 mA/input. Voltage between "U0" and "GND": unstable 20 to 24 V DC Contact current-carrying capacity: 230 V AC/2A at cos phl > 0.4 A encoder with two square wave signals where the phase is shifted by 90° is required. As standard, a resolution of 1024 pulses/revolution is recommended. It is possible to connect encoders with a resolution ranging from 64 to 1024 pulses. "ET1" "ET2" "ET3" "ET4" "ET5"
Motor posistor connection "P1-P2"
2
90,notbedewed 9.5 9.5 11.5 12.5 13 290 306 350 350 230 230 "gL" according to the nominal motor current 10 10 16 16 35 35 9.5
+15V track A track B GND -15V
Total current consumption of the encoder: max. 250 mA Current consumption per track: typ. +7 mA /-1 mA Temperature monitoring of the motor according to DIN 44 081. -Electrolytically separated by means of an opto-coupler. -In case of a resistor of higher than 2.5 kOhm at "P1 P2", a trouble
fan terminal "11-12"
occurs. This thermal contact switches the control device off when a heat sink temperature of 80 ° C is achieved Independent from the nominal voltage, the connection voltage is 230V 50/60Hz. A thermal contact switches the fan on at a heat sink temperature of max. 55° C and switches it off at a temperature of min. 35° C
EMC & rfi suppression
The control devices are indifferent to trouble and tested according to IEC 801-4.
Thermal contact on the upper part of the power stage Only controller 1DV080 and 1DV090
As standard, commutation throttles are incorporated in the control devices. By using the radio interference filter (FEFUS) the radio interference level B is attained (EN 55011)
2
Denotation of controller types
ZETADYN 1DV080N4 Nominal mains voltage 3~ 2 : 230V 4 : 400V 5 : 500V N : Normal (Standard version) Nominal current 016 : 16A 025 : 25A 040 : 40A 060 : 60A 080 : 80A 090 : 90A
ZETADYN
1DV016N4
400V 3~ 50/60 Hz, 16A, IP 00 Teile-Nr.: 00156006 Fert.-Nr.: 39135001/0001 ZIEHL-ABEGG
Voltage-regulated
Figure A2.1 Type key
A3
Figure A2.2 Controller data plate
Dimension sheet
Installation clearances:
At least 30mm at the sides At least 60mm at the top and bottom
A4
Errorlist
If troubles occur the controller cuts the current travel program. The display starts flashing and a short message will be displayed with number including a hint to possible causes. ->Press any key to delete the error message. All messages are stored in the error list /STATISTICS/STAT0. Individual monitoring functions can be blocked in menu /ZA_INTERN by means of the parameters MASK 1 to 3. To do this, the corresponding error number has to be put in.
No.
Error
Reason
Prüfe L1, L2, L3
Outage of a mains phase.
0
Memory empty
No error: Is put in in the error list if no error has occurred up to now.
2
A_NEG
Range limit /DECELERATING/A_NEG has to be smaller than /INSTALLATION/A_MAX.
3
Phase failure
Outage of a mains phase at start-up trial or at stop.
4
Phase failure
Outage of a mains phase during running.
Reference to 3 & 4:
If parameter /INTERFACES/QUIT is set to AUTOMAT., the drive automatically starts running again after all mains phases have been fed.
5
Temp.Motor
Monitoring of the motor temperature (Terminal P1 P2) has responded at standstill.
6
Temp.Motor
Monitoring of the motor temperature has responded during running.
Reference to 5 & 6
If parameter /INTERFACES/QUIT is set to AUTOMAT. the drive automatically starts running again after cooling of the motor.
7
V1< V2< V3
V1 has to be smaller than V2 and V2 has to be smaller than V3.
8
Wrong direction
The car has moved a distance in the wrong direction.
9
No starting
The controller does not receive any signal from the encoder within the monitoring time /ZA-INTERN/T_GUE.
10
No stopping
Although the control device has closed the mechanical brake via contact "MB", the drive does not come to a halt.
11
RV1 or RV2
Both directions set have been triggered.
12
RV1 /RV2 missing
A speed has been triggered without any direction set.
14
Encod. drop out
The signal of the encoder has broken down at start-up or during running.
15 16 17 18 19
R_NEG too small A_NEG too small R_POS too small A_POS too small V1 too small
The lower limit of the range is achieved. Increase the corresponding parameter.
20
EEPROM error
Parameter storage defective. Contact ZIEHL-ABEGG
21
EEPROM cleared
The entire parameter storage has been erased and overwritten with the factory setting. The message must only appear when the controller software has been replaced with different release numbers.
22 23 24 25
R_NEG too large A_NEG too large R_POS too large A_POS too large
The upper limit of the range is achieved. Decrease the corresponding parameter.
26
V3<1.5V_NEN
TRAVELING/V3 may not exceed 1.5 times /INSTALLATION/V_NENN.
27
!Switch off!
The controller has to be switched off for a short time. Sequential message from no. 21 or rotary-field direction could not be determined as not all phases have been connected at the same time (e.g. rotary switch slowly actuated).
28
Short travel off ?
Triggering log for short travel not met. Input "V1" has been switched off prior to input "V_ZE3".
29
Power stage...
Connection of the motor of the power stage is still not closed at start-up trial.
30
V_Z < V_3
TRAVELING/V_Z has to be smaller than /TRAVELING/V_3.
31
V_Z too small
Range limit achieved.
32
Stop input !
Driving command has been connected although one parameter has still been changed.
33
Temp. controller
Temperatur monitoring of the power stage has responded.
34
Drive with brake
The drive moves after is has come to a halt (the mechanical brake is closed via output "MB"). - Occurs when brake is manually opened - if not, check whether contact "MB" directly closes the brake without delay (without influence of the control).
35
N_PROG >> N_REAL
36
N_PROG << N_REAL
37
MTR still turns
Motor still turns although the mechanical brake should have come in before long (controlled by means of contact "MB").
38
False rot. field
The current supply is not connected to the right phases.Two phases on the controller board as well as on the power unit have to be changed. Please observe that both boards have the same phases connected.
39
Para-Change?
The parameter set has been reversed during running.
40
Motor-Change?
During running, the second motor has been changed to.
Drive cannot follow the programed speed. Real speed is much higher than the programed speed.
A5
Error tracing plan
During commissioning, error messages can be caused by basic connection of triggering errors. Therefore, please check the following four points. Condition for a controlled operation:
Are the board of the controller board as well as the power stage connected to the same phases? Is the correct encoder type adjusted in menu /INSTALLATION/GEBER ?
Conditions so that the control device is able to control start-up and stopping without jerk:
Is the spring-loaded safety brake switched on and off without delay by means of the relay "MB"? Is the main contactor "K0" switched on and off without delay by means of therelay "RB"? If the control does not evaluate the contact "RB": Is the main contactor switched on at the latest when the driving command is fed? Is the main contactor switched off time-delayed only when the brake comes in?
The error search plan is divided into the following sections: A5.1
Error message at standstill
A5.2 A5.3 A5.4 A5.5
Drive is not running. Brake does not open and main contactor does not switch on Drive is not running. Brake opens and main contactor switches on. or accelerates and switches off. Drive switches off at deceleration. Drive switches to trouble when stopping.
A5.6
Checking the encoder.
A5.1
Error message at standstill
3 Phase failure 5 Temp. Motor
Outage of a mains phase Monitoring of the motor temperature responds... a) If monitoring is not needed. -Set a bridge between terminal "P1" and "P2". b) If motor is hot: - Does the forced air cooling of the motor switch on? - Does the forced air cooling work in the correct direction? - Is /TRAVELING/V_3 set at 95 % of INSTALLATION/V_NENN atleast? - Is rat run min. 15 cm? - Is there an additional balance weight available? - Number of runs too high? - Installation efficiency unexpectedly high? In case of inspection run and long running distances at slow speed, normally the motor heats off above-average! c) If motor is cold: If display blinks, actuate any key several times. If the error message is masked out, the error message occurred a long time ago and the motor has already cooled down (see b). In all other cases if the error message is not masked out: - Check whether the function of the control device is okay: Switch device off. Set a bridge between terminal "P1" and "P2". The error message must not occur once again.
38 False rot. field 27 !Switch off!
Neue Version Ja = Taste [P] 20 EEPROM-error 34 Travel with brake
33 Temp.Controller
- Checking the posistor: If the motor is cold, the resistor has to be smaller than 2.5 kOhm. Attention when using electrical continuity testers! The maximum admissible testing voltage of the posistors is 2.5 V. The current supply is not connected to the right phases.Two phases on the controller board as well as on the power unit have to be changed. Please observe that both boards have the same phases connected Switch the controller off for a short time a) After having changed the software, the control device has to be switched off for a short time for acknowledgement. b) It was not possible to determine the rotary-field when switching the device on as not all three phases have been connected at the same time. c) After loading the factory setting by means of the parameter /OPERATING /RESET, the control device has to be switched off for a short time for acknowledgement. This reference appears after the software has been changed. Press [P]. Wait 1 minute. Switch the controller off for a short time. Parameter storage defective. Contact ZIEHL-ABEGG a) Mechanical brake has been manually opened. b) Error in the control device: Drive starts moving although the contact "MB" is open. The heat sink temperature has increased and exceeded 80° C. a) If heating up can be determined: In case of control devices starting with1 DV80, the fans have to be switched on. (They switch on at 55° C and off at 35° C only). b) If no heating up can be determined: Check the flat cable between the controller board and the power stage
A5.2
Drive does not start running
- Spring-loaded safety brake does not open. - Main contactor does not switch on. Error No. 2,7,15-19,22-25 Range limit for parameters is achieved: 30 and 31 - Change the parameter value according to the reference. 32 Driving command has been fed although one parameter has still been changed. Stop input ! Press any key to end parameterization. 11 Error in the PLC: Both direction sets are fed at the same time. RV1 or RV2 12 Error in the PLC or line break: RV1/RV2 is missing - A driving command is fed without direction set. 29 In case of a start-up trial, no voltage is fed at the motor: Power stage - There should be no contactor between motor and power stage. - The main contactor is to be switched on by means of contact "RB" or if a driving command is fed at the latest.
A5.3
The drive switches off when accelerating or does not start running
- Brake opens - Main contactor closes a) Drive turns up quickly to maximum speed and switches off after 2 seconds. 8 -> Exchange encoder connection ET2 and ET3. Wrong direction b) Counter balance pulls cabin to the wrong direction. - Check in general whether drive, brake and main contacter are okay. 9 The controller does not receive a encoder signal within the monitoring No starting time /ZA-INTERN/T_GUE.
14 Encod. dop out 35 N_PROG >> N_REAL
A5.4
Drive swi tches off wh en de celerating
14 Encod. drop out 36 N_PROG << N_REAL
A5.5
a) Motor turns up quickly to maximum speed and switches off -> Check the connection of the encoder (see A5.6). b) Motor does not move, motor noise can be heard ->Motor blocks? Speed transmitter signal (ET2/ET3) has broken down. - See A5.6 "Checking the encoder". Drive is not able to follow programed value. - check whether the correct encoder type has been set in /INSTALLATION/GEBER (bar number probably to high).
Speed encoder signal (ET2/ET3) has broken down. - See A5.6 "Checking the encoder". Drive does not decelerate: - Brake winding is probably not connected correctly. - /DECELERATING/A_MAX to high.
Drive switches to trouble when stopping
37 MTR still rotate
Motor still turns although the mechanical brake should have come in before long. Contact "MB" does not directly connect the mechanical brake.
A5.6 • •
• •
Checking the encoder
Is the encoder connected in the way shown in the connection proposal A8? Should external encoders be connected, you have to check whether the technical data are met. Is the monitor connected in the right way?
Observe the real speed at the control device: /MONITOR/N_REAL Open the brake manually and observe the real speed.
If the control device does not register any speed: - Check the voltage of the transmitter supply: ET1 +15V
ET2 trackA
ET3 trackB
ET4 GND
ET5 -15V
In case of slow motor rotation (open brake manually for a short time), the voltage levels at terminal "ET2" resp. "ET3" have to change between + and -. - Current consumption in "ET2" and "ET3" typ. +7 mA /-1mA.
It is further possible to check the following two points by means of an oscilloscope or another multimeter of high-quality: - The pulse/pause ratio has to be 50 %. - The phases of track A and B are shifted by 90°.
A6
Accessories
Radio interference filter Radio interference filter for controller ZETADYN 1DVxxxN2 and 1DVxxxN4 (230V-mains, 400V-mains) Radio interference filter for controller 1DVxxN5 (500V-mains) upon request.
Type Converter
Radio interference filter
Article-No.
ZETADYN1DV016N4 ZETADYN1DV025N4
FEF025 FEF045
357101 357102
ZETADYN ZETADYN1DV040N4 1DV060N4 ZETADYN1DV080N4 ZETADYN1DV090N4
FEF090 FEFUS 063N FEFUS080N FEFUS100N
357103 357023 357024 357025
G F
C
E
D
B
A Dimensions of radio interference filter type FEFUS/FEF
Type of filter
ABC 250 120 250 120 300 120
100 100 115
fixing dimens. D E 230 100 230 100 280 100
FEFUS063 FEFUS080
330 330
153 153
130 130
315 315
FEFUS100
330
153
133
315
FEF025 FEF045 FEF090
length
width
height
top-edge terminal
bore-hole
terminal connect. mm2 16 16 25
Weight
F 215 215 255
G 275 275 327
7,0 7,0 7,0
105 105
300 300
396 396
7 7
95 95
9,7 9,2
105
300
396
7
95
10,0
∅
kg 3,5 3,6 5,3
Encoder ET 3R-1024 The ZIEHL-ABEGG encoder ET 3R-1024 is designed with a quill shaft for direct mounting on the controlled motor . The second motor shaft is still available. The encoder features contactless operation free of wear. The encoder connected to the controller ZETADYN 1DV produces two rectangular signals with 1024 pulses per revolution each at 24 Vss (centre zero). They are in phase quadrature. The encoder part produces a rectangular signal with 64 pulses per revolution electrically separated at 12 Vss. The signal is provided for monitoring devices (for example GU1). Description see data sheet ET 3R-1024, Connection see figure A8.
Encoder ET2R-1024 Hollow shaft encoder like the ET3R-1024, however with a closed case. An additional signal track for monitoring functions is not available. All encoders will be delivered with a 10m connecting cable. Encoder 58H-1024 We offer a retrofitting kit where an external encoder is driven by a V-belt (see 1.3 Requirements).
Encoder G71-xx30 This encoder is of the same construction as an analog tacho with Euro-flange (see 1.3 Requirements).
A7
Changes and new functions
Control devices starting with themanufacturing number 3942xxxwith the software release 3.0 have the following differences compared with previous devices.
Changes:
•
When connecting the control device, itis no longer necessary to remove the front plate.
•
The current supply of the control unit board is also executed plugged-in.
•
The installation as well as the exchange of the control device has been simplified by means of constructional measures.
•
The freely programmable special outputs and the additional inputs have been preset as follows by the factory: "SK1"-Special contact 1 Contact K11-K12 is closed when the speed is higher than 0.3 m/s. "SK2"-Special contact 2 Contact K21-K22 is closed if the nominal speed is exceeded by 10 %. "SK3"-Special contact 3 Contact K34-K33 is open if the motor temperature monitoring is triggered. The running speeds"V_ZE1 - V_ZE3" are allocated to the additional inputs"ZE1 - ZE3".
•
The contact "RB- Controller active" is preset from the factory in a way that the relay connects the main contactors (Factory setting INVERS instead of STANDARD used up to now).
•
The terminal designation of the special outputs has been changed in order to be better understandable.
•
The control inputs can be directly connected to an external voltage of 24 V without being modified (see 2.3.3)
Expansions:
•
The input "VZ" is used for post-adjustment (except with installation type "Running gear").
•
Besides the additional input "ZE", two further additional speeds are available (see above).
•
It is possible to connect an encoder with a pulse resolution of 64 - 1024 per revolution andtrack.
•
The input of the encoder evaluation wiring has been completed by a constant current source. (Preresistors probably needed up to now are no longer necessary).
A9
HOTLINE-NOTIC
Please check.:
Tel.: +49 (0) 79 40-16-308 Fax: +49 (0) 79 40-16-2 00
Location: ................. .................. .................. .................. ... Controller-Type:
ZETADYN 1DV ................... .............. Fert.-Nr.: ............... ................. ......... ( see Controller data plate)
State of the installation
O New building O Renovation/Rebuilding O Installation already working without troubles since.......................... O Commissioning - Assembly operation O Commissioning - Automatic operation
Installation type
O O O O
Passenger elevator Freight elevator Lifting gear Running gear
O Gear transmission ......................... O Lifting height about ............ m O Elevator cage in the basement
Error no.
................. .................. .................. .................. .
Error
................. .................. .................. .................. .
Error/Problem occurs
O O O O O O
when switching the supply voltage on at start-up when accelerating in case of constant run when decelerating at stopping
Error/Problem occurs
O at both directions O only at Empty DOWN O only at Empty UP O Error is reproducible O Error is only sporadic
.................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. .................. Encoder
O ET 3F-64
O ET 3R-1024
O others............................
Motorno. .................. .................. .................. .................. .................. .... Manufactor of the PLC:................. .................. .................. .................. ........ Name: ................. ................. .................. .................. ......... Telefon: ............................................
Telefax:...........................................
TRAVELLING:
CONTROLLER:
V
V_3 R_NEG1
R_POS2
A_NEG
A_POS
R_NEG2 V_1
R_POS1
t
inputs
V_1 V_2 V_3 V_Z V_ZE1 V_ZE2 V_ZE3
m/s m/s m/s m/s m/s m/s m/s
DYN
[100]
%
OPERATING: PASSWORD
INSTALLATION:
RF V1 V3 RV1
ACCELERATING:
RV2 outputs
RB MB
Menu-structure:
Examples: V_3 [m/s]
MONITOR
S: V_3 -> Stop [m]
*********************** DIST. & TIMES *********************** STATISTIC *********************** TRAVELLING *********************** ACCELERATING ***********************
0.80 1.00 1.20 1.50 1.60 1.80 2.00
1.20 1.45 1.70 2.50 2.70 3.50 4.20
DECELERATING ***********************
R_NEG1 = 60%
CONTROLLER
R_NEG2 = 90 %
*********************** OPERATING *********************** INSTALLATION *********************** INTERFACES
m/s2 % % ms % %
A_POS R_POS1 R_POS2 T_VB M_VB M_0
Elevator
GEBER
ET3R-1024
MO_DR S_ABH A_MAX
LEFT OFF m/s2
run. gear
min m/s
RIGHT ON
INTERFACES:
DECELERATING: A_NEG R_NEG1 R_NEG2 V_BR M_NB
ANL N_NENN V_NENN
[60] [90] [0.001] [35]
m/s2 % % m/s %
[0]
mm
I_ZE3 O_SK1 O_SK2
Manuf. V_ZE3 else: Manuf: V < 0.3 m/s else: Manuf. 1.1 x V_NENN
*********************** EXPANSION *********************** ZA-INTERN ***********************
Location:
S_DI1 S_DI 2 S_DI 3
[0] [0]
m m
O_SK3
O_RB QUIT
elset: Manuf. TEMP.MOT else: STANDARD MANUELL
INVERS AUTOMAT
ZA INTERN: MASK1 MASK2 MASK3
0 0 0
Control functions:
T_GUE V_UE T_AUS_
1.0s 50% 7.0s
Start-Opti.:
ANF_D V_DM
ON 1.00%
Stop-Opti.:
A_10 R_N1 HALT S_HALT T_NB
0.50 m/s2 50 % t-HALT 5.0cm 250ms
Controller:
K_N1 K_N1 K_N2 K_N2 BR_F BR_OF P_T1
1400 110ms 1400 110ms 70 % 18% 300&
ZETAMON:
MS_1 MS_2 RS232
0 0 4800
Info:
STATUS SE_NR ZA
Error suppression:
Notice:
Technical assistance for commissioning:
Telephone
+49 (0) 79 40 / 16-3 08
T el ef ax
+49 (0) 79 40 / 16-2 49
Ziehl-Abegg AG Heinz-Ziehl-Straße D-74653 Künzelsau Postfach 11 65 D-74641 Künzelsau Telephone +49 (0) 79 40 / 16-3 74 (Sales department) Telefax +49 (0) 79 40 / 16-2 49
ASK8.T-GB0197-ZA/R Art.-Nr. 00156714-GB