May 2006 rev. 3
Page 1 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
Contents CHAPTER 4 OPERATORS 1 HISTORICAL HISTORICAL OVERVIEW OVERVIEW OPERATORS................... OPERATORS............................... ....................... ....................... ....................... ................... ........ 3 2 Old operators operators ....................... ................................... ........................ ....................... ....................... ........................ ....................... ....................... ..................... ........... .. 4 2.1 Overview Overview of delivered delivered Cardo Cardo operators operators........... ...................... ....................... ....................... ...................... ....................... ..................... ......... 4 2.1.1 Ovitor Ovitor operators operators (Delivered (Delivered from: Start – 1974) ..................... ................................ ...................... ...................... ..................... .......... 4 2.1.2 Operator Operator CDM-1 (Delivered (Delivered from: 1974 – 1980) 1980) ...................... .................................. ........................ ....................... ................. ...... 4 2.1.3 Operator Operator CDM–2 (Delivered (Delivered from 1978 – 1980) 1980) ...................... .................................. ........................ ....................... ................. ...... 4 2.1.4 Operator CDM-5 (Control system in the mechanical unit, 1982 – 1994) ......................... ............ ............... .. 6 2.1.5 Operator CDM-5 (HD) (control system system in the mechanical mechanical unit, 1982 - 1994) .................... .............. ...... 7 2.2 Circuit Circuit Diagram Diagram CDM 5 K 2605 ....................... ................................... ....................... ....................... ....................... ....................... .................... ........ 8 2.2.1 CDM-5 Dead man’s grip............................ grip....................................... ....................... ....................... ....................... ....................... ....................... ............... ... 9 2.3 Control Control unit CDM-5............. CDM-5......................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ............. 10 2.4 Mechanical Unit CDM5 (Separate control control system, 1984 – present)............ present) ........................ .................... ........ 10 2.4.1 Mechanical Unit CDM 5 adjustment of sliding clutch and limit switches................ switches.. ...................... ........ 11 3 mECHANICAL mECHANICAL UNIT CDM-6................................ CDM-6........................................... ....................... ....................... ...................... ..................... .......... 14 3.1 Mechanical Unit CDM6 (HD)(Separate control system, system, 1984 – present) ........................ ............. ........... 14 3.2 Installatio Installation n of fixing fixing bars CDM 6 (HD) ....................... .................................. ....................... ....................... ....................... .................... ........ 15 3.2.1 CDM6 (HD) adjustment of limit switches and sliding sliding clutch....... clutch.................... .......................... ......................... ............ 16 4 Control Control system CDM-5/CDM-6 CDM-5/CDM-6 (metal boxes) boxes) ...................... ................................. ...................... ....................... .................... ........ 17 4.1 CDM 5/6 - Control unit CDM6-07 K2-12253............... K2-12253... ......................... ......................... ......................... .......................... ............... .. 18 4.2 CDM 6 -07 Connectio Connection n diagram diagram -113-K2-12 -113-K2-12247 247 ...................... ................................. ....................... ....................... ................ ..... 19 4.3 CDM6 Main diagram - 111 K2 - 5640............... 5640.. .......................... .......................... .......................... .......................... ........................ ........... 20 5 Automatic system ECS 600 .......................... ............. ......................... ......................... .......................... .......................... .......................... ............... .. 21 5.1 Additional system ECS 600 (Added (Added to control system CDM5/6 or to CDM5 with control system system in mech.unit, mech.unit, 1984-1988).............. 1984-1988).......................... ....................... ...................... ....................... ....................... ...................... ...................... ............. .. 21 5.1.1 Functiona Functionall descriptio description n ECS 600 ..................... ................................. ....................... ...................... ...................... ....................... .................... ........ 22 5.1.2 Interface Interface unit (Obsolete).............. (Obsolete).......................... ....................... ....................... ....................... ....................... ....................... ....................... ............... ... 22 5.1.3 Power unit (Obsolete (Obsolete)............. )........................ ....................... ....................... ...................... ....................... ....................... ....................... ..................... ......... 22 5.2 Automatic door operating system ECS ECS 600....................... 600.......... ......................... ......................... ......................... ..................... ......... 23 5.3 CDM5 - ECS 600 - wiring wiring diagram diagram ...................... .................................. ....................... ...................... ....................... ....................... .............. ... 24 5.4 CDM6 - ECS 600 - Wiring Wiring diagram ..................... ................................. ....................... ...................... ....................... ....................... .............. ... 25 5.5 Photocell Photocell ECS 600 ...................... ................................. ....................... ....................... ....................... ....................... ....................... ....................... ............... .... 26 6 Control Control system system ECS 601.............................. 601.......................................... ....................... ...................... ....................... ....................... ..................... .......... 27 6.1 Control system ECS 601 (for CDM5 and CDM6, 1988-1993) 1988-1993) .......................... ............. ........................... ................ 27 6.2 Functiona Functionall descriptio description n ECS 601/602 ...................... .................................. ....................... ...................... ....................... ...................... .......... 28 6.2.1 Contactor Contactor unit................................ unit........................................... ....................... ....................... ....................... ....................... ....................... ....................... ............. .. 28 6.2.2 Impulse Impulse unit............................... unit........................................... ....................... ...................... ....................... ....................... ....................... ....................... ................. ...... 28 6.2.3 Safety supervision unit (Pinch guard monitoring) .......................... ............. .......................... .......................... ..................... ........ 28 7 Thermospe Thermospeed ed (1988 - 1998) 1998) ...................... ................................. ....................... ....................... ....................... ....................... ....................... ............ 50 7.1 Thermospeed (1988 - 1998)...................... 1998)......... .......................... ......................... ......................... ......................... ......................... .................... ....... 50 7.2 Automatic ECS 601............ 601 ........................ ......................... ......................... ......................... .......................... ......................... ......................... .................. ..... 51 7.3 ECS 601 Thermospe Thermospeed ed 111-K3 111-K3 - 31207 31207 ...................... ................................. ....................... ....................... ....................... ................ .... 54 7.4 Photocell Photocell kits K 35724..................... 35724................................ ....................... ....................... ....................... ....................... ...................... ....................... ............ 55 8 Control Control system system ECS 602.............................. 602.......................................... ....................... ...................... ....................... ....................... ..................... .......... 56
May 2006 rev. 3
Page 2 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
8.1 Functiona Functionall descriptio description n ECS 601/602 601/602 ....................... ................................... ....................... ....................... ....................... ..................... .......... 57 8.1.1 Contactor Contactor unit:............................... unit:.......................................... ....................... ....................... ....................... ....................... ....................... ....................... ............. .. 57 8.1.2 Impulse Impulse unit:.............................. unit:.......................................... ....................... ...................... ....................... ....................... ....................... ....................... ................. ...... 57 8.1.3 Safety supervision unit: (Pinch guard monitoring) ......................... ............ .......................... .......................... ..................... ........ 57 8.2 Automatic ECS 602 System design............. design......................... ......................... .......................... .......................... .......................... ................. .... 58 8.3 Automatic ECS 602 Control components components ......................... ............. ......................... .......................... ......................... ..................... ......... 59 9 Control Control system system ECS 410/420/43 410/420/430 0 ...................... ................................. ....................... ....................... ...................... ...................... ................ ..... 60 10 Control Control Unit ECS 430S – CDM 6/5 ...................... ................................. ....................... ....................... ....................... ....................... ............. .. 61 10.1 ECS 430S 2H-CDM6 2H - 400V........................... 400V.............. .......................... ......................... ......................... .......................... ..................... ........ 62 10.2 B1 System System - ECS 430 S ....................... ................................... ....................... ....................... ....................... ....................... ....................... ................. ...... 63 11 Connectin Connecting g diagram ECS 430 P – CDM6/5 ...................... ................................. ....................... ....................... ....................... ............ 64 11.1 Automatic functions ECS 430 P ......................... ............. ......................... .......................... .......................... .......................... ...................... ......... 65 11.2 Control Control system system C-kit matrix descriptio description n ....................... .................................. ....................... ....................... ....................... .................. ...... 66 12 Diagram Diagram CDM 9 ....................... .................................. ...................... ....................... ....................... ....................... ....................... ....................... .................. ...... 67 12.1 Control Control system system D-kit matrix descriptio description n ....................... .................................. ....................... ....................... ....................... .................. ...... 69 13 RADIO EQUIPMENT EQUIPMENT ...................... ................................. ....................... ....................... ....................... ....................... ...................... ....................... ............ 70 13.1 Radio equipmen equipmentt 40 MHz.............................. MHz......................................... ....................... ....................... ...................... ....................... ..................... ......... 72 13.2 Radio equipmen equipmentt 433 MHz............................... MHz.......................................... ...................... ...................... ....................... ....................... .................. ....... 73 13.3 Radio equipment 433 MHz PLUS.......................... PLUS.............. ......................... ......................... ......................... ......................... .................... ........ 74 13.4 Programmin Programming g the transmitters transmitters........... ...................... ...................... ....................... ....................... ...................... ....................... ...................... .......... 78 13.5 Supplementing old 433 MHz installations 1.................. 1...... ......................... .......................... ......................... ......................... ............. 80 13.6 Supplementing old 433 MHz installations 2.................. 2...... ......................... .......................... ......................... ......................... ............. 81 13.7 Supplementing old 433 MHz installations 3.................. 3...... ......................... .......................... ......................... ......................... ............. 82 13.8 Coding Coding tables tables ....................... .................................. ....................... ........................ ....................... ....................... ........................ ........................ ..................... ......... 83 13.9 Radio equipmen equipmentt 869 MHz............................... MHz.......................................... ...................... ...................... ....................... ....................... .................. ....... 85 13.10 Transmitter Transmitterss in the 869MHz 869MHz program program ..................... ................................. ....................... ...................... ...................... ....................... ............ 86 13.11 Receivers Receivers in the 869MHz program program........... ...................... ....................... ....................... ...................... ....................... ....................... ............. .. 87 14 Magnetic Magnetic loop system system ....................... .................................. ...................... ....................... ....................... ....................... ....................... ..................... .......... 90 14.1 Magnetic loop – connection diagram.............. diagram. .......................... .......................... .......................... ......................... ......................... ............... 91 15 Reduced Reduced opening opening – ECS 430 P – CDM 5 ....................... .................................. ....................... ....................... ....................... .............. .. 92 16 Reduced Reduced opening ECS 430P – CDM6 ...................... ................................. ....................... ....................... ....................... .................... ........ 93 17 Reduced opening – ECS 930A / 940A* – CDM 9........................ 9............ ......................... ......................... ....................... ........... 94 18 Dipswitch Dipswitch settings settings – ECS 930A/ 940A – CDM 9 ....................... .................................. ....................... ....................... ............... .... 95
May 2006 rev. 3
Page 2 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
8.1 Functiona Functionall descriptio description n ECS 601/602 601/602 ....................... ................................... ....................... ....................... ....................... ..................... .......... 57 8.1.1 Contactor Contactor unit:............................... unit:.......................................... ....................... ....................... ....................... ....................... ....................... ....................... ............. .. 57 8.1.2 Impulse Impulse unit:.............................. unit:.......................................... ....................... ...................... ....................... ....................... ....................... ....................... ................. ...... 57 8.1.3 Safety supervision unit: (Pinch guard monitoring) ......................... ............ .......................... .......................... ..................... ........ 57 8.2 Automatic ECS 602 System design............. design......................... ......................... .......................... .......................... .......................... ................. .... 58 8.3 Automatic ECS 602 Control components components ......................... ............. ......................... .......................... ......................... ..................... ......... 59 9 Control Control system system ECS 410/420/43 410/420/430 0 ...................... ................................. ....................... ....................... ...................... ...................... ................ ..... 60 10 Control Control Unit ECS 430S – CDM 6/5 ...................... ................................. ....................... ....................... ....................... ....................... ............. .. 61 10.1 ECS 430S 2H-CDM6 2H - 400V........................... 400V.............. .......................... ......................... ......................... .......................... ..................... ........ 62 10.2 B1 System System - ECS 430 S ....................... ................................... ....................... ....................... ....................... ....................... ....................... ................. ...... 63 11 Connectin Connecting g diagram ECS 430 P – CDM6/5 ...................... ................................. ....................... ....................... ....................... ............ 64 11.1 Automatic functions ECS 430 P ......................... ............. ......................... .......................... .......................... .......................... ...................... ......... 65 11.2 Control Control system system C-kit matrix descriptio description n ....................... .................................. ....................... ....................... ....................... .................. ...... 66 12 Diagram Diagram CDM 9 ....................... .................................. ...................... ....................... ....................... ....................... ....................... ....................... .................. ...... 67 12.1 Control Control system system D-kit matrix descriptio description n ....................... .................................. ....................... ....................... ....................... .................. ...... 69 13 RADIO EQUIPMENT EQUIPMENT ...................... ................................. ....................... ....................... ....................... ....................... ...................... ....................... ............ 70 13.1 Radio equipmen equipmentt 40 MHz.............................. MHz......................................... ....................... ....................... ...................... ....................... ..................... ......... 72 13.2 Radio equipmen equipmentt 433 MHz............................... MHz.......................................... ...................... ...................... ....................... ....................... .................. ....... 73 13.3 Radio equipment 433 MHz PLUS.......................... PLUS.............. ......................... ......................... ......................... ......................... .................... ........ 74 13.4 Programmin Programming g the transmitters transmitters........... ...................... ...................... ....................... ....................... ...................... ....................... ...................... .......... 78 13.5 Supplementing old 433 MHz installations 1.................. 1...... ......................... .......................... ......................... ......................... ............. 80 13.6 Supplementing old 433 MHz installations 2.................. 2...... ......................... .......................... ......................... ......................... ............. 81 13.7 Supplementing old 433 MHz installations 3.................. 3...... ......................... .......................... ......................... ......................... ............. 82 13.8 Coding Coding tables tables ....................... .................................. ....................... ........................ ....................... ....................... ........................ ........................ ..................... ......... 83 13.9 Radio equipmen equipmentt 869 MHz............................... MHz.......................................... ...................... ...................... ....................... ....................... .................. ....... 85 13.10 Transmitter Transmitterss in the 869MHz 869MHz program program ..................... ................................. ....................... ...................... ...................... ....................... ............ 86 13.11 Receivers Receivers in the 869MHz program program........... ...................... ....................... ....................... ...................... ....................... ....................... ............. .. 87 14 Magnetic Magnetic loop system system ....................... .................................. ...................... ....................... ....................... ....................... ....................... ..................... .......... 90 14.1 Magnetic loop – connection diagram.............. diagram. .......................... .......................... .......................... ......................... ......................... ............... 91 15 Reduced Reduced opening opening – ECS 430 P – CDM 5 ....................... .................................. ....................... ....................... ....................... .............. .. 92 16 Reduced Reduced opening ECS 430P – CDM6 ...................... ................................. ....................... ....................... ....................... .................... ........ 93 17 Reduced opening – ECS 930A / 940A* – CDM 9........................ 9............ ......................... ......................... ....................... ........... 94 18 Dipswitch Dipswitch settings settings – ECS 930A/ 940A – CDM 9 ....................... .................................. ....................... ....................... ............... .... 95
May 2006 rev. 3
Page 3 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
1 HISTORICAL OVERVIEW OPERATORS
1955
1965
7
1975
1985
1990
5
2000
5
) e g i e b ( r 1 o t i M v D O C
) n ) e w o u r l B B ( ( 2 3 M M D D C C
4 M D C
) n e e r G ( 5 M D C
6 M D C
D F / 0 7 8 2 9 M M M M D D D D C C C C
D S H 0 1 M D C
May 2006 rev. 3
Page 4 of 95
Group
Service Manual Industrial Doors
2 OLD OPERATORS 2.1 Overview of delivered Cardo operators 2.1.1 • •
Ovitor operators (Delivered from: Start – 1974)
No spare parts available anymore Only small adjustment/repair actions possible.
Note! Only if complete operator is in good condition! Possible adjustments : Limit switches Possible repairs : Motorprotection switch, Main relays • •
•
If other repairing is needed : REPLACE COMPLETE OPERATOR
2.1.2 Operator CDM-1 (Delivered from: 1974 – 1980)
Most electrical parts for control system not available anymore. Some repair/adjustment actions are still possible.
•
•
Note ! Only if complete operator is in good condition Possible adjustment s : Limit switches / Sliding clutch Possible repairs: Electro-motor, Sliding clutch, Brake, RPM-transmitter, Disengagement, Limit switches. Motor-protector switch, Main relays. •
•
•
If other repairing is needed : REPLACE COMPLETE OPERATOR
Note! Consult checklist for right type of operator. 2.1.3 •
Operator CDM–2 (Delivered from 1978 – 1980)
Most electrical parts (PCB’s) are not available anymore.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 5 of 95
Group
Service Manual Industrial Doors •
Some adjustment/repair actions are still possible.
Note! Only if complete operator is in good condition! Possible adjustments: Limit switches / Sliding clutch. Possible repairs: Electro-motor, Sliding clutch, Brake, RPM-transmitter, Disengagement, Limit switches, Motor-protector switch, Main relays. •
• • • • • • • •
•
If other repairing is needed : REPLACE COMPLETE OPERATOR
Above mentioned operators are not in accordance with the present state of the art, when it comes to safety and other regulations.
If upgrading and/or severe repairing is necessary, the customer should be advised to replace the complete operator by one of our present types. Consult check list for right type of operator!
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 6 of 95
Group
Service Manual Industrial Doors
2.1.4 • •
Operator CDM-5 (Control system in the mechanical unit, 1982 – 1994)
Not all spare parts are still available. All kind of adjustments/repair actions possible.
Note! Only if complete operator is in good condition. •
No safety supervision.
If upgrading and/or severe repairing is needed, Replace the complete operator for one of the present types (Consult checklist for right type). •
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 7 of 95
Group
Service Manual Industrial Doors
2.1.5
• •
Operator CDM-5 (HD) (control system in the mechanical unit, 1982 - 1994)
Not all spare parts are still available. All kind of adjustments/repair actions possible.
Note! Only if complete operator is in good condition. • •
•
No safety supervision If upgrading and/or severe repairing is needed, replace the complete operator for one of the present types (consult checklist for right type) Maximum door weight: CDM 5 = 650 Kg CDM 5 (H) = 1150 Kg
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 8 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 2.2
Circuit Diagram CDM 5 K 2605 4 3 5 5 2 1 3 3 2 1 2 2 4 3 4 4
M
4 3 1 1
0 0 1 x 3
F u 2 2 , 0 x 3
6
5
4
3
2
1
A 6 , 1 1
2 K 1 2 A A 4 3 5 5 2 1 3 3 2 1 2 2
6 4
4 3 4 4
2
5 3
B
6
5
4
3
2
1
R
1
4 3 1 1
2 1 + 4 3
V V 0 5 8 1 T 3 4 x x S 3 3
B a M b
1 1 2 A K A
B M 3 1
1 K
b
0 0 1
a
F u 2 2 , 0
4 1
V 5 1 4 / 0 8 3
N W O R 2 1 B
V 4 2
G
E N P ° 0 1 1
1 1
2 K
6 3 0 1 1
5 1
. .
2 K
5 / 4 M D C
1 D
A 5 1 , 3 A S
1 2 2 2
4
7
6 1 K
1 2 2 2
8
4 5 2 D 3 5
2 K
2
7
4 5 3 5
5 c n o n c
1 3 1 3
2 K S
P O T S 1
1 K
5
2 3
2 3
1 A
F u 2 2 , 0
5
1 G 1 K
0 0 1
4 1
7 2 0 1
1 A
2 A
. .
2 3 1
0 3 8 2
2 A
2 K
2
2
3
4
4 4 3 4
o n
c n
E 2 N G P
c 1 1
May 2006 rev. 3
Page 9 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 2.2.1 CDM-5 Dead man’s grip
PE N 1
L1 T
1
L2 L3 3
5 F1 1AT ON
110°
11
T1 11 1 24V
S4 1
3
5
2
4
6
K1
1
3
5
2
4
6
K2 S1
PE PE
u1 v1 w1 U1 V1 W1 U1
V1
N N N
W1
S2
1 PE
U1
V1
W1 13 32
M
~
M =
~
S4
K1 =
31
S3 K1 TR1 14
22 21 2
A1 TR1
14
K2
22 21 A1
K1 A2
K1
K2 A2
May 2006 rev. 3
Page 10 of 95
Group
Service Manual Industrial Doors 2.3
Control unit CDM-5
2.4 Mechanical Unit CDM5 (Separate control system, 1984 – present)
Spare parts still available All kind of adjustments/repair actions possible Note! Only if complete mech. unit is in good condition • •
•
Maximum door weight: CDM 5 = 650 Kg CDM 5HD = 1150 Kg
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 11 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
2.4.1
Mechanical Unit CDM 5 of sliding clutch and limit switches
adjustment
Adjustment of sliding clutch:
Increase of the sliding force: - Unscrew the 2 lock nuts and the thrust washer. - Take away the necessary rings (One ring increases the force by 10-15kg). - Fit the thrust washer and the lock nuts again. - Test the door. (The sliding clutch has to be adjusted so that the operator is strong enough to drive the door from any position, but not too strong. The door could have to be stopped by hand. Too strong adjustment can give a wrong functioning of the SBD). Adjustment of the limit switches:
To adjust the limit switches, a control plate can be pressed in and then you can rotate the nuts along the screw-thread. Choose first which limit switch is for OPEN and which one for CLOSED. - The door will stop at fully opened position by the limit switch. (Adjust the limit switch so, that the buffer is pressed ca. 2 cm) - On the floor the door stops by the rev. monitor or by the pneumatic safety device. (ECS 430S and 430P) Adjust the lower limit switch, so that it will be activated between 30-70mm from the floor. For earlier activation, rotate the nut towards the limit switch.
May 2006 rev. 3
Page 12 of 95
Group
Service Manual Industrial Doors Replacement and adjustment of the V-belt:
Loosen the brace nut of the motor plate. (Make sure that the motor does not fall off) - Dismantle the V-belt. - Install the new V-belt and adjust the tension of the V-belt by tightening the brace nut again. The V-belt is tensioned correctly if you can press it in the middle for ± 6mm. Replacement of the brake :
Symptom: The electro-motor turns but the door does not. (Sliding clutch is working) - Old type of mechanical units has a brake with the rectifier included. Check that 220VAC reaches the brake while the electro-motor is running. If that is the case: Replace the brake + separate rectifier. If not, check for a fault in the electrical system. - New type of mechanical units has a brake with a separate rectifier. Check that 220VAC reaches the rectifier while the electro-motor is running. If that is the case: Check if the rectifier gives ±110VDC at the secondary side. If not, check for a fault in the electrical system. If the rectifier gives ±110VDC, replace the brake.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 13 of 95
Group
Service Manual Industrial Doors
RPM control:
Symptom: Door goes up for ±10cm and stops. Or: Door goes down for ±10cm, stops, reverses and goes up for ±10cm again.
•
•
•
•
Check the distance between the sensor of the rev. counter and the round surface of the cam on the shaft. (Distance should be 0,8mm = hack saw blade) If this distance is right, check the sensor! (Use an Ohm-meter) In 1 direction you have to measure ± 3.8 MΩ. In the other direction you have to measure an open circuit. If you measure other values, replace the sensor. If the sensor is right, check the electrical part!
CDM-5 old (Control unit in mech. Unit): Replace the black PCB (K035755) CDM-5 new(Control unit ECS601/602 – 430(S)(P): Replace the adapter PCB in the mech. unit (K033808)
•
•
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 14 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
3 MECHANICAL UNIT
CDM-6
3.1 Mechanical Unit CDM6 (HD)(Separate control system, 1984 – present) • •
Spare parts available All kinds of adjustments/repair actions possible.
Note! If one of the inside toothed wheels is broken or damaged the complete gear unit has to be replaced.
• • •
Maximum door weight: CDM 6 = 275 Kg. CDM 6 HD = 350 Kg.
May 2006 rev. 3
Page 15 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 3.2
Installation of fixing bars CDM 6 (HD)
Installation of fixing bars CDM6-(HD) Min 5° Max 30°
Min 5° Max 30°
Min 5° Max 30°
The bars should be aligned to each other see fig. • The bar on the mech. unit can be installed upwards or downwards. • The other bar can be fitted in Line with or towards the mech. Unit. • The Z-bar design ensures that the unit can follow the movement of the door shaft without hinder. Note! Lock nuts must be used where indicated Installation of fixing bars CDM6-(HD)
Between both fixing bars should be fitted a vibration damper see fig. 1 vibration damper 2 fixing bar
Min 5° Max 30°
May 2006 rev. 3
Page 16 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
3.2.1
CDM6 (HD) adjustment of limit switches and sliding clutch
MOTOR
M
2 MOTOR UNIT
3
1
V
2
W
3
N
N
1 2 3 N
U1 V1 W1 N
1
Y1 5
S4
7 1 9
.. S1 S2 S3
LIMIT SWITCH 6 UNIT
4
U
1 2 3 4 5 6 7
1 2 3 4 5 6 7
2 1 2 3 4 5 6 7
X01 1 LIMIT SWITCH PART 2. SLIDING CLUTCH
2 MOTOR 3 OPERATOR 4 LIMIT SWITCH UNITS 5 RPM CONTROL 6 DISENGAGEMENT SWITCH 7 LIMIT SWITCH "completely open" 8 LIMIT SWITCH "closed" 9 LIMIT SWITCH "reduced opening"
S3 S2 S1
Adjustment of limit switches . Door will stop above by limit switch and on . The bottom by the RPM control. . The lower limit switch has to be adjusted so . That it will be activated approx. 50 mm from . Floor level. . For earlier switching: turn the switch arm . Towards the micro switch roller. . For later switching: turn the switch arm away . From the micro switch roller. S1 = Limit switch "Completely open" S2 = Limit switch "Closed" S3 = Limit switch "Reduced opening"
B
A
Adjustment of the sliding clutch . Loosen clamping screw B. . Screw adjusting nut A inwards to increase . Sliding force. . One turn of the adjusting nut corresponds . To about 10 kg change of the sliding force.
May 2006 rev. 3
Page 17 of 95
Group
Service Manual Industrial Doors
4 CONTROL SYSTEM CDM-5/CDM-6 (METAL BOXES)
CONTROL SYSTEM CDM5/6 – 01, Steel control box (1984-1988) •
•
•
Not all spare parts are still available. Has been delivered with or without safety supervision. If upgrading or severe repairing is needed, replace the control unit by one of the present systems (consult check list for right system).
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 18 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 4.1
CDM 5/6 - Control unit CDM6-07 K2-12253 1 2 3 4 5 6 7 8 9 1 1 1 1 0 1 2 3
F2
3 8 0
1 5
X1
F1 T1
1 2
3
K20
4
5 6
X2
0
7
8
1 2
3 4
2 4
K12271
9
K21
K22
K19
K18
X3
6
K11
1 3
K17
K6868
4
K6869
K1
21
22
5
6
K2
1
X4
7
K10
8
K14
W 2
K6915
1/2
A 1 - 3 6 , 0
K15
X5
V 4
S12 UP
K2517
K5784
K12
2 4
1/1
K16 U 6
1
H1
4 2
9
3
K8119
2
3
4
6
6
1
K13
2
5
22
5 3
5
S21
21
3
N
2
S5 STOP
1
5 6
X6
X9
1 2 3 4 5 6
1 2 3 4 5 6
X7 1 2 3 4 5 6
X9 1 2 3 4 5 6 7
Q1 K5775
K6979
S1 3 N W1
2
1
X10 V1 U1 K5756
5 L1
3 L2
1 L3
K6978
S15 DOWN
CONTROL UNIT CDM 6-07 LAYOUT BASEPLATE AND LID
May 2006 rev. 3
Page 20 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 4.3
CDM6 Main diagram - 111 K2 - 5640
PE
3x380V (3x220V), 3x415V L1 L2 L3
N 1 T
5
3
1
F2 2A
4
X8 2
PE
N
1
2
c
c S1
B1
n> c
S2 c
N
1
PE
N
U1 V1 W1
Y1 M1
2
3
N
U1 V1 W1
2 K1
1
4 3
S10
S13 S12
K1
K17 no
nc
1
S14 K16
X8 4
X8 5
X8 6
31
nc X5 4 PNE
b
~
P X1 6
c
d
e
Y1
14 K10 14 K11 14 K12 13
13
5 9
11 1
5
13
8
8 8
8 4
9
7 4
5
11
9
12
8
8 4
12
X4 1
9
X4 2
K12
a
a
a
b
b
b
K15
K16
K17
K18
no
10 no
12 nc
1
5
K13 9 K11 X6 1 X7 1 X5 6 8 S15 S17 S16
X9 9
X6 2 X7 2 X5 5
5
X9 8
X1 1 53
X1 15
10 nc
X9 5
22
K2 K2
21
54
K2 21
X4 6
b
10 nc
4 X9 6
5
(S19)
X4 7
a
10 no
no
X4 4
>1 =
DRAWING 112-K2-5783
1
nc
K10
X1 8 22
b K14
12
9 K18
g i
a
13
13
c
S8
L
f
&
=
3 X 220V
h
>1 =
M1
no K15
X4 3
~ =
X1 7
L+
c
X5 3
K2
X8 3
X10 a
X1 9
X7 3 K2
44
>1 =
4
K13
c
X7 4
K2
PEU1V1 W1 2
3 X 380V (3 X 415)
43
K1
32
a b
S11
X3 5 X31 X3 3 X6 5 X7 5 X5 2 X1 1
S7
S3
6 5
32 31
no
3
PE
c
S9
no K14
9
no
nc
5
nc
X6 4
X2 6
c
X3 6 X32 X3 4 X6 6 X7 6 X5 1 X1 3
T1
2
6
3
X2 7
X2 5 X9 3
nc
1
X6 3 X9 1 S5
S4
nc
nc
4
X4 8 12 12 K11 K12 K10 4 4 4
c 110°
24V
2
X1 13 X9 7 X2 9 12
7
Q1
6
X8 1
F1 2A
X1 2
S18
X1 4
X2 3
X2 4
X4 5 14 K13 X4 9
5
12
A1 X8 7 X2 2
13
9
X2 8
X9 4
A1
K1 UP
A2
5 1 : 1 X
K2 DOWN
A2
2
1
2
3
1
2
2
3
4
3
3
4
2
5
6
3
5
6
13
14
13
14
43
44
7
43
44
31
32
7
31
32
13 21
22
11 21
22
12 53
54
12 53
54
1
10 no
13 no
12 8
10 nc
13 nc
12 4
12
7
CDM 6 MAIN DIAGRAM 111-K2-5640
May 2006 rev. 3
Page 20 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 4.3
CDM6 Main diagram - 111 K2 - 5640
PE
3x380V (3x220V), 3x415V L1 L2 L3
N 1 T
5
3
1
F2 2A
4
X8 2
2
PE PE PE
N N N
1
2
1
c
c S1
B1
n> c
S2 c
Y1
K1
1
4 3
5
43
K1
c
S11 S10
S13 S12
31
X8 4
X8 5
X8 6
nc X5 4
44 PNE
K17 no
nc
1
S14 c
P
b
~
X1 6
c
d
e
Y1
14 K10 14 K11 14 K12
M1
13
13
5 9
11 1
5
13
K16
8
8 8
8 4
9
7 4
5
11
9
12
8
8
a
a
a
b
b
b
K15
K16
K17
K18
no
10 no
12
12
4
nc 10 no 10 nc
X4 1
9
(S19) X4 2
K12
13 nc
5
S16
X9 9
X6 2 X7 2 X5 5
5
X9 8
X1 1 53
X1 15 22
K2 K2
21
X9 5
54
K2 21
X1 2
S18
X1 4
X2 3
X2 4
X4 5 14 K13 X4 9
A1 X8 7 X2 2
13
X2 8
5
12
9
X9 4
A1
K1 UP
A2
5 1 : 1 X
K2 DOWN
A2
2
1
2
3
1
2
2
3
4
3
3
4
2
5
6
3
5
6
13
14
13
14
43
44
7
43
44
1
10 nc 13 no
1
K13 9 K11 X6 1 X7 1 X5 6 8 S15 S17
X4 6
b
10 nc
4 X9 6
5
X4 7
a
10 no
no
X4 4
>1 =
DRAWING 112-K2-5783
1
nc
K10
X1 8 22
b K14
12
9 K18
g i
a
13
13
c
S8
L
f
&
=
3 X 220V
h
>1 = L+
no K15
X4 3
~ =
X1 7
>1 = a
c
X5 3
K2
X8 3
X10
4
K13
X1 9
X7 3
K2
PEU1V1 W1 2
9
K1
X3 5 X31 X3 3 X6 5 X7 5 X5 2 X1 1
X7 4
K2
32
a
3 X 380V (3 X 415)
no K14
S7
S3
6
U1 V1 W1
b
M1
3
N
U1 V1 W1
2
32 31
no
3
2
S9
no
nc
5
nc
X6 4
X2 6
c
X3 6 X32 X3 4 X6 6 X7 6 X5 1 X1 3
T1
6
3
X2 7
X2 5 X9 3
nc
1
X6 3 X9 1 S5
S4
nc
nc
4
X4 8 12 12 K11 K12 K10 4 4 4
c 110°
24V
2
X1 13 X9 7 X2 9 12
7
Q1
6
X8 1
F1 2A
12 8
12
12 4
31
32
7
31
32
13 21
22
11 21
22
53
54
53
54
7
12
12
CDM 6 MAIN DIAGRAM 111-K2-5640
May 2006 rev. 3
Page 21 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
5 AUTOMATIC SYSTEM ECS 600 5.1 Additional system ECS 600 (Added to control system CDM5/6 or to CDM5 with control system in mech.unit, 1984-1988) •
•
Not all spare parts are still available. If upgrading or severe repairing is needed, replace the control system and the additional system by one of the present types.
•
(Consult check list for right system). •
For automatic systems : see ECS 601.
May 2006 rev. 3
Page 21 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
5 AUTOMATIC SYSTEM ECS 600 5.1 Additional system ECS 600 (Added to control system CDM5/6 or to CDM5 with control system in mech.unit, 1984-1988) •
•
Not all spare parts are still available. If upgrading or severe repairing is needed, replace the control system and the additional system by one of the present types.
•
(Consult check list for right system). •
For automatic systems : see ECS 601.
May 2006 rev. 3
Page 22 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
5.1.1 Functional description ECS 600
ECS 600 is an additional automatic system to be connected to old operators CDM-5 (Control system in the Mech. Unit) and to control systems CDM5/6-01. The basic system consists of 2 circuit boards: 5.1.2
-
Different types for CDM5 and CDM6 Receives signals from the control system and converts them into logic signals (12VDC) to the circuit boards for automatic functions. Receives commands from the circuit boards for automatic functions and converts them to the control system. In the front panel there are indication LED’s for the position of the door.
5.1.3
-
Interface unit (Obsolete)
Power unit (Obsolete)
Supplies a stabilized, suppressed drive voltage to the other components of the additional system. In the front panel there are indication LED’s to see if all voltage is present and a switch to switch off the automatic functions.
Note! For more information concerning the automatic functions, see chapter ECS601.
May 2006 rev. 3
Page 23 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
5.2
Automatic door operating system ECS 600 1
7 K-12100 (K-12103)
13 K-12106
interface CDM5 (interface CDM6)
18 K-12109
Closing Timer Warning signal
Power Unit
23 K-12112 (K-12113)
28 K-12114 (K-12115)
33 K-12116
Remote Control Photoelectric Magnetic loop Radio 27 (40) Mhz Amplifier 1(2) Ch Vehicle detector
Ch1 Ch2
12V 24V
24V
Ch1 Ch2 F
32V RF t1
1,6A
16-160 t2
Aut
6TE
6TE 7
1-9 4-36
Man
1
2-20
6TE 13
5TE 18
5TE 23
5TE 25
8TE 33
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 4 4 46 48 50 52 54 56 58 60 62 64
1 3 5 7 9 11 1 3 15 1 7 19 2 1 23 2 5 28 2 7 29 3 1 33 3 5 37 3 9 41 4 3 45 47 49 5 1 53 5 5 57 5 9 61 6 3
Cable wiring diagrams
Spare for board pos 7 Pushbutton long vehicle
114-K4-12465
Interlock Unit
114-K4-12117
Sensors for board pos 7 Magnetic loop
114-K4-3084
Photoelectric Optics
114-K4-12447
SCR-switch, warning lights
114-K4-12173
Pullstation for CDM5
114-K4-507
Inhibit key
114-K4-12464
External function
114-K4-867
Door Operator -CDM5 -CDM6
114-K4-2546 114-K4-5792
May 2006 rev. 3
Page 24 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
5.3
CDM5 - ECS 600 - wiring diagram
CDM 5 - ECS600 Wiring diagram
Control units for: CDM5
CDM5/SL
CDM5-07, 08
CDM5-01
1 12
1 13
1 13
1 13
9 11 LB 5 6 3 4 7 8
10 12 LB 6 7 4 5 8 9
12A 12B 6 7 2 3 8 9
10 8 4 5 3 2 ** 6 7
*
*
**
ECS 600 Screw terminal RKKR 12G 0,75 HO3VV-U 1 2
1 2
3 4 5 6 7 8 9 10
*)
Wire from pneumatic switch (LB) connected to screw 9 (10 in CDM 5 / SL) to be connected to wire 4 from ECS 600 under flying top joint.
**)
Remove loop if any and connect wires 7 and 8 in series with existing stop devices.
8 9 10 11 12 13 14 15
May 2006 rev. 3
Page 25 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 5.4
CDM6 - ECS 600 - Wiring diagram
x2/1 x2/2 x2/3 x2/4 x2/5 x2/6 x2/7 x4/5 x4/6 x5/1 x5/2 x5/3 x5/4 x5/5 x5/6
Connect wires 1 and 2 to X2/9 end X2/8 resp. if supply voltage 24VAC is to be disconnected from ECS 600 when the operator is disengaged.
RKKR 18G 0,75 HO3VV-U 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 PE
2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
May 2006 rev. 3
Page 26 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 5.5
Photocell ECS 600
7 9 1 2 2 3
k c d a e l B R
S T
w o l l e Y
d l e i h S
M R
Photocell optics Channel 1
6 8 0 2 2 3
k c d a e l B R
S T
w o l l e Y
d l e i h S
M R
Photocell optics Channel 2
May 2006 rev. 3
Page 27 of 95
Group
Service Manual Industrial Doors
6 CONTROL SYSTEM ECS 601
6.1 Control system ECS 601 (for CDM5 and CDM6, 1988-1993) • •
•
Spare parts are still available Has been delivered with or without safety supervision. If severe repairing is needed, replace the control unit by one of the present types. (consult checklist for the right system).
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 28 of 95
Group
Service Manual Industrial Doors
6.2 Functional description ECS 601/602 The control systems ECS601/602 can be connected to the mechanical units CDM5 and CDM6. The basic function consists of 3 circuit boards: 6.2.1 Contactor unit
There are 2 contactors on the circuit board which connect the mains voltage to the motor. The connectors are controlled by signals from the impulse unit. The contactor unit also includes a protective transformer which supplies the 24 VAC for the control voltage. 6.2.2 Impulse unit
The impulse unit includes all the electronic control functions. - Gives the needed signals to the contactor unit. - It senses the function of the safety device. - It senses the RPM-control. When it indicates that the number of rotations is too low, the door will be stopped and reversed, depending on the position of the door. - Maximum running device = 45 sec. Power has to switched off and on again after ± 10 sec. - The 1-button function is built into this board. 6.2.3 Safety supervision unit (Pinch guard monitoring)
In most countries it is a regulation that the pneumatic safety edge is tested every time when the door hits the floor. As soon as the limit switch “Door closed” is activated (± 50mm from the floor) the function will be tested and can be seen by the flashing of the LED on the front. If the pulse is too short or not given at all to the supervision unit, the control system switches over to so-called dead man’s function. This is indicated by the red LED on the front of the unit. It will stay on constantly.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 29 of 95
Group
Service Manual Industrial Doors SYSTEM DESIGN
Board 7-9 Basic control Board 10-11 Optional automation
Control box in ABS plastic
5 Circuit board 1 Bottom part 2 Collar 3 Top lid
13 Motor protection switch 15 Terminal connections 16 Button control set
4 Lower lid Additional automations Grundstyrning
10 Interface Power unit 6 Cover plate11 7 Contact und
11. 4 board positions for additional automations
8 Impulse unit
12 Antenna for radio receiver
9 Safety supervision unit 14 Semiconductor for warning light
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 30 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Connection of automation circuit boards
The board positions X4-X7 on the circuit board are intended for auxiliary automation circuit boards. The contacts are connected to terminals X13-X16 via lines on the circuit board shown in the diagram below. ie. X4 - X13. X5-X14 etc. Crawford Door Strömstad Sweden X0
X1
X2
X3
X4
X5
X6
X7
X16
X17
X09
X10
X11
X15
X08 X14
X13
The terminal X12 has a special function. Signals between two interlocking doors are transferred via X12. Bus signals are also transferred through this terminal and a band cable to an extra box for automation boards. The external units belonging to a specific automation function are connected via a connection terminal installed on the relay track. This is connected to terminal X13-X16 via ribbon cable.
X12
May 2006 rev. 3
Page 31 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
INTERFACE POWER UNIT
The unit is connected to the 4th board position. X3 (pos 37-42 in the casing). The module contains a neutralized and stabilized 12 V DC drive voltage unit for the supply of voltage to the electronics. The electronics on the board also function as an interface between basic control and automatic options. This implies that the basic control 24 V AC signals are converted to 12 V DC which the automatic units work with. The front panel of the board contains diode Lamps which indicate the current door position.
Fully open door interface / Power unit
Opening door Door opened between limits reduced o enin Closing door Fully closed door Supply voltage to automatic board 12 V DC
12 V DC Man
Manual function ie. automatic board disconnected, the door is operated with the aid of basic control. Switch automatic / manual function
Aut Man
May 2006 rev. 3
Page 32 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
AUTO CLOSING / WARNING LIGHT
The units include two basic functions, automatic closing and warning lights. Controlling of warning Lights The control signals are sent to a semi-conductor relay (thyristor) which in turn connects 110/220V to the lamp fittings. Control signal to thyristor, red warning signal, (flashing or steady) Control signal to thyristor, green warning signal
Closing Timer Warning signal
(steady light) When time t2 is running the LED is flashing with 10w intensity The flash frequency depends on the setting of the f2 trimming screw. Short impulse indicates that the closing signal goes to the interface board. When time t1 is running the LED is blinking with low intensity. The frequency depends on the setting of the t1 trimming screw. Automatic closing
t1
The board contains times circuits which control how long the door is to be open before t is automatically closed. This interval is divided into two time intervals t1 and t2. Setting of t1
2-20 16-160
t2
t1= the time the door is fully open with the green lamp on.
1-9
The time range. (2-20 or 16-160 sec.) is selected with the switch and the time is adjusted: with the trimming screw.
4-36
Setting of t2 t2= the time the door is fully open but warns for closing
with a flashing red signal. The time range (1-9 or 2-36 sec.) is selected with the switch and the time is adjusted with the trimmin screw.
The total time when the door is open is t1 + t2. The times t1 and t2 can be changed with switch S4/3 on the circuit board, see next page.
May 2006 rev. 3
Page 33 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Optional automation On the circuit board there are two blocks with DIP switches, S3 and S4 plus a bar block L1. Note !!!! The bar block shall sit in lower position on L1 for ECS 601. The top position is used for ECS 600.
* D1 * D3 * D2
ON
ON
S3
S4 L1
S1 R13 S2 R14
S3/1 closing.
of
Flashing red light before
on Flashing red light before closing and between limit positions. S3/2 of red light for closed door.
No
on Constant red light for closed door. S3/3 light.
of
No green
on Constant green light for fully open door.
May 2006 rev. 3
Page 34 of 95
Group
Service Manual Industrial Doors Example:
The time t1 + t2 is timed from the first of "fully open door" or "passage of safety photo cell / magnetic loop". The time t1 + t2 is timed from "fully open door". The switches of S3 are set on and off.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 35 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Optional automation The conditions for automatic closing are selected with S4. S4/1off The time t1 + t2 is timed from the first of "fully open door" or "passage of safety photo cell / magnetic loop". on The time t1 + t2 is timed from "fully open door". S4/2 off The closing the safety function is reset when the downwards. on The closing the safety function is reset when the closed.
memory for door moves memory for door is fully
S4/3 off The timer works according to the S4/1 setting. When safety photo cell/magnetic loop is passed, remaining time t1 is divided on by 4. The time interval t1 applies as per setting on front panel. Example:
Exit from parking deck S4 switches set to: off off off
Assume that t1 = 40 sec. and t2 = 10 sec. The door opens. When fully open, the time t1 starts to run and when it has run out, t2 starts to run. If no one passes the photo cell, the door will close after 40 sec. + 10 sec. = 50 sec. If someone passes the photo cell after, for example, 12 sec. the remainder of t1 (40 sec. - 12 sec. = 28 sec.) is divided by 4:28 sec./4 = 7 sec. The door starts to close after a total time of 12 sec. + 7 sec. + 10 sec. = 29 sec.
May 2006 rev. 3
Page 36 of 95
Group
Service Manual Industrial Doors The consequence of S4/2 being set in off position is: If a closing door is made to reverse, e.g. by the pinch guard monitor or a safety function, it will not close automatically, unless the photo cell is activated. This is because the closing memory is reset when the door has started to move downwards.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 37 of 95
Group
Service Manual Industrial Doors
Optional automation SEMI-CONDUCTOR RELAY (THYRISTOR)
The semi-conductor relays for control of mains voltage to the warning light are comprised of separate circuit boards mounted on the relay rail. One board is required for each warning light. Max. effect 250W. Connection ot warning light
The semi-conductor relay(s) and lamps are connected to the connection block as per the diagram below. The connection block is linked via ribbon cable to the terminals X13-16 which belong to the board position where the insert circuit is put in.
By using the connections to the in the diagram, the automatic closing function or the opening can be blocked, e.g. by an external timer (closing contact).
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 38 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Optional automation PHOTO CELL AMPLIFIER
This unit is available as a single channel and double channel amplifier.A photo cell transmitter and corresponding receiver can be connected to each amplifier channel.
The system works with IR-light
Indicating codes for each channel. Lights when the IP beam is unbroken and received by the receiver.
1 Y + + 2 Y
Photoelectric Amplifie r 1(2) Ch
Ch1 Ch2 S1 on
12 3
on
12 3
S2
On the circuit board there are two switches which can be set according the function of the photo cell. The following alternatives are available: • Safety function • Acknowledgement function (interlock) • Opening function Switch S1 is used to select the function for amplifier channel 1;
May 2006 rev. 3
Page 39 of 95
Group
Service Manual Industrial Doors on off off Safety function off on off Acknowledge function off off on Opening function The corresponding settings are made on switch S2 for channel 2.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 40 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Optional automation CONNECTION
The photo cell transmitters and receivers are connected to the connection block as per diagram below. Use shielded cable e.g. EKLK 39 1.5. Note !!!!
The shield must be connected to earth in view of risk for inductive interference from high tension cables. Connect via ribbon cable to the terminals X13-X16 which belong to the circuit board position where the insert board is to be put.
May 2006 rev. 3
Page 41 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Optional automation MAGNETIC LOOP DETECTOR
The detector can power and sense two separate loop systems each connected to their own channel. Each loop system can in turn comprise two in series or parallel connected loops. The detector is micro processor controlled and does not require trimming or manual resetting. There is also an automatic fault tracing facility which continuously checks for loop failure/grounded to earth.
Indicating that vehicle is over loop system connected to channel 1 or 2. Indicating fault in one of t he loop systems
Magnetic loop Vehicle detector
Ch1 Ch2 F
ON OFF ON OFF 10
2 1
SW1 ON OFF
1
SW3
2 1
SW2
0 1 . . . . . 7
J1
May 2006 rev. 3
Page 42 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
There is a jumper field with 8 pairs of pins and three DIP switches for the setting of the detector function on the circuit board. Note!!!! If one of the channels is not used, all switches for this channel shall be set in the off position. Jumpers
The output signal status is selected by putting jumpers over the pair of pins which are closest to the contact unit J1. The pairs of pins 0-3 are used for the loop system in channel 1 and 4-7 for channel 2. Channel 1, jumper in pos.
Channel 2, jumper in pos.
Output signal status
0 1 2
7 4 5
Acknowledge impulse Reversing impulse (safety) Opening impulse Opening impulse to opposite
3
6 door in interlock
May 2006 rev. 3
Page 43 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Optional automation SETTING OF FREQUENCY
When two loop systems are close to each other there is always a risk for "overlapping" between them. This can be avoided by using different frequencies in the loop systems. The frequency can be set to 4 different values. The DIP switches SW1 is used for channel 1 and SW2 for channel 2. off off on on ADJUSTMENT OF ATTENDANCE TIME
off on off on
SENSITIVITY
high frequency average high frequency average low frequency low frequency AND
Detector sensitivity and attendance time are set on the DIP switch SW3. The switches 5-6 are used for sensitivity and 7-8 for attendance time. SENSITIVITY
off on off on
off off on on
Sensitivity should be set so that the detector will not respond when the front bumper of a car reaches the edge of the loop but only when the whole loop is covered by the car. It may be necessary to change the sensitivity if special vehicles are to activate the detector. ATTENDANCE
If an object which is detected by the magnetic loop detector remains for a certain time, the attendance time, the detector will readjust automatically. The object will no longer be detected. The attendance time can be set on the switch block SW3/ 7-8 for channel 1 and SW3/3-4 for channel 2.
low average low average high high
May 2006 rev. 3
Page 44 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors off on off on Note !!!!
off off on on
If one channel is not used all corresponding switches must be set in off position.
100 msec. impulse 3,5 min. 7,5 min. 2 hours
May 2006 rev. 3
Page 45 of 95
Group
Service Manual Industrial Doors
Optional automation The magnetic loops are connected to ECS 601 via a connection block mounted on the relay rail. The connection block is connected by a ribbon cable to one of the terminals X13-X16, which connects internally to the circuit board position where the insert board is to be put.
The connections "Block Ch1/Block Ch2" on the connection block are used when an external function is to be used to deactivate one of (or both) the loop systems, e.g. timer (closing contacts) can be used for the purpose.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 46 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
Optional automation INTERLOCKING
Used to achieve an interlocking function i.e. to avoid the exchange of air in the door opening e.g. for reasons of heating economy. Interlocking normally functions so that one door is blocked in closed position as soon as the other door is opened. An acknowledging photo cell in the interlock senses that a vehicle has passed the first door and prepares the opening of the second door as soon as the first one has closed. If the "OPEN" command is given to an interlocked door the command is tored and carried out when the block has been taken away. Indicates that door A or B is blocked Indicated that door A or B receives OPEN signal
Crawford
Interlock Unit A B X
When long vehicles are to pass through the interlock it is possible to cancel temporarily the Indicating "long vehicle"
interlocking by pressing a separate push button on the wall. Both doors open then at the same time.
Interlocking can also be cancelled with push buttons in the front panel by blocking of the Push buttons for blocking of door A or B in open position. Diode lamp on the button for indicating blocking. Push button which breaks the interlocking function. A diode lamp indicates that interlocking is blocked.
doors in the open position (summer connection). An open impulse to the outer door will then be transferred to the inner
A A (X)
May 2006 rev. 3
Page 47 of 95
Group
Service Manual Industrial Doors door and vice versa. There is also a push button which breaks the interlocking function completely.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 48 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
Installation
MAINS
380V AC MAX 10 A
M
MOTOR M O T O R U N I T
LIMIT SWITCH UNIT CLUTCH RELEASE SWITCH RPM TRANSMITTER
n>
LIMIT SWITCH CLOSED
B U T T O N B E U X T T T E O R NN U A L N P I T U S H
N
U
1
V
2
W
3
1 2 3 N
1 3 5
Q
N
U1 V1 W1 N
N
LIMIT SWITCH OPEN
U P N U I T S H
1 2 3
LIMIT SWITCH REDUCED OPENING
STOP DOWN
UP STOP DOWN
EXTRA SAFETY
SINGLE BUTTON FUNCTION
OPENING FUNCTION
1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 5 6 BLACK BROWN 1 2
1 2 3 4 5 6
UP
PNEUMATIC SWITCH
1 2 3 4 5 6 7
p
1 2 3 4 5 6 BLACK BROWN 1 2
1 2 1 2
1 2 1 2
P U S H B U T T O N S I N
UP
STOP
DOWN
C O MAN´S V DEAD E GRIP DOWN R
Connect pass door contact on clamp 16 or 17 in series with stop button.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
X 0 8
X11:1 X11:2 X11:3 X11:4 X11:5 X11:6 X10:1 X10:2
May 2006 rev. 3
Page 49 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
c o 8 1
2 A F 5 m
c o 4 1
1 3 T
1 A F 1 T
c o 6 1
V 0 2
V 4 2
V 0 8 3
V 0 2 2
c o 2 3
1 T
W W k k 3 3 A 7 , 7 , 8 , 0 0 3
1 0 6 S C E c i t a m o t u A
W k 7 A A 3 , 1 , 9 , 0 1 1
t n e r r u c n i a M
W k A 2 3 1 , 6 , A 0 0 1
V 0
c o 8 c o 4 2
c o 6 c o 2 1
2 c r 1 2 1 K
2 2
3 A
1 2
2 K
V V 0 0 8 2 3 2
1 Q
1 u
1 Y
) V 0 2 2 * 3 (
1 A
1
4
3
1 w
6
5
1 v
1 K 1
2
3
4
3
4
1
2
5
6 2 K
1 2 3 E L L L N P
1 v
2
6
z H 0 6 / 0 5 V 0 2 2
M
1 K
5
z H 0 6 / 0 5 V 0 8 3
1 w
1 A 2 K 1 c r
2 2
1 u N
1 Y
) V V M 0 5 8 1 4 3 * * 3 3 (
May 2006 rev. 3
Page 50 of 95
Group
Service Manual Industrial Doors
7 THERMOSPEED (1988 - 1998)
7.1 • • •
• •
Thermospeed (1988 - 1998)
Spare parts are still available Adjustments and repair actions are still possible Control unit as ECS 601, but with frequency converter Special mechanical unit For automatic systems : see ECS 601
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 51 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 7.2
Automatic ECS 601
Hole, only when safety pull unit Photocell support
Photocell unit
Fit the photocell support to the photocell unit, see fig. 1.
Roller Left side installation
Always fit the photocell receiver on the left side. Receiving eye = marked “R”. (or in older versions, silver painted eye) Transmitting eye = marked “F” (or in older versions, gold painted eye)
Receiving eye Photocell support
Fit the photocell unit on the left side and the right side. Drill and screw with 20 screws, see fig. 2. Alternative corner brackets and installation of the photocell support. Adjust the photocell units so that they are directed towards each other exactly.
Receiving eye
May 2006 rev. 3
Page 52 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 53 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors Adjustment of limit control
1 low speed closing
3 limit closed position
High speed area 1 and 2
Rough adjustment
Adjustments of the end limit position see fig.1 The limit position closed should be activated when the door is approx. 50 mm from being completely closed.
low speed opening
4 limit open position
The limit position open should be activated when the door is approx. 50 mm from being completely open. Check if the door stops with the shock absorbers approx. 20 mm compressed. Adjustments of the low speed limit position see fig.1 Set the low speed inner cam so that it stops approx. 600 mm before the door reaches its open position. Speed adjustments see fig. 2 Turn the variable speed control up/down to 75% of its adjustment level. Test the door
Adjust UP speed + ● plastic rivet (don´t touch) ○
The opening and closing time should be min. 6 sec. for a 4 meters high door, min. 5 sec. for 3.5 meters and 4.5 sec. for a 3 meters high door.
Adjust DOWN speed + ● plastic rivet (don´t touch) ○ plastic rivet (don´t touch) ○
Note! The value refers to the average speed 0.7
m/s.
May 2006 rev. 3
Page 54 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
7.3
ECS 601 Thermospeed 111-K3 - 31207
5
MOTOR UNIT
34 RAIL
37 PUSH BUTTONS
33 BACK PLANE
220 AC X11.4
PE L1 N
1
31 FREQUENCY CONVERTER 32ac
4-6 A
3
2 4
L1
STOP
18ac
15V 0V 315 15V
+
X11.3
AT
X8.17
1AT
X8.16
11
N
29 IMPULSE UNIT
38 SAFETY SUPERVISION UNIT
220V
24V 0V 20V
X8.11
14ac
14ac
X8.18
16ac
17ac
+ -
1ac
X8.1
2ac
X8.7 DEAD MAN GRIP DOWN
13 U1 V1 W1 Y1 N
(1)
4
(2) (3)
M
(4) (5)
X18.2
8ac
14ac
X18.3 4 X8.2
8
X8.5
Y1
X8.13
12 D1
X8.18 X11.6
26
24 28 27 23
CLUTCHRELEASE SWITCH
DOWN
(1)
12
16 20 24 28
X11.7 32
(2)
X8.19
LIMIT SWITCH CLOSED
(3)
X8.12
LIMIT SWITCH LOW SPEED
(6)
1
(7)
2
U1 V1 W1
H4 Hrav
Y1 N L1
24ac
9ac
8ac
25ac
Hu
L1
L1
H1 H1bo IMPD
PE
HDON
15ac 23ac
n>
(3)
LIMIT SWITCH OPEN
(4)
X17.6 X17.5
29ac
X8.3
H3 Hugr
X9.4
18ac
X8.15
UP
SAFETY DEVICE
18
12ac 13ac
X11.1 6ac
X8.14
27ac
X8.8 P H O A T M O P L E L I F E I E C R T R I C
3
6 7
24VDC
H3 Hugr
X8.9 21ac
K 3 1 0 1 2
30ac
10a
X11.2
14
12ac
11ac
4
X8.4 X9.2 X17.1 X8.6
8
X8.29
9
X8.21
May 2006 rev. 3
H1
A . v e r 7 0 2 1 3 3 K D E 1 E 1 P 1 r S : e O b M m R u E n H T G / W 1 D 0 l 6 a n S i g i C r E o
Page 55 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 7.4
Photocell kits K 35724
K-35746 Set of Emitter
Cable color OLD
White (+) Green (-)
NEW White (+) Blue (-)
May 2006 rev. 3
Page 55 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 7.4
Photocell kits K 35724
K-35746 Set of Emitter
Cable color
NEW White (+) Blue (-)
OLD
White (+) Green (-)
K-35747 Set of Reciever
Cable color
White (+)
NEW White (+)
Green and Brown (shield)
Blue and shield.
OLD
May 2006 rev. 3
Page 56 of 95
Group
Service Manual Industrial Doors
8 CONTROL SYSTEM ECS 602
Control system ECS 602 (for CDM5 and CDM6, 1988 - 1993) • •
•
Spare parts are still available Has been delivered with or without safety supervision. If upgrading or severe repairing is needed, replace the control system for one of the present types (consult check list for the right system).
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 57 of 95
Group
Service Manual Industrial Doors 8.1
Functional description ECS 601/602
The control systems ECS601/602 can be connected to the mechanical units CDM5 and CDM6. The basic function consists of 3 circuit boards:
8.1.1
Contactor unit:
8.1.2
Impulse unit:
There are 2 contactors on the circuit board which connect the mains voltage to the motor. The connectors are controlled by signals from the impulse unit. The contactor unit also includes a protective transformer which supplies the 24 VAC for the control voltage.
The impulse unit includes all the electronic control functions. - Gives the needed signals to the contactor unit. - It senses the function of the safety device. - It senses the RPM-control. When it indicates that the number of rotations is too low, the door will be stopped and reversed, depending on the position of the door. - Maximum running device = 45 sec. Power has to switched off and on again after ± 10 sec. - The 1-button function is built into this board. 8.1.3
Safety supervision unit: (Pinch guard monitoring)
In most countries it is a regulation that the pneumatic safety edge is tested every time when the door hits the floor. As soon as the limit switch “Door closed” is activated (± 50mm from the floor) the function will be tested and can be seen by the flashing of the LED on the front. If the pulse is too short or not given at all to the supervision unit, the control system switches over to so-called dead man’s function. This is indicated by the red LED on the front of the unit. It will stay on constantly.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 58 of 95
Group
Service Manual Industrial Doors 8.2
Automatic ECS 602 System design
Apparatus Box in ABS plastic
1 2 3 4
Bottom part Collar Top cover Bottom cover Components
5 6 7 8 9 10 11 12
Circuit plan board Cover plate Contactor unit Impulse unit Pinch guard monitoring Motor protection switch Terminal connections Operating button unit
Material: ABS plastic. The Top cover is transparent. Impact strength and chemical resistance are sufficient for a temperature range from -30º to +60º. Electrical safety: Complies with IEC specifications for insulation and screen protection for connections to mains supply and control electronics on circuit board.
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 59 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
8.3 Automatic ECS 602 Control components
Circuit plan This board includes all contacts and line tracks required to connect the insert board and other components included in the basic control together. X0 - X2 Board contacts for basic control. X07 = Screw terminal for connection of external push button boxes and air switches. The push button for the one button operation is also connected here. X08 Screw terminal for connection of cables to the machinery.
CrawfordDoor
X09 Connection for switch Full/reduced opening. X 10= connection for push button or key s witch for hold unit operation.
X0
X1
X2
X1l Connection for push buttons in the lower cover for the three button operation.
X09
X17
X10 X07
X08
X11
May 2006 rev. 3
Page 60 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
9 CONTROL SYSTEM ECS 410/420/430
Approv. Godk.
03-11-28/KHm
May 2006 rev. 3
Gr4005-6.CDR
Page 61 of 95
Group
Service Manual Industrial Doors
10 CONTROL UNIT ECS 430S – CDM 6/5
CHAPTER 4 OPERATORS
Doc.no / Dok.nr
May 2006 rev. 3
Page 61 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors
10 CONTROL UNIT ECS 430S – CDM 6/5
May 2006 rev. 3
Page 62 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 10.1
ECS 430S 2H-CDM6 2H - 400V 400V AC
N07VA5EV-U5G1.5
< 10A 1 2 3
U2 V2 W2
3 4
2 1
4 5 6 1 2
Y2 U2 V2 W2 U1 V1 W1 Y1
1 2 3 4 5 6
A05VV-R7G1.5
W1 V1 U1
Q1 2
FKK 7G1.5
M
Y
1 2 3
EKLK 5G1,5
1 N
L1 L2 L3 N PE 400V 50/60Hz
1
< 10A
X3
5
Q1 0,75 A
N
FKK 3G1.5
3
2
4
6
T1
T2
T3
PE
A05VV-R3G1.5
J1
J1.4
400V J1.2
S4 B1 S1 S2 S3
1 2 3 4 5 6 7 1 2 3 4 5 6
1 2 3 4 5 6 7 1 2 3 4
RKKR 7X0,75 H05VV-K7X0.75
5 6 Coiled cable K012977
1 2 1 2
1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
K1 Up
5
3
1
2
4
6
6
4
2
1
3
5
K2
230V
Down
112 54 53
X1
62 61
74
84
73
83
0V
K1
X3 U2
V2
U2
W2
V2
U1
W2
V1
U1
W1
V1
Y1
Y2
N
W1
Y 400V HIGH
LOW
1 2 20V AC
1 2
1 2
1 2 3
X4 Approv. Godk.
15103462 r2
97-04-15
Gr430S2H.CDR /KHm
Doc.no / Dok.nr
May 2006 rev. 3
Page 62 of 95
Group
CHAPTER 4 OPERATORS
Service Manual Industrial Doors 10.1
ECS 430S 2H-CDM6 2H - 400V 400V AC
N07VA5EV-U5G1.5
< 10A 1 2 3
U2 V2 W2
FKK 7G1.5
4 5 6 1 2
W1 V1 U1
2 1
3 4
Y2 U2 V2 W2 U1 V1 W1 Y1
1 2 3 4 5 6
A05VV-R7G1.5
L1 L2 L3 N PE
Q1 2
M
Y
1 2 3
EKLK 5G1,5
1 N
400V 50/60Hz
1
< 10A
5
Q1
X3
0,75 A
N
FKK 3G1.5
3
2
4
6
T1
T2
T3
PE
A05VV-R3G1.5
J1
J1.4
400V J1.2
1 2 3 4 5 6 7 1 2 3 4 5 6
S4 B1 S1 S2 S3
1 2 3 4 5 6 7 1 2 3 4
RKKR 7X0,75 H05VV-K7X0.75
5 6 Coiled cable K012977
1 2 1 2
1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
K1 Up
5
3
1
2
4
6
6
4
2
1
3
5
K2
230V
Down
112 54 53
X1
62 61
74
84
73
83
0V
K1
X3 U2
V2
U2
W2
V2
U1
W2
V1
U1
W1
V1
Y1
Y2
N
W1
Y 400V HIGH
LOW
1 2 20V AC
1
1 2
2
1 2 3
X4 Approv. Godk.
15103462 r2
97-04-15
May 2006 rev. 3
Doc.no / Dok.nr
Gr430S2H.CDR /KHm
Page 63 of 95
Group
Service Manual Industrial Doors 10.2
CHAPTER 4 OPERATORS
B1 System - ECS 430 S
K032231
A1
Closing timer
Q
1
1 N 1 N U V W
2 3
11 10 9 8 7 6 5 4 3 2 1
1 2
Photoelectric amplifier
3 4
5
6
7
1
7 7 9 2 1 0 K k c a l
B 2
3
1
2
3
4
5
6
7
1
n w o r B
2
C A 0 A 1 V x 0 a 8 3 M
20VAC External powersupply
B 0 1 C / 3 T P S
M R
g n s i n n i t a a M M
Motor unit
p o t S
c i t a m u h c t e i n w P s
B1
12 11 10 9 8 7 6 5 4 3 2 1
S1
2
k n c w a o l r B B
1
One button Open function
1 1 2
3
K034161
F
11 10 9 8 7 6 5 4 3 2 1
X1
1 3 5 1
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 0 1 1 1 1 1 1 1 1 1 1
K032236
0 1 T C / 2 1 D E I
S T
Fotocelloptik Photocell optics n e p O
K1
1 2 4 1 2 4 2 1 1 1 1 2 2 2 A A
May 2006 rev. 3
Page 63 of 95
Group
Service Manual Industrial Doors 10.2
CHAPTER 4 OPERATORS
B1 System - ECS 430 S
K032231
A1
Closing timer
Q
1 1 N 1 N U V W
2 3
11 10 9 8 7 6 5 4 3 2 1
1 2
One button Open function
Photoelectric amplifier
3 4
5
6
7
1
2
k n c w o a r l B B
20VAC External powersupply
7 7 9 2 1 0 K k c a l B 1
2
3
1
2
3
4
5
6
7
1
B 0 1 C / 3 T P S
n w o r B
2
C A A 0 1 V x 0 a 8 3 M
M R
g n s i n n i t a a M M
Motor unit
p o t S
0 1 T C / 2 1 D E I
S T
Fotocelloptik Photocell optics
c i t a m h u t c e i n w P s
n e p O
May 2006 rev. 3
Page 64 of 95
Group
Service Manual Industrial Doors
B1
12 11 10 9 8 7 6 5 4 3 2 1
S1 1
1 2
3
K034161
F
11 10 9 8 7 6 5 4 3 2 1
X1
1 3 5 1
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 0 1 1 1 1 1 1 1 1 1 1
K032236
CHAPTER 4 OPERATORS
11 CONNECTING DIAGRAM ECS 430 P – CDM6/5
X6
K1
1 2 4 1 2 4 2 1 1 1 1 2 2 2 A A
May 2006 rev. 3
Page 64 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
11 CONNECTING DIAGRAM ECS 430 P – CDM6/5
X6
May 2006 rev. 3
Page 65 of 95
Group
Service Manual Industrial Doors 11.1
CHAPTER 4 OPERATORS
Automatic functions ECS 430 P 8 7
6
S2
5 4 3 2 1
ON
S2
OFF 6
1 ON = Flashing red light between limit position s
4 OFF = Open function 4 ON = Eenknops bediening functie
S1 ON
800mAT
6 5 4 3 2 1
N W
V U N
X1 1 2 3 4 5 6 7 8 9 10 11 12 13141516 17 18 19
X2
800mAT
11 1 213 1 4 15 16 17 18
1 2 3 4 5 6 7 8 9
OFF
Indication Hold to run
1
.9
.8 .7
D22
0.63
S1: 1 on Automatic closing off NO automatic closing on Aut. closing time: X2 when safety 2 acknowledge failed (e.g. photocells). :2 after acknowledge off Aut. closing according
S1:1 S1:2 OFF OFF OFF OFF OFF OFF OFF OFF S1:6
ON S1:3 S1:4 S1:5 T1 T2 CLOSING OFF OFF OFF 2 s 3 s 5 s ON OFF OFF 2 s 8 s 10 s OFF ON OFF 12 s 3 s 15 s OFF OFF ON 8 s 12 s 20 s ON ON OFF 12 s 8 s 20 s ON OFF ON 8 s 32 s 40 s OFF ON ON 48 s 12 s 60 s ON ON ON 48 s 32 s 80 s ON The time is counted after "passage of photocell"
May 2006 rev. 3
Page 65 of 95
Group
Service Manual Industrial Doors 11.1
CHAPTER 4 OPERATORS
Automatic functions ECS 430 P 8 7
6
S2
5 4 3 2 1
ON
S2
OFF 6
1 ON = Flashing red light between limit position s
4 OFF = Open function 4 ON = Eenknops bediening functie
S1 ON
800mAT
6 5 4 3 2 1
N W
V U N
X1 1 2 3 4 5 6 7 8 9 10 11 12 13141516 17 18 19
X2
800mAT
11 1 213 1 4 15 16 17 18
1 2 3 4 5 6 7 8 9
OFF
Indication Hold to run
1
.9
.8 .7
D22
0.63
S1:1 S1:2 OFF OFF OFF OFF OFF OFF OFF OFF S1:6
ON S1:3 S1:4 S1:5 T1 T2 CLOSING OFF OFF OFF 2 s 3 s 5 s ON OFF OFF 2 s 8 s 10 s OFF ON OFF 12 s 3 s 15 s OFF OFF ON 8 s 12 s 20 s ON ON OFF 12 s 8 s 20 s ON OFF ON 8 s 32 s 40 s OFF ON ON 48 s 12 s 60 s ON ON ON 48 s 32 s 80 s ON The time is counted after "passage of photocell"
S1: 1 on Automatic closing off NO automatic closing on Aut. closing time: X2 when safety 2 acknowledge failed (e.g. photocells). :2 after acknowledge
3 4 5 6
off Aut. closing according S1 : 3,4,5 of 6. flashing time (see tabel). closing time (see tabel). clos. time / flashing time (see tabel). on Ònly aut. closing after passing safety acknowledge. Always aut. closing after reaching off limitswitch open.
S2: 1 on off on 2 off 3 on off on 4 off 5 on off on 6 off 7 on off on 8 off
Red light flashing between limit switches. No flashing red light. Steady red light at closed door. No steady red light at closed door. Steady green light at door opened. No steady green light at door opened. One button function. Open function. Delayed door movement / flashing light (France). Direct movement (all other countries). "Interlocking" . No function. Option for "Open outside". No function. Option for "Automatic closing" on/off. No function.
Matrix dipswitches 430P / PeRoll EN
May 2006 rev. 3
Page 66 of 95
Group
Service Manual Industrial Doors 11.2 C-kit
C1 C2
CHAPTER 4 OPERATORS
Control system C-kit matrix description Description
Automatic c losing, photocell saf ety and 2 red w arning lights Automatic c losing and C2 photocell safety
In the control unit
SCR-module, Photocell module, DIP-sw itch in the control unit. Photocell module, DIP-sw itc h in the control unit.
C3
Automatic c losing and 2 red warning lig hts
SCR-module, DIP-switch in the control unit.
C4
Automatic c losing
DIP-sw itch in the c ontrol unit.
C5
Photocell saf ety
Photocell module
C6
Magnetic loop
Magnetic loop detector.
C7
Traf f ic light
DIP-sw itch in the control unit.
Mounted externally
Photocell optics, 2 red w arning Iights
Explanation Flashing red lights during all door movement (door betw een limit positions). Flashing red lights before automatic closing. Possible w ith steady red light for c losed door.
Photocell optics.
2 red w arning lights
Flashing red lights during all door movement (door betw een limit positions). Flashing red lights before automatic closing. Possible w ith steady red light for c losed door.
Photocell optics. Magnetic loop kit (40 metre w ire, 2 cable conduit 16,0 metal L750mm, 2 tube bends) SCR-module (external box), 2 red and 2 green signal lig hts.
Traffic light is dir ection sensing.
Cable betw een the doors (3- leaded), not included.
Function is only obtained betw een 2 ECS 430P contr ol units, 2 Peroll control units or 1 ECS 430P and 1 Peroll control unit.
C8
C9
Interlocking
DIP-sw itch in the control unit
C10
Service counter
Counter
One-button / Open function Automatic c losing, photocell saf ety, 2 red w arning lights and one-button / open function Automatic c losing, photocell saf ety and one-button / open function
DIP-switch in the control unit
C11
C12
C13
C16
Automatic c losing, 2 red w arning lights and one-button function Automatic c losing and one- button / open function Photocell safety and one- button / open f unc tion
C17
Automatic c losing and magnetic loop
C14 C15
Counts door cycles
SCR-rnodule, Photocell module, DIP-sw itch in the contr ol unit
Photocell optics, 2 red w arning lights
Photocell module, DIP-sw itch in the control unit
Photocell optics
SCR-module, DIP-sw itch in the control unit
2 red w arning lights
Flashing red lights during all door movement (door betw een limit positions). Flashing red lights before automatic closing. Possible w ith steady red light for closed door
Flashing red lights during all door movement (door betw een limit positions). Flashing red lights before automatic closing. Possible w ith steady red light for closed door
DIP-sw itch in the control unit DIP- sw i tc h in the c ontr ol unit
Magnetic loop detector, DIP-sw itch in the contr ol unit
Photoc ell optic s Magnetic loop kit (40 metre w ire, 2 cable conduit 16,0 metal L750mm, 2 tube bends)
C18
C19
C20
C21
Automatic c losing, photocell saf ety, 2 red w arning lights and magnetic loop
SCR-module, Photocell module, DIP-sw itch in the contr ol unit Magnetic loop detector
Automatic c losing, photocell saf ety and magnetic loop Automatic c losing, photocell saf ety and traff ic lights
Photocell module, DIP-sw itch in the contr ol unit Magnetic loop detector Photocell module, DIP-sw itch in the contr ol unit
Photocell optics, 2 red w arning lights, Magnetic loop kit (40 metre w ire, 2 cable conduit 16,0 metal L750mm, 2 tube bends) Photocell optics, 2 red w arning lights, Magnetic loop kit (40 metre w ire, 2 cable conduit 16,0 metal L750mm, 2 tube bends) Photocell optics, SCR-module (extemal box), 2 r ed an d 2 gr ee n s ig na l lig ht s
Flashing red lights during all door movement (door betw een limit positions). Flashing red lights before automatic closing. Possible w ith steady red light for closed door.
Tr af f ic lig ht is d ir ec tio n s en sin g.
May 2006 rev. 3
Page 67 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
12 DIAGRAM CDM 9 23
5 5
Brown
6
*) 15
Blue
M
230VAC / 10A
24
16
14 9 8 7
1
1
1
2
2
6 5 4
3
3
4
4
5
5
3 2 1
6
6
7
7
23
1
2
2
3
3
4
8 9
SW1 On =
SW2 On =
12
40 12
installationmode installationsläge
force adj. mode kraftinst.l äge
X2
1 5
X3
1 2 3 4 5 6 7 8 9
5 4 3 2 1
X8 1
1
4
2
Diode
1 2 1 3 1 4
(The installers documentation)
PCB ControlBox / Kontrollenhet 930A
29
1 0 1 1
18
X4
13
X1 9
4
Basic Wiring Diagram
3 2 1 2 1
8
1 2 3
1
X5 X6
2
2
3
1
4
2
5
1
6
7
2
1
8
9
2
1
10 11 12 13 14 15
2
1
2
1
2
1 2 3 4
18
Coiled cable
P
4
23
15
39
10
41
42
43
44
May 2006 rev. 3
Page 68 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
10 25 17 18 1 9 2 0
Yellow Shield
S1
Photocell kit SINGLE
1
2 3
4 5
6 7 8
FR-varningsljus
One-button function
8
24V AC
1
1-knappsfunktion
WarninglightsRED
S2
9 10 11
C-Board/ Kort
PCB
Fotocellsats ENKEL
31
1
J4
1 2 3 4 5 6 7
24
Blue Blå
n
receiver 27 25
10
Fotocellsats DUBBEL
7
Open function
Öppnafunktion
Red
IED 12
1
17 18 1 9 2 0
Upp - stopp - nerfunktion
Yellow
SPT 3
Shield
S1
1
2 3
6 7 8
Yellow Gul 230V
18
Shield
nc
t1
S1
5
22 21
*)
J1 1 2
3
5
1 2 3 4 5
Varningsljus GRÖNT
32
1 2 3 4 18 23
1
2 3
2 3
4 2
8 9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 2
3
5
X3 29
1 2 3 4 5
Förregling, reläsats
X6
X15
LSC
H1
N
SW1
13
Diode
12
SW2
13
Diode
X8
1
Traffic lights 48
Trafikljus
X4
X5
1 2
1 2 3
X11
X14 1 2
31
1 2
35
15
1
7 5
*)
5
*)
230VAC Max 10A
230VAC Max 16A
< 10A
< 10A
2
1
3
38
Coiled cable
P
Basic Wiring Diagram 44
2
with ADDITIONALS
1
3
RED
RÖD H1
H1
GREEN
GRÖN
H2
H2
Inside
Outside
Inne
43
1
2
H2
43 8 7 9
37
42
5
< 10A
36
41
*) 230VAC Max 10A
1 2 2 1
34
3
23
5
1 2 3 4
34
8
16
X12
N N N L1
H1
6
4
1 2 3 4
35 1 2 24V AC
1 2 33
14
X11
X12
N N N L1
N 3
56
10
1
40
On = force adj.mode kraftinst.Läge
On =installationmode installationsläge
1 2 1 2 1 2 1 2 1 2 1 2
39
1 2 3 4
H2
X13
Slinga
15
X12
N N N L1
24VAC 300 mA
X1
1 2
4
2
Int.lock
SC-Relay
31
ControlBox A / Kontrollenhet A
1 2 3 4 5 6 7 8 9 10 1 1 1 2 1 3 1 4 1 5
4
18
1
7 8 9
X2
PCB
31
Interlocking, relay kit
J4
7 8 9
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7
47
51
Warninglights
X11
9 8 7 6 5 4 3 2 1
2
H2
230VAC / 10A
1 2
1
< 10A
< 10A
C-Board/ J6 Kort
LSO
1
*) 230VAC Max 10A
30
Blue
1
5
2 1
*)
S2
24
27
230VAC Max 10A
X9
M
1
17
400V
t2
5 5
1
LV
H1
28
23
N
1 2 3 4
d d k w w d e e c o o l a l R R l e l l l i B e e h Y Y S
Yellow
Brown
Red Röd
46
Black SPT 3
L1
X12
N N N L1
45
Black Svart
2 1
9 10 11 12
Red
IED 12
2
4 5
17
0V
21 Antennkabel
24V AC
1
F10 T2AH
N
Black
X11
2
SC-relay HR-relä
24V
19
1 L 1 N 1 X N
Up - stop - down function
8
Photocell kit DOUBLE
Red Röd
PCB HR-Relay 930A
5
2 1
0V
3
50
Varningsljus RÖTT
J6
30
X8
d k w o l c l e d a i e l l e h R B y S
1 2
49
FR-warning lights
21 Antennkabel
receiver
Black
SPT 3
26
7
Red
IED 12
Ute
May 2006 rev. 3
Page 68 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
10 25 17 18 1 9 2 0
Yellow Shield
S1
Photocell kit SINGLE
1
2 3
4 5
6 7 8
FR-varningsljus
One-button function
8
24V AC
1
1-knappsfunktion
WarninglightsRED
S2
9 10 11
C-Board/ Kort
PCB
Fotocellsats ENKEL
31
30
X8
d k w o l c l e d a i e l l e h R B y S
1
J4
1 2 3 4 5 6 7
24
Blue Blå
1 2
3
5
receiver 10
Fotocellsats DUBBEL
Upp - stopp - nerfunktion
7
Open function
Öppnafunktion
Red
IED 12
1
17 18 1 9 2 0
Yellow
SPT 3
Shield
S1
1
2 3
6 7 8
Yellow Gul 230V
18
Shield
nc
t1
S1
5
*)
J1 1 2
3
5
1 2 3 4 5
Varningsljus GRÖNT
1 2 3 4 18 23
1
2 3
2 3
4 2
8 9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 2
3
5
1 2 3 4 5
X3
X2
29
PCB
Förregling, reläsats
1
X6
X15
LSC
Int.lock
X12
N N N L1
N
1 2 3 4
1
1
H2
X13
Traffic lights
SC-Relay
31
ControlBox A / Kontrollenhet A
48
Trafikljus
31
24VAC 300 mA
X1
SW1
13
Diode
12
SW2
13
Diode
40
X8
X4
X5
1 2
1 2 3
X11
X14 1 2
On = force adj.mode kraftinst.Läge
On =installationmode installationsläge
1 2
35
15
1
*) 5
230VAC Max 10A
1 2 2 1
1
2
< 10A
34 H2
34
43 8 7 9 7
6
5
3 4
5
1 2 3 4
H1
8
16
X12
N N N L1
35 1 2 24V AC
1 2 33
14
1 2 3 4
N 3
56 1 2 1 2 1 2 1 2 1 2 1 2
X11
X12
N N N L1
Slinga
1 2
*)
5
*)
230VAC Max 10A
230VAC Max 16A
< 10A
< 10A
2
1
3
2
36
38
3 H1
GREEN
GRÖN
H2
H2
Inside
Outside
Inne
Coiled cable
1
RED
RÖD H1
37
18
2 H1
7 8 9
1 2 3 4 5 6 7 8 9 10 1 1 1 2 1 3 1 4 1 5
4
31
Interlocking, relay kit
J4
7 8 9
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7
47
51
Warninglights
32
X11
9 8 7 6 5 4 3 2 1
2
H2
230VAC / 10A
1 2
1
< 10A
< 10A
C-Board/ J6 Kort
LSO
1
*) 230VAC Max 10A
30
22 21
Blue
1
5
2 1
*)
S2
5 5
27
230VAC Max 10A
X9
24
1
17
400V
t2
M
1
LV
H1
28
23
N
1 2 3 4
d d k w w d e e c o o l a l R R l l l l i e B e e h Y Y S
Yellow
Brown
Red Röd
46
Black SPT 3
L1
X12
N N N L1
45
Black Svart
2 1
9 10 11 12
Red
IED 12
2
4 5
17
0V
21 Antennkabel
24V AC
1
F10 T2AH
N
Black
X11
2
SC-relay HR-relä
24V
19
1 L 1 N 1 X N
Up - stop - down function
8
Photocell kit DOUBLE
Red Röd
PCB HR-Relay 930A
2 1
0V
27
50
Varningsljus RÖTT
J6
n
25
49
FR-warning lights
21 Antennkabel
receiver
Black
SPT 3
26
7
Red
IED 12
Ute
P
4
Basic Wiring Diagram
23
15
39
10
41
42
43
44
with ADDITIONALS
May 2006 rev. 3
Page 69 of 95
Group
Service Manual Industrial Doors 12.1
CHAPTER 4 OPERATORS
Control system D-kit matrix description
There are 7 base automation kits, the D-systems: Kit
Description / content
part.no.
D1 D2 D3 D4 D5 D6 D7
Including D7 + red lights Including D7 + magnetic loop PCB SCR D3 is always a part of D5 or D6 Including D7 + 2 red lights + magnetic loop Including D3 + 2 red lights + 2 green lights (traffic lights system) Including D3 + 2 red lights + 2 green lights (traffic lights system) + magnetic loop the minimal kit: Interlocking 2 doors
K043512 K043510 K043508 K043506 K043504 K043502 K043445
May 2006 rev. 3
Page 69 of 95
Group
Service Manual Industrial Doors 12.1
CHAPTER 4 OPERATORS
Control system D-kit matrix description
There are 7 base automation kits, the D-systems: Kit
Description / content
part.no.
D1 D2 D3 D4 D5 D6 D7
Including D7 + red lights Including D7 + magnetic loop PCB SCR D3 is always a part of D5 or D6 Including D7 + 2 red lights + magnetic loop Including D3 + 2 red lights + 2 green lights (traffic lights system) Including D3 + 2 red lights + 2 green lights (traffic lights system) + magnetic loop the minimal kit: Interlocking 2 doors
K043512 K043510 K043508 K043506 K043504 K043502 K043445
D1
D2
D5
D6
D3
The visual difference between D3 and D7 is 1 SCR relay on D7 and 4 SCR relays on D3 (for Red and Green lights (see arrows).
Also a separate print Indication "Door open" (K043446) is available for the ECS 930A control unit: This PCB card can be used for e.g. interlocking a leveler.
D4
D7
May 2006 rev. 3
Page 70 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
13 RADIO EQUIPMENT
Radio equipment 40 MHz
Radio equipment 433 MHz
May 2006 rev. 3
Page 71 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
Radio equipment 869 MHz
May 2006 rev. 3
Page 72 of 95
Group
Service Manual Industrial Doors 13.1
CHAPTER 4 OPERATORS
Radio equipment 40 MHz
The 40 MHz equipment is not available as Spare Part any more. These items have become obsolete.
May 2006 rev. 3
Page 73 of 95
Group
Service Manual Industrial Doors 13.2
CHAPTER 4 OPERATORS
Radio equipment 433 MHz
The 433 MHz equipment is not available as Spare Parts any more. All 433 MHz equipment is replaced by the 433-MHz PLUS range. Both systems are compatible. For programming new equipment on existing installations see next paragraphs.
May 2006 rev. 3
Page 74 of 95
Group
Service Manual Industrial Doors 13.3
CHAPTER 4 OPERATORS
Radio equipment 433 MHz PLUS
About the transmitter Shortcut for a door (433-999 ) The * and # buttons are used to program a shortcut (1
selection per button) for a specific door. If you hold down the * or # button when a number is shown on the display for more than three seconds (display flashes) this saves the number as the shortcut.
Switch
The transmitter must be taken apart to access the system switch (A) and code switches (B) so that these can be set. The switches are located as shown in the diagram. Battery replacement
The transmitter must be taken apart to access the battery. Note that on transmitters with button batteries the plus character should (+) face the plus character marked on the battery holder.
K045625 , Battery 3V K047196,
available)
Battery
for
mini transmitter. (SP) −
(No
picture
May 2006 rev. 3
Page 75 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
About the Receiver
Receiver 433 MHz PLUS Frequency Operating voltage Dimensions Enclosure
: 433MHz : 12/24DC : 86 x 30 x 58 mm : IP 23, for internal installation. K039101, Receiver 433 Plus
Green LED indicates signal reception
Button for selfteach function
12/24 VDC 12/24 VDC C NO
C NC C NO
Red LED indicates programming status
Yellow LED indicates supply voltage
May 2006 rev. 3
Page 76 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
Register a standard code •
•
•
•
Press the self-teach button for at least 300 milliseconds, longest 4 seconds. Release the button Programming mode, red LED comes on Enter the door number, followed by an optional function button (With just the one-button function only the door number, with just up-stop-down function only the function key) Red LED flashes The standard code has now been stored Red LED flashes
Register a private code (= Standard and unique codes) •
Press the self-teach button for at least 300 milliseconds, longest 4 seconds
•
Press the button (longer than 1 second )
•
Private program mode, the red LED comes on
•
•
Enter the door number, followed by an optional function button (With just the one-button function only the door number, with just up-stop-down function only the function key) Red LED flashes The private code has now been stored Red LED double flashes
Erase the programmed codes •
Press the self-teach button for more than 6 seconds. (Red LED goes out)
•
All programmed codes are erased.
May 2006 rev. 3
Page 77 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
To ensure that the remote control system has a long lasting and reliable operation it is very important that the receiver and antenna are mounted correctly. Correctly installed equipment will provide better range and longer lifetime for the system. It will be worthwhile spending a few minutes reading through these instructions.
433-DP Duopole aerial
K041765 , Arial,duopole 433MHz
K045646, T conn.for radio 433 MHz Plus −
K039114, Wire, f.aerial 10 m
May 2006 rev. 3
Page 78 of 95
Group
Service Manual Industrial Doors 13.4
CHAPTER 4 OPERATORS
Programming the transmitters
433-1 433-3 433-999
PLUS (K045613) PLUS (K045614) PLUS (K045619)
The transmitter and receiver are coded together so that they then have a common code. Program as follows: •
•
•
•
Check that the transmitter’s system switch (A) is in the ON position. Set an own code on the transmitter’s code switches (B) 110. Press the self-teach button (C) on the receiver. The red LED comes on (programming mode 6 seconds) Press the required door number button (1-15) on the transmitter.
Check that the relay switches when one of the transmitter’s buttons is pressed in.
May 2006 rev. 3
Page 79 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
Programming the transmitters:
433-01 433-06 433-015
PLUS (K045612) PLUS (K045615) PLUS (K045618)
The transmitter and receiver are coded together so that they then have a common code. Program as follows: •
•
•
•
Check that the transmitter’s system switch (A) is in the ON position. Set an own code on the transmitter’s code switches (B) 110. Press the self-teach button (C) on the receiver. The red LED comes on (programming mode 6 seconds) Press the required door number button (1-999) and an optional function button (up-stop-down) on the transmitter (approx. 3 seconds).
Check that the relay switches when one of the transmitter’s buttons is pressed in.
May 2006 rev. 3
Page 80 of 95
Group
Service Manual Industrial Doors 13.5
CHAPTER 4 OPERATORS
Supplementing old 433 MHz installations 1.
Programming the transmitter 433-999 PLUS to an “old” 433receiver and a 433-93 (type truck transmitter) in the existing installation. •
•
•
•
Set the transmitter’s system switch (A) in the 1 position. (off) Check that the code switch (B) 9 is in the + (plus) position. Set an identical code on the transmitter’s three first switched (code switches 1-3) as set on the receiver. (The transmitter’s code switches 4-8 and 10 are not used). Check that the relay switches when one of the transmitter’s button is pressed.
433-999
May 2006 rev. 3
Page 81 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
13.6 Supplementing old 433 MHz installations 2.
Programming the PLUS transmitter 433-1, 433-01 and 433-06 to an “old” 433-receiver and small 433transmitters) in the existing installation. (Not Robust). •
•
o
•
Set the transmitter’s system switch (A) in the 1 position. (off)
433-01
For 433-1 or 433-01 transmitters proceed as follows:
Set an identical code on the transmitter’s code switches (B) 1-4) as set on the existing receiver. Set the code switch 10 to the minus position (5-9 are not used). For 433-06 transmitter proceed as follows:
Set an identical code on the transmitter’s code switches (B) 1-4, as set on the existing receiver. Set the code switch 10 to the minus position (5-9 are not used). o
•
Check that the relay switches when one of the transmitter’s button is pressed.
433-03
433-06
May 2006 rev. 3
Page 82 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
13.7 Supplementing old 433 MHz installations 3.
Programming the PLUS transmitter 433-1, 433-01 and 433-06 to an “old” 433-receiver and robust transmitters.
•
•
•
•
•
•
Set the transmitter’s system switch (A) in the 1 position. (off)
433-01
For 433-1 or 433-01 transmitters proceed as follows:
Set an identical code on the transmitter’s code switches (B) 1-8) as set on the existing receiver. (9-10 are not used). For 433-3 and 433-06 transmitter proceed as follows:
Set an identical code on the transmitter’s code switches (B) 1-4, as set on the existing receiver. (9 is not used) Set the code switch 10 to the minus or plus position depending on the code table used on the other Robust transmitters being used
433-03
433-06
May 2006 rev. 3
Page 83 of 95
Group
Service Manual Industrial Doors 13.8
CHAPTER 4 OPERATORS
Coding tables
Setting the code on the receiver to operate with the”old” 433-06 / 433-10 transmitter switches 1-4 should have the same setting on both the transmitter and receiver. Table for 10 Doors
Plus (+) code
Minus (-) code
May 2006 rev. 3
Page 84 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
Setting the code on the receiver to operate with the “old” 43393 transmitter
Note that the positions A0=D0, B0=E0, C0=F0 Switches 1-3 should have the same settings on both the transmitter and receiver. Table for 93 Doors
May 2006 rev. 3
Page 85 of 95
Group
Service Manual Industrial Doors 13.9 • • • • •
• • •
CHAPTER 4 OPERATORS
Radio equipment 869 MHz
New ergonomic design - with high quality Easy to install - easy programming Safe with secure data transmission Each transmitter is supplied with a unique code The receiver can manage 100 unique codes (AGM: 500 unique codes) The receiver is programmed via the handheld transmitter Possibility to operate up to 999 doors Robust
Battery replacement
The transmitter must be taken apart to access the battery. Note that on transmitters with button batteries the plus character should (+) face the plus character marked on the battery holder. About the transmitter Shortcut for a door (869-999 ) The * and # buttons are used to program a shortcut (1 selection
per button) for a specific door. If you hold down the * or # button when a number is shown on the display for more than three Seconds (display fl ashes) this saves the number as the shortcut.
May 2006 rev. 3
Page 86 of 95
Group
Service Manual Industrial Doors 13.10 Transmitters in the 869MHz program Transmitter 869-1 K047181
with function buttons Up - Stop - Down. Transmitter 869-3 K047182
with function buttons Up - Stop - Down. For 3 doors. Transmitter 869-O1 K047180
with One button function. For 1 door. Transmitter 869-O6 K047183
with One button function. For 6 doors. Transmitter 869-O15 K047184
with One button function. For 15 doors.
Transmitter 869-999 K047185
with function buttons Up - Stop - Down. For up to 999 doors.
For latest info see Spare Parts Catalogue
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 87 of 95
Group
Service Manual Industrial Doors 13.11 Receivers in the 869MHz program DIN Receiver 869
Up to 100 unique codes (transmitters)
Frequency: Operating voltage: Dimensions: Enclosure: installation
869 MHz 12/24V AC/DC 86 x 30 x 58 mm IP 23, for internal
WR Receiver 869
Frequency: 869 MHz Operating voltage: 12/24V AC/DC Dimensions: 120 x 103 x 44 mm Enclosure: IP 65, for external installation
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 88 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
WR Receiver 869
Button for self teach function (A)
Green LED indicates signal reception
Yellow LED indicates supply voltage
WR 869 / AGM WR 869
Red LED shows the programming status
May 2006 rev. 3
Page 89 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
AGM WR Receiver 869 • • • • •
Frequency: 869 MHz Operating voltage: 12/24V AC/DC Dimensions: 120 x 103 x 44 mm Enclosure: IP 65, for external installation AGM WR Receiver 869 is used together with an Onebutton transmitter and/or with a transmitter with Up-StopDown functions.
Programming the AGM WR Receiver
The receiver can be programmed to accept up to 500 different transmitters, where each transmitter has its own unique IDcode. It is recommended to keep a log of transmitter serial numbers that have been programmed into the receiver and on which position. It could also be useful to log which user has access to which transmitter. For programming the ID codes see document K046727, RADIO 869MHz Installation & Programming
May 2006 rev. 3
Page 90 of 95
Group
Service Manual Industrial Doors
14 MAGNETIC LOOP SYSTEM
CHAPTER 4 OPERATORS
May 2006 rev. 3
Page 91 of 95
Group
Service Manual Industrial Doors 14.1
CHAPTER 4 OPERATORS
Magnetic loop – connection diagram Position
0 1 2 3 4 5 6 7 8 9 101112131415
Sensitivity 0,5,15,05,020,5,15 ,05 ,02 0,5,15 ,05 ,02 0,5,15 ,05 ,02 Presence 5 min 120 min 5 min 120 min Frequency High Low SWITCH SETTINGS INSTRUCTIONS 1) Select required switch position Fault Flash Rate High sens. = ,02 Open Circuit Loop 1 Hz Low sens. = 0,5 Short Circuit Loop or faulty oscillator 2 Hz 2) On application of LED FAULT INDICATION power detector will retune in < 2 sec Presence 3) Observe detection of vehicles on LED Loop Pulse Safety Earth Supply
1
11
CONNECTIONS - Viewed from base
Mode switch position Frequency mode:
HIGH
Presence time (minutes): Low med. Low Sensitivity: med. High High
5 0 1 2 3
120 4 5 6 7
SOCKET CONNECTION Loop n e e r G
Blue Presencerelay
Yellow Grey
Pulserelay Line
Or ange Black Red
5
6
7
4
8
3
9 10
2 1
11
White
n w o r B
n e e r G / w o l l e Y
LOW 5 8 9 10 11
120 12 13 14 15
May 2006 rev. 3
Page 92 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
15 REDUCED OPENING – ECS 430 P – CDM 5 Disengage
X1:
n>
1
2
S1
3
S2
4
S3
5
24 VAC
n.c.
n.o.
c
c
n.c.
n.o.
n.o.
n.c.
c
S1
S2
X4:1
S3
1
reduced door opening CDM 5 reduzierter Toröffnung CDM 5 1/2 deur opening CDM 5
1/2
X4:2
4
1
3
2
6
7
May 2006 rev. 3
Page 93 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
16 REDUCED OPENING ECS 430P – CDM6 X1
2 : 4 X
1 2 3 4 5 6 7
1 2 3 N W V
5
) a 5 2 (
1 : 3 : 4 4 X X
) 6 2 (
4 6
) 4 2 ( 4
1
7
) 5 2 (
U N
3
2
(25b) O
I
K-33282
ABS
Voor gemonteerd
1
2
3
2 5 a
2 5 a 1
1
4
2
O N 3
N C
2
3
2 5
2 5 2 4 2 5 b
2 4
2 5 b 2 6
2 6
½
1
PS1
ECS 430P
«
1
X1
2 : 4 X
1 2 3 4 5 6 7
½
1
1 2 3
5
) a 5 2 (
1 : 3 : 4 4 X X
4 6
) 6 2 (
) 4 2 (
1
7 ) ) 6 4 4 4 ( (
) 5 2 (
4 3
2
(25b)
s
Additionalsystem
ECS 400 CDM-6 (P) Reduced Door travel
May 2006 rev. 3
Page 94 of 95
Group
Service Manual Industrial Doors
CHAPTER 4 OPERATORS
17 REDUCED OPENING – ECS 930A / 940A* – CDM 9 *) the ECS 940A for the 855 does not have reduced door travel
Installing the reduced door travel (K043434) (reduced door opening) on an ECS 930A:
Dip Switch S2:2 (in the LID of the ECS 930A) is used
to set the position for reduced opening. •
•
•
Put the door in the wanted position. Turn the DIP Switch S2:2 switch ON and directly OFF to store the position in memory. Change-over switch in the lid for fully open and reduced position.
(SP )K0 435 75 K- 43501.2
3 X L
1
P O 2 T S
X4
SW2 D6 ON
1 P U 2 N W 3 O D
X5
2 X R E V I E C E R
C O R P . C
X6
L E C O T O H P
4
5 1
3
4 1
2
3 1
1
2 1 1 1
9 8 7 6 5
D5 D4 D3 SW1 N O
4 3 2 1
0 1 9 8 7 6 5 4 3 2
X1
1
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15
8 X
reduced door opening open outside open inside interlocking extra safety one button open function