DOC. NO: ACV/TEVA/DQ-01
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 1 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN TABLE OF CONTENTS CONTENTS:: SR. NO.
DESCRIPTION
PAGE NO.
Table of Contents
1
1.0
Design Qualification Protocol Approval
2
2.0
Objective
3
3.0
Scope
3
4.0
Responsibilities
3
5.0
Pre-Requisites
3
6.0
References
4
7.0
Equipment / System Description
8.0
Basis of Equipment / System Design
9.0
Design Data (Detailed Specifications for Major Components)
10.0
Documentation
12
11.0
Post Construction Review (For any kind of deviation, if any) & Discussions
13
12.0
Design Qualification Summary and Conclusion
13
13.0
Design Qualification Approval
14
14.0
Abbreviations
15
Enclosure - 1
Bill Of Quantity
16
Enclosure - 2
G.A. Drawing of AHU & Duct Layout Drawing
17
0
Enclosure – 3 Enclosure - 4
Room Data Sheet Technical Specifications
4 - 10 11 11-12
18 19
DOC. NO: ACV/TEVA/DQ-01
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 2 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN
1.0
DESIGN QUALIFICATION PROTOCOL APPROVAL
PREPARED BY: NAME
DESIGNATION
ORGANISATION
MR. Rahul. AGGARWAL
TECHNICAL DIRECTOR
ACV SYSTEMS PVT. LTD.
SIGNATURE
DATE
SIGNATURE
DATE
SIGNATURE
DATE
APPROVED BY: NAME
DESIGNATION
ORGANISATION TEVA API INDIA LIMITED
CHECKED BY: NAME
DESIGNATION
ORGANISATION TEVA API INDIA LIMITED
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 3 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN
2.0
3.0
OBJECTIVE (a)
To prepare detailed specifications (design data) for HVAC System and its major components, to ensure that the User Requirement Specifications, as described in URS are achieved.
(b)
To design the system in conjunction with the design data in order to provide basis for the vendor & manufacturers to design and fabricate the system (equipment & component) to meet design intent.
SCOPE Applicable to the HVAC System for TEVA API INDIA LIMITED at Gwalior, Malanpur. Data sheet for the subjected equipment and its major components is defined by the engineering department in consultation with the User department, which is finalized and mutually discussed with the system supplier, ACV Systems Pvt. Ltd. The design qualification is a basic document for the subsequent Validation activity.
4.0
RESPONSIBILITIES
4.1
ACV SYSTEMS PVT. LTD.:
Preparation of the DQ Protocol in consultation with the User. Collection of Data & preparation of final design. Execution of the protocol and preparation of DQ Summary Report.
4.2
TEVA API INDIA LIMITED
Checking the protocol for accuracy and adequacy prior to the approval. Review and approval of the protocol. Review and approval of the design qualification report.
5.0
PRE-REQUISITES Prior to the preparation of the Design Qualification Protocol following conditions is fulfilled:
Approval of user Requirement Specification to the HVAC System URS
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 4 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN
6.0
REFERENCE Following documents have been referred in preparation of this protocol: Validation Master Plan Document # VMP/MF/06001 ASHRAE Standards
7.0
EQUIPMENT / SYSTEM DESCRIPTION The subjected HVAC System is designed for MPP BUILDING. The HVAC System is designed in such a way to: Minimize or eliminate the potential sources of airborne contamination. Provide desired environment conditions w.r.t. Temperature, Relative Humidity, Pressure Differentials etc.
The entire Plant has been divided into different Hygiene Class / Level as per WHO cGMP Regulatory requirements & ISPE Baseline Pharmaceutical Guidelines for MPP Building. The HVAC System consists of 3 Set Air Handling Unit – (AHU-1, AHU-4 & AHU-5), 2 Set Air Washer – (AW-1 & AW-3) 6 Set Exhaust Fan - (EX FAN – 1, EX FAN – 2 & EX FAN – 3) The major division of AHU Systems is as tabulated below:
7.1
TABLE:
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010 Page 5 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN SYSTEM NUMBER
CATERED AREAS Ground Floor for Change Room, Air Lock, Centrifugal Material/PAL, Blender Room Sifter Mill, Clean Corridor, RVD Room, Wash Room, Storage, Packing & Quarantine Room Ground Floor for Change Room, Air Lock, Centrifugal Material/PAL, Blender Room Sifter Mill, Clean Corridor, RVD Room, Wash Room, Storage, Packing & Quarantine Room Ground Floor, First Floor & Second Floor for Reception, Workers C/R, Visitor C/R, Tea Room, Lobby, Dispensing Room, MAL, Air Lock, Material entry, Lobby, Material Store, IPQC, Office, Lobby, Storage & Material Store
HYGIENE CLASS/ LEVEL
AHU – 1
AHU – 1
AHU – 4
AHU – 5 AW – 1 AW – 3 Exhaust Fan – 1 Exhaust Fan – 2 Exhaust Fan – 3
10,0000
Unclassified
Ground Floor For RVD
Unclassified
Ground Floor For Hall (Reactors Area), Centrifuge, Centrifuge, Wash & AFND
Unclassified
Second Floor For Reactors Area
Unclassified
10,0000
First Floor For Reactors Area
Second Floor For Reactors Area
Third Floor For Reactors Area
The Air Handling Unit (AHU) is a closed type box construction, which filters, cools/ heats & supplies the air to the conditioned space. Air Handling Systems is described below;
7.2
Air Handling System (AHU-1)
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
March 8, 2010 Page 6 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN
This Air Handling System is a “ once thru” system, which supplies the conditioned air.
AHU System consists of following components:
7.2.1
AHU-1(Supply 12500 CFM) 1. 2. 3. 4. 5. 6. 7.
8. 9. 7.2.2
Pre-Filters of (EU-4) 10 μ in Size – 610 x 610 x 50 mm = 6 Nos. 610 x 305 x 50 mm = 2 Nos. 8 Row Deep Cooling Coil. 2 Row Deep Hot water Coil. Blower Section with DIDW backward curved blower. Supply Air Blower with Motor 18.5 KW / 4 Pole Fine-Filters of (EU-7) 1 μ in Size – 610 x 610 x 305 mm = 6 Nos. 610 x 305 x 305 mm = 2 Nos. Semi-HEPA Filters (EU-9) of 1 μ in Size – 610 x 610 x 305 mm = 6 Nos. 610 x 305 x 305 mm = 2 Nos. Exhaust Air Blower with motor 15.0 KW / 4 Pole Bag filter of (EU-5) 5 μ Size – 610 x 610 x 360 mm = 6 Nos.
The Other Components of the System are as follows: 1. Temperature and relative humidity sensor with DDC Controller for controlling temperature and RH. 2. Velocity sensor with DDC Controller for controlling a supply air speed of blower. 3. DP sensor for controlling pressure.
7.2.3
False ceiling mounted HEPA filter box with perforated SS Sheet
7.2.4
G.I. Return Grill with perforated Aluminum Grill. For above refer AHU Drawing No. FL-9076-1B enclosed
7.3
Air Handling System (AHU-4) This Air Handling System is a “re -circulation” system, which supplies the conditioned air.
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010 Page 7 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN AHU System consists of following components: 7.3.1
AHU-4( 5500 CFM) 1. 2. 3. 4. 5. 6.
7.3.2
Pre-Filters of (EU-4) 10 μ in Size – 610 x 610 x 50 mm = 2 Nos. 305 x 610 x 50 mm = 2 Nos. 8 Row Deep Cooling Coil. 2 Row Deep Hot Water Coil. Blower Section with DIDW backward curved blower. Supply Air Blower with Motor 5.5 KW / 4 Pole Fine-Filters of (EU-7) 1 μ in Size – 610 x 610 x 305 mm = 2 Nos. 305 x 610 x 305 mm = 2 Nos.
The Other Components of the System are as follows: 1. Humidistat and Thermostat for controlling the temperature & humidity.
7.3.3
Supply Air Diffuser mounted with false ceiling
7.3.4
Return Air Diffuser mounted with false ceiling. For above refer AHU Drawing No. FL-9076-3C enclosed
7.4.1
Air Handling System (AHU-5) This Air Handling System is a ” once thru” system, which supplies the conditioned air.
AHU System consists of following components: 7.4.1
AHU-5 (1850 CFM) 1. 2. 3. 4. 5. 6.
Pre-Filters of (EU-4) 10 μ in Size – 610 x 610 x 50 mm = 1 No. 8 Row Deep Cooling Coil. 2 Row Deep Hot Water Coil. Blower Section with DIDW backward curved blower. Supply Air Blower with Motor 2.2 KW / 2 Pole Fine-Filters of (EU-7) 1 μ in Size – 610 x 610 x 305 mm = 1 No.
7.4.2 The Other Components of the System are as follows: -
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 8 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN 1. Humidistat and Thermostat for controlling the temperature & humidity.
7.4.3
Supply Air Diffuser mounted with false ceiling .
7.4.4
Return Air Diffuser mounted with false ceiling. For above refer AHU Drawing No. – FL-9076-2C
7.5
Air Washer (AW – 1) This Air washer system having a capacity of 40000 CFM, which supplies the Cooled Filtered air. AW – 1 System consists of following components:
7.5.1
AW – 1 (40000 CFM) 1.
2. 3.
4.
Pre-Filter of (EU-4) 10 μ of Size – 610 x 610 x 50 mm = 18 Nos. 305 x 610 x 50 mm = 6 Nos. 610 x 305 x 50 mm = 3 Nos. 305 x 305 x 50 mm = 1 No. Supply Air Blower with Motor (2 Nos.) - 15.0 KW / 4 Pole Fine Filter of (EU-) 7 μ of Size – 610 x 610 x 305 mm = 18 Nos. 305 x 610 x 305 mm = 6 nos. 610 x 305 x 305 mm = 3 Nos. 305 x 305 x 305 mm = 1 No. Fan Pulley, Motor Pulley, Cell deck Pad, Belt & Pump
7.5.2
Aluminum Powder Coated Supply Air Grille.
7.5.3
Return Air Grill For above refer Drawing No. – FL-9076-7B enclosed
7.6
Air Washer (AW – 3) This Air washer system having a capacity of 36000 CFM, which supplies the Cooled Filtered air. AW – 3 System consists of following components:
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 9 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN 7.6.1
AW – 3 (36000 CFM) 1. 2. 3. 4.
Pre-Filter of (EU-4) 10 μ of Size – 610 x 610 x 50 mm = 18 Nos. 305 x 610 x 50 mm = 6 Nos. Supply Air Blower with Motor (2 Nos.) - 11.0 KW / 4 Pole Fine Filter of (EU-) 7 μ of Size – 610 x 610 x 305 mm = 18 Nos. 305 x 610 x 305 mm = 6 nos. Fan Pulley, Motor Pulley, Cell deck Pad, Belt & Pump
7.6.2
Aluminum Powder Coated Supply Air Grille.
7.6.3
Return Air Grill For above refer Drawing No. – FL-9076-8B enclosed
7.6
Exhaust Fan – 1 This Exhaust Fan system having a capacity of 10000 CFM (2 Nos.), which Exhuast the Return air. Exhaust Fan – 1 System consists of following components:
7.6.1
Exhaust Fan – 1 ( 10000 CFM) 1. 2. 3. 4.
7.6.2
Pre-Filter of (EU-4) 10 μ of Size – 610 x 610 x 50 mm = 8 Nos. 610 x 305 x 50 mm = 4 Nos. Supply Air Blower with Motor (2 Nos.) – 3.7 KW / 4 Pole Centrifugal DIDW forward curved Blower Fan Pulley, Motor Pulley, & Belt
Return Air Grill with Exhaust Air Blower For above refer Drawing No. – FL-9076-8B enclosed as Enclosure
7.7
Exhaust Fan – 2 This Exhaust Fan system having a capacity of 9000 CFM (2 Nos.), which Exhaust the return air. Exhaust Fan – 2 System consists of following components:
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
March 8, 2010 Page 10 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN 7.7.1
Exhaust Fan – 2 ( 9000 CFM)
2. 3.
7.7.2
1. Pre-Filter of (EU-4) 10 μ of Size – 610 x 610 x 50 mm = 4 Nos. 610 x 305 x 50 mm = 2 Nos. Supply Air Blower with Motor (2 Nos.) – 3.7 KW / 4 Pole Centrifugal DIDW forward curved Blower 4. Fan Pulley, Motor Pulley, & Belt
Return Air Grill with Exhaust Air Blower For above refer Drawing No. – FL-9076-15 enclosed
7.8
Exhaust Fan – 3 This Exhaust Fan system having a capacity of 7500 CFM (2 Nos.), which Exhaust the Return Air. Exhaust Fan – 3 System consists of following components:
7.7.1
Exhaust Fan – 3 ( 7500 CFM) 1. 2. 3. 4.
7.6.2
Pre-Filter of (EU-4) 10 μ of Size – 610 x 610 x 50 mm = 4 Nos. Supply Air Blower with Motor (2 Nos.) – 2.2 KW / 4 Pole Centrifugal DIDW forward curved Blower Fan Pulley, Motor Pulley, & Belt
Return Air Grill with Exhaust Air Blower For above refer Drawing No. – FL-9076-17 enclosed as Enclosure
7.7
Support Systems / Utilities All Air Handling Systems & Air Washers are provided with following support utilities that are important for the correct functioning of the system. However, the performance of these support systems does not have any influence on the air filtration capabilities of the system, it may be considered as Non-Critical Support Systems. Main Panel for AHUs. Power, earthing & control cabling by TEVA API INDIA LIMITED
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 11 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN Following Equipment / System of these support utilities are planned as per BOQ (Refer enclosure 1)
8.0
BASIS OF EQUIPMENT / SYSTEM DESIGN To achieve the desired level of Cleanliness Class as defined in as Room Data Sheet enclosed as Enclosure - 3. Following approved drawings for fabrication/execution, Enclosed as Enclosure 2.
SR. NO.
TITLE OF APPROVED DRAWINGS
DRAWING NUMBER
1.
GA Drawing for AHU – 1
FL-9076-1B
2.
GA Drawing for AHU – 4
FL-9076-3C
3.
GA Drawing for AHU – 5
FL-9076-2C
4.
GA Drawing for AW – 1
FL-9076-7B
5.
GA Drawing for AW – 3
FL-9076-8B
6.
GA Drawing for Exhaust Fan – 1
FL-9076-14
7.
GA Drawing for Exhaust Fan – 2
FL-9076-15
8.
GA Drawing for Exhaust Fan – 3
FL-9076-17
9.
Ground Floor Plan HVAC Ducting Layout
ACV/DL/TEVA/GF/001 (Rev. 03)
10.
First Floor Plan HVAC Ducting Layout
ACV/DL/TEVA/FF/002 (Rev. 03)
11.
Second Floor Plan HVAC Ducting Layout
ACV/DL/TEVA/SF/003 (Rev. 02)
9.0
DESIGN DATA (Detailed Specification for Major Components)
Bill of Quantities (BOQ) for all components of the system enclosed as Enclosure 1.
DOC. NO: ACV/TEVA/DQ-01
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
March 8, 2010 Page 12 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN
SR. NO. 1.
Technical specifications for all major components that have been identified in the HVAC System is described enclosed as Enclosure 4.
COMPONENT Pre Filter
PURPOSE Pre-filtration of air up to 10µ
2.
Fine-Filter
Fine File of air up to 1 µ
3.
Cooling/Hot water
Maintain temp/Relative Humidity
4.
Supply Air blower with motor
Pump the conditioned air into the conditioned space
5.
Heating/ Cooling Thermostat
To sense return air temperature & give signal to the 3 way valve
6.
Magnehelic gauge
To Measure Pressure Differential across room.
10.0
SPECIFICATION
Enclosed as Technical Specification sheet
DOCUMENTATION For preparation and execution of subsequent qualification activities of the HVAC System (IQ / OQ / PQ) and to generate documented evidence that the equipment/ system was manufactured as per the pre-defined design following documents is provided in two copies.
SR. NO.
DESCRIPTION OF REQUIRED DOCUMENT
1.
GENERAL:
a)
Purchase Orders
2.
MANUALS:
a)
Operation and maintenance manuals
b)
Operation and maintenance manuals for imported components and bought out items.
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010 Page 13 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN 3.
AS-BUILT DRAWINGS :
a)
Ground Floor Plan HVAC Ducting Layout (ACV/DL/TEVA/GF/001/03)
b)
First Floor Plan HVAC Ducting Layout (ACV/DL/TEVA/FF/002/03)
c)
Second Floor Plan HVAC Ducting Layout (ACV/DL/TEVA/SF/003/02)
4.
TEST CERTIFICATES :
a)
Material specifications and certificates for all contact surfaces
b)
Instrument Calibration Certificates
11.0
POST CONSTRUCTION REVIEW (For any kind of deviation, if any) & DISCUSSIONS After the equipment was ready at manufacturer’s works. It was checked and no deviation was found with respect to Design Qualification.
12.0 DESIGN QUALIFICATION SUMMARY AND CONCLUSION On completion of DQ activity it is found that the manufactured system and its component do not have any deviation with design specification. The system can be taken for installation and further qualification.
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
Page 14 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN
13.0
DESIGN QUALIFICATION APPROVAL
13.1
ACV SYSTEMS PVT. LTD.
SR. NO.
NAME
DESIGNATION
1.
RAHUL.AGGARWAL
TECHNICAL DIRECTOR
SIGNATURE
DATE
SIGNATURE
DATE
13.2 TEVA API INDIA LIMITED
SR. NO.
1.
2.
NAME
DESIGNATION
DOC. NO: ACV/TEVA/DQ-01
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
March 8, 2010 Page 15 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN
14.0
ABBREVIATIONS
SR. NO.
ABBREVIATIONS
1.
AHU
2.
ASHRAE
3.
BOQ
Bill Of Quantity
4.
CFM
Cubic Feet Per Minute
5.
cGMP
6.
DQ
Design Qualification
7.
GA
General Arrangement
8.
HEPA
High Efficiency Particulate Air
9.
HVAC
Heating Ventilation & Air Conditioning
10.
IQ
Installation Qualification
11.
ISO
International Standards Organization
12.
ISPE
International Society of Pharmaceutical Engineering
13.
MOC
Material Of Construction
14.
OQ
Operational Qualification
15.
PQ
Performance Qualification
Air Handling Unit American Society of Heating, Refrigeration & Air Conditioning Engineering
Current Good Manufacturing Practice
CLIENT
: TEVA API INDIA LIMITED
PROJECT
: HVAC WORK FOR MPP BUILDING
CONTRACTOR : ACV SYSTEMS PRIVATE LIMITED
DOC. NO: ACV/TEVA/DQ-01 March 8, 2010 Page 16 of 15
DESIGN QUALIFICATION FOR AHU, AW & EXHAUST FAN 16.
QA
Quality Assurance
17.
URS
User Requirement Specification
18.
VMP
Validation Master Plan
19.
MPP
Multi Product Plant