Electrical Installation Design for (G+6) Urban Building Design /2016
1. INTRODUCTION We are often interested in communicating or transferring energy from one point to another. To do this requires an interconnection of electrical devices. Such interconnection is referred to as an electric circuit, and each component of the circuit is known as an element. . Charge: The concept of electric charge is the underlying principle for all electrical phenomena. Charge is an electrical property of the atomic particles of which matter consists, measured in coulombs (C).Law of Conservation of Charge: Charge can neither be created nor destroyed, only transferred. Electricity: - is a flow of electrical charges such as electrons, through conductor and an invisible force that is used to transfer energy into heat, light, intelligence, or motion. Electricity is explained in terms of potential difference (or voltage), electrical charge flow (or current), and resistance to current flow. Current: The time rate of change of charge, Measured in amperes (A). Mathematically, i(t)=d/dt*q(t) or I=V/R The unit of current measurement is the ampere, and unit of voltage measurement is the volt. .The unit of opposition to current flow Voltage (or potential difference): the energy required to move a unit charge though an element, measured in volts (V).The voltage between two points a and b in a circuit is denoted by vab and can be interpreted in two ways: or resistance, is the ohm. a fundamental form of energy observable in positive and negative forms that occurs naturally (as in lightning) or is produced (as in a generator) of electrons. Electricity service in a building consists of fixtures like, light switches, sockets, clock connectors, cooker control units and similar outlets. Such fittings are collectively known accessories. A switch is used to make a circuit. A complete switch consists of three parts. There is the mechanism itself, a box containing it, and a front plate over it…… Illumination :-is a supplying of sufficient lighting either by natural means (e.g. sun light) or artificial light sources (e.g. electric lamps). Luminous Flux: It is the total quantity of light energy radiated from a luminous body in the form of light waves. It is measured in lumens. It is denoted by symbol φ 1
Electrical Installation Design for (G+6) Urban Building Design /2016
Illumination (intensity of illumination) (E) –is the luminous flux received by a surface per unit area of surface. Measured in lumens per square meter or lux or meter candle. Mathematically, E=ϕ/A Coefficient of utilization (Cu): This is a factor showing the ratio of the lumens reaching on the working plane to the total lumens generated by the source. depends on the dimension of the room to be illuminated, the reflectance of the walls, ceilings, and floors, the lamp output of reflectors and diffusers Maintenance Factor: The light obtained from a light source may be affected by variables due to dire, ageing of the lamp, e.g. The MF takes in to account such effects.
Electric work in a building has three different steps 1.,INSTALATION AND ITS MATERIALS:- Installation is the process of installing electric conduit and scat olla before placing concrete of slab and before masonry work. Conduits can be flexible or rigid. Flexible conduit mostly used for installation in wall while rigid conduit used to install in both concrete and wall. Scat olla protects the entering of concrete or other materials into the conduit. Scat olla also used for fitting with electric fixture like, socket, switch etc. 2, Wiring and wiring materials:A wire is a single strand or a group of strands of an electrically conductive material, usually aluminum or copper Wires are mainly used to carry electrical and telecommunications signals, Several wires stranded together is known as a cable But in practice bare conductors, whether single or stranded together are termed as wire and conductors covered with insulation are termed as cables Cables are mainly used for Power transmission,
carry electricity and
telecommunications signals several wires stranded together is known as a cable But in practice bare conductors, whether single or stranded together are termed as wire and conductors covered with insulation are termed as cables Cables are mainly used for Power transmission carry electricity and telecommunications signals 3, fitting is the process of placing of electric fixtures like, light switches, sockets, CB, clock connectors, cooker control units and similar outlets. 2
Electrical Installation Design for (G+6) Urban Building Design /2016
2. STANDARDS 2.1 Lighting The basic consideration of a complet electricity service (design) in a building consists of; Lighting points switches, Sockets circuit breakers distribution boards clock connectors Agood lighting shoud be Providing adequate uniform lumunation Avoid glare and hard shadow Providing light of suitable color Type of lighting that we have used in our design are:Incandescent lamp Fluorescent lamp Incandescent:-is the light source most commonly used in residential lighting. Light is produced in this source by a wire or filament being heated to incandescence by a flow of current through it. The short life and low efficacy (lumens per watt) of this source limits its use mostly to residential and decorative commercial lighting. Efficacy varies with wattage and filament type, but generally ranges from 15 to 25 lumens per watt for general service lamps. Fluorescent lamp:- Produces light by activating selected phosphors on the inner surface of the bulb with ultraviolet energy which is generated by mercury, arc. Because of the characteristics of a gaseous arc, ballast is needed to start and operate fluorescent lamps. The advantages of the fluorescent light source include improved efficacy and longer life than incandescent lamps. Efficiencies range anywhere from 45 to 90 lumens per watt. Their low surface brightness and
3
Electrical Installation Design for (G+6) Urban Building Design /2016
heat generation make them ideal for offices and schools where thermal and visual comfort is important
The Regulations recommend that every consumer’s installation should have a means of isolation, a means of over current protection and a means of earth leakage protection. This recommendation applies whatever the size or type of installation. Step 1 Calculate number of lamp and layout design. Step 2 Determine the number of socket outlet. Step 3 Calculate automatic circuit breaker for light and for socket according to Ethiopian Electrical Power Corporation Organization Regulation (EEPCO). Step 4 Determine the size and rating of the main circuit breaker which control the whole switch. Step 5 Draw the distribution board Table 2.1.1 standards of electrical light
E(lux)
Φ(lm)
UF
MF
Shop
500
2100
0.6
0.8
Store
50
780
0.6
0.8
Kitchen
300
2100
0.6
0.8
Bath Room
50
780
0.60
0.8
Living Room
100
2100
0.6
0.8
Bed Room
50
780
0.6
0.8
Corridor
150
2100
0.6
0.8
Balcony
50
780
0.6
0.8
Part of building
4
Electrical Installation Design for (G+6) Urban Building Design /2016
100
Stair Case
2100
0.6
0.8
The value of E is obtained from the Standard table 1.of Illumination Engineering Society, IES. according to Ethiopian Electrical Power Corporation Organization Regulation (EEPCOR) for light circuit breaker:-for single phase will be 10A*220V*Allowability. Where in Ethiopia allow ability is 80%. So the value is 1760VA.and according to Ethiopian Electrical Power Corporation Organization Regulation (EEPCOR) for Socket circuit breaker for single phase 16A*220V* Allow ability. So the value is 2816VA Commonly utilized symbols for electrical installation on design. Incandescent lamp.---------------
Socket---------------------Lighting calculation and socket providing for the following housing typolog
1.Three bed Room STEP 1and 2.Lighting calculation and socket providing Table 2..1.2 Lighting calculation and socket providing
Room functions
Area
IILuminati
(m²)
on (E) Flux
NO ,of MF
F lm
cu
lamp calculated (N)
Din. and Living
N, of
NO, of
lamp
Socket
provide
provide
d
d
(N)
31
100
0.8
2100lm
0.6
3.0754
4
4
M. bed rm
14
50
0.8
780
0.6
1.86966
2
2
Child bed1
8
50
0.8
780
0.6
1.06838
2
1
CH.bed2
9
50
0.8
780
0.6
1.20192
2
1
kitchen
6
300
0.8
2100
0.6
1.78571
2
3
RM
5
Electrical Installation Design for (G+6) Urban Building Design /2016
M .bath
4
100
0.8
780
0.6
1.06838
2
2
bath
4
100
0.8
780
0.6
1.06838
2
1
16
14
TOTAL
NB; in bath rooms one of the lamps are for mirror light and the sockets provided in M. bath one is for shaver & the other for boiler and only boiler socket in common bath to enhance best facility Step 3:-Calculate automatic circuit breaker for light and for socket Table 3. circuit breaker for light and for socket
Total socket
VA
14
400
Total Lamp
VA
16
100
Total VA 5600 Total VA 1600
ACB
PRO.ACB
1.9886364
2
ACB 0.9659091
PRO. ACB 1
Step4: Determine the size and rating of MACB fixture
SACB
Current(amp)
Voltage(volt)
Power
Re.factor
F. power
bell
1
6
220
1320
0.7
924
light
1
10
220
2200
0.7
1540
socket
2
16
220
7040
0.2
1408
stove
1
20
220
4400
0.2
880
mitad
1
20
220
4400
0.2
880
Total
5632
Step 5:- Draw the distribution board. 6
MAC
Pr,MAC
B
20.00 5
B
25A
Electrical Installation Design for (G+6) Urban Building Design /2016
2. Two bed Room Step 1. Light Calculation and socket provided
Type of room
area(m2) E
Ø
CU
MF
No
No
Socket
lamp
lamp
provided
0.8013
1
1
M.bath
3
50
780
0.6
Living/Dining
31
100
2100
0,6
0.8
3.0754
4
4
M.Bed Room
13
50
780
0.6
0.8
1.7361
2
2
Bed Room
7
50
780
0.71
0.8
0.9348
1
1
Kitchen
6
300
2100
0.6
0.8
1.7857
2
3
Bath Room
3
50
780
0.6
0.8
0.8013
1
1
11
12
Total 7
Electrical Installation Design for (G+6) Urban Building Design /2016
Step 3. Calculate automatic circuit breaker for light and for socket
Total
VA
socket 12
400
Total Lamp
VA
11
100
Total VA 4800 Total VA 1100
ACB
PRO.ACB
1.70455
2
ACB
PRO.ACB
0.625
1
F.
fixtur
SAC
Current(amp
Voltage(volt
Powe
Re.facto
e
B
)
)
r
r
bell
1
6
220
1320
0.7
924
light
1
10
220
2200
0.7
1540
socket 2
16
220
7040
0.2
1408
stove
1
20
220
4400
0.2
880
mitad
1
20
220
4400
0.2
880
Total
powe r
5632
8
MAC
PR,MAC
B
B
20.005 25A
Electrical Installation Design for (G+6) Urban Building Design /2016
3.ONE BED ROOM Step 1 &2:- Light Calculation and socket provided No
No
Socket
lamp
lamp
provided
0.8
2.381
3
4
0.6
0.8
1.2019
2
2
2100
0.6
0.8
1.7857
2
3
780
0.6
0.8
1.0684
2
2
9
11
Type of room
area(m2)
E
Ø
CU
MF
Living/Dining
25
100
2100
0.6
M.Bed Room
11
50
780
Kitchen
6
300
Bath Room
3
50
Total
9
Electrical Installation Design for (G+6) Urban Building Design /2016
Step 3, Calculate automatic circuit breaker for light and for socket Total socket
VA
Total VA
11
400
4400
Total Lamp
VA
Total VA
9
100
900
ACB
PRO.ACB
1,5625
2
ACB
PRO.ACB
0.511363636
1
FP
MACB
Pr.ACB
20.005
25A
Step4, Determine the size and rating of MACB
Fixture
SACB AMP
VOLT
POWER
RF
Bell
1
6
220
1320
0.7
924
Light
1
10
220
2200
0.7
1540
socket
2
16
220
7040
0.2
1408
staph
1
20
220
4400
0.2
880
meted
1
20
220
4400
0.2
880
Total
10
Electrical Installation Design for (G+6) Urban Building Design /2016
Step 5:- Draw the distribution board.
4. STUDIO Step1,and 2; Light Calculation and socket provided Table1.1: Light Calculation and socket provided
Room
Area(m2)
function multipurpose
Illumination(flux) E
Ø
MF
CU N
N .PRO.
Sockets
20
100
2100
0.8
0.6 1.9842
2
4
kitchen
6
300
2100
0.8
0.6 0.5952
1
3
bath
4
50
780
0.8
0.6 0.5342
1
1
Total lamp=4 11
Electrical Installation Design for (G+6) Urban Building Design /2016
Total socket=8
Step 3 .Calculate automatic circuit breaker for light and for socket
Total socket
VA
Total VA
ACB
PRO.ACB
8
400
3200
1.8181818
2
Total Lamp
VA
Total VA
ACB
PRO.ACB
4
100
400
0.227272727
1
Step4, Determine the size and rating of MACB fixture
SACB AMP VOLT POWER
RF
FP
bell
1
6
220
1320
0.7
924
light
1
10
220
2200
0.7
1540
socket
2
16
220
7040
0.2
1408
stove
1
20
220
4400
0.2
880
mitad
1
20
220
4400
0.2
880
Total
Step5.Draw the distribution bord.
12
MACB
Pr.ACB
20.005
25A
Electrical Installation Design for (G+6) Urban Building Design /2016
5. SHOP Step1,and 2; Light Calculation and socket provided Room function DISPLAY
Area(m2)
Illumination(flux) E
Ø
MF
CU N
N .PRO.
Sockets
20
100
2100
0.8
0.6 1.9842
2
1
STORE
6
300
2100
0.8
0.6 0.5952
1
1
TOILET
4
50
780
0.8
0.6 0.5342
1
ROOM
Total lamp =4 Total socket=2
13
Electrical Installation Design for (G+6) Urban Building Design /2016
Step 3, Calculate automatic circuit breaker for light and for socket Total socket
VA
Total VA
ACB
2
400
800
0.23123
Total Lamp
VA
Total VA
ACB
4
100
400
0.227272727
PRO.ACB 1 PRO.ACB 1
Step4, Determine the size and rating of MACB fixture
SACB AMP
VOLT
POWER
RF
FP
light
1
10
220
2200
0.7
1540
socket
2
16
220
7040
0.2
1408
Total
MACB
Pr.ACB
20.005
25A
2948
14
Electrical Installation Design for (G+6) Urban Building Design /2016
COMMON SPACES
Step1,and 2; Light Calculation and socket provided
Room
Area(m2) Illumination(flux)
function
Ø
MF CU
N
N .PRO.
E
Staircases
11
100
2100
0.8
0.6 1.098417
2
corridor
70
150
2100
0.8
0.6 10.59523
11
Lift
2,25
100
780
0.8
0.6 0.223214
1
Total Lamp per floor=14 Total Lamp Per block=14*7=98 Step3. As EEPCO one ACB (SDB) of lamp can carry a min. 8lamp and a max.16lamp.so we provided one ACB for each floor and totally 7ACB.
15
Electrical Installation Design for (G+6) Urban Building Design /2016
Step4, Determine the size and rating of MACB fixture
SACB
AMP
VOLT
POWER
DF
FP
LIGHT
7
100
220
154000
0.7
107800
TOTAL
107800
Step5.draw Distribution Boards
16
MACN
61.25A=64A
Electrical Installation Design for (G+6) Urban Building Design /2016
17
Electrical Installation Design for (G+6) Urban Building Design /2016
Fig Ground floor of socket
18
Electrical Installation Design for (G+6) Urban Building Design /2016
Table of Contents Contents
Pages
1. INTRODUCTION .................................................................................................................................... 1 2. STANDARDS............................................................................................................................................... 3 2.1 Lighting ................................................................................................................................................ 3 2. Two bed Room .......................................................................................................................................... 7 3.ONE BED ROOM ......................................................................................................................................... 9 4. STUDIO .................................................................................................................................................... 11 5. SHOP ....................................................................................................................................................... 13
19