generator protection
ADP
GENERATOR PROTECTION
Class A
For Generator Protections/Transformer/Unit Auxiliary Transformer Protections. This will trip the GCb Breaker, Field Breaker, Change over of Auxiliary Transformer, Turbine Trip. Class B
This is for Mechanical Trips like turbine trip, etc. This will trip the GCb Breaker, Field Breaker, Change-over of Auxiliary Transformer . Class C
Faults beyond Generator System like Distance Faults/grid faults. This will trip the GCB Breaker only. The Generator will come to house load delivering power only only to auxiliary. auxiliary. This Class C Relay will give commands to reduce Load to Governing System/HP-lp Bypass, etc.