Content Benefits·············································································································3 Footprint and energy saving···········································································································3 Modular configuration, flexible expansion······················································································4 All-in-one, Orderliness···················································································································4 Fast deployment, ROI improvement································································································5
Main specifications····························································································6 Typical scenario configuration············································································7 Typical application A - Mini-sized indoor macro site·········································································7 Typical application B - High integration solution for DBS site····························································8 Typical application C - Battery cabinet with independent cooling·····················································9 Typical application D - Outdoor cabinet for power system·····························································10
1
HUAWEI TECHNOLOGIES
Huawei Mini-shelter was developed for easing operators' pressure in site acquisition, meeting operators' requirements for energy saving and flexible expansion. As an innovative installation solution for site equipment, it not only has a large housing capability like traditional shelter, but also adopts independent compartment temperature control method as outdoor cabinet. Because Mini-shelter has few limitations on application scenarios and can satisfy operators' different requirements, it is gaining more and more popularity in modern site.
HUAWEI TECHNOLOGIES
2
Benefits Footprint and energy saving • Mini-size, decreasing 60% footprint, easing site acquisition pressure and decreasing deployment cost • In non-high-temperature areas*, using independent temperature control method without A/C, reducing 50~80% cooling power consumption • In high-temperature areas*, adopting intelligent heat exchanger system, decreasing A/C running time, saving energy 40~60% • Independent cooling for battery, prolonging its lifespan 2~5 years
Door with HEX*
Door with HEX & TEC*
Door with HEX & direct cooling
Door with TEC
Door with direct Door with natural cooling cooling
power Minimum configuration of traditional shelter
Configuration of Minishelter equipment cabinet
1000W 70% 300W 50% 150W
Air conditioner
Heat exchanger 04
Heat exchanger 02
Temperature control mode
*Notes: None-high-temperature area refers to the area where the total time of the temperature higher than 40oC is less than 12 days (288 h) in one year. High-temperature area refers to the area where the total time of the temperature higher than 40oC is equal to or longer than 12 days (288 h) in one year. TEC: Thermal electric Cooler HEX: Heat Exchanger
3
HUAWEI TECHNOLOGIES
Modular configuration, flexible expansion • Modular configuration. Providing series combinations by three basic function units, "equipment cabinet, auxiliary cabinet, and storage battery cabinet" • Easy configuration according to customer needs • According different working temperature demands of different equipment, every cabinet has individual cooling method • Flexible expansion, and easily solves the management problems of co-site
Example of modular configuration, "equipment cabinet+auxiliary cabinet, +storage battery cabinet"
Side by side expansion
Back to back expansion
HUAWEI TECHNOLOGIES
4
All-in-one, Orderliness • Large housing capability, minimizing the number of outdoor cabinet • All-in-one. "Main equipment, temperature control equipment, power system, battery, ACDC, DCDU …" • Simplifying the site design, making the site orderly
Fast deployment, ROI improvement • Supporting installation in the factory and transportation as a whole • Supporting shipment in components and onsite assembly • Onsite assembly for a three-unit-combination takes about 2 hours by 4 persons • Less civil engineering
crane lifting
5
HUAWEI TECHNOLOGIES
forklift moving
On-site assembly
Main Specifications Technical Index
Equipment Cabinet (1unit)
Battery Cabinet (1unit)
Auxiliary Cabinet (1unit)
Dimensions (W×D×H)
Inner dimensions: 800×800×1800 mm Outside dimensions: Max 905×1085×2155mm (height: 200 mm-base included)
Typical temperature control mode
Heat exchange
TEC conditioner/direct cooling
Natural dissipation
Integration capability
Telecom power, BBU, monitoring
Deep cycle: 2 V single unit, 490 Ah AGM: 2 V single unit, 400 Ah AGM: 12 V single unit, 600 Ah
ACDB, ATS
Relative humidity
Heat exchange: 5-100%RH
TEC: 5-100%RH Direct-cooling: 5-95%RH
5-95%RH
IP protection
IP55
IP55(TEC)/IP34(direct cooling)
IP55
Weight (base, door, and rack included)
Minimum: 204kg Maximum: 236kg
Minimum: 212kg Maximum: 220kg
177kg
Technical Index
Power Consumption
Cooling Capacity
Heat Exchanger
Typical Power Consumption
Maximum Power Consumption
HX02 110W
150W
HX04 215W
300W
HX02: 80W/K HX04: 190W/K Inner Equipments HX02 heat
Temperature Conditioning Performance
TEC
ΔT* Inner Equipments HX04 heat ΔT
700W
1000W
10oC
12oC
Direct cooling
Maximum Typical Power Typical Power Power Consumption Consumption Consumption
Maximum Power Consumption
310W
48W
380W
48W
190W
300W
Inner temperature: 15oC~30oC
ΔT: 2oC~3oC
1600W 2000W 2300W 10oC
13oC
14oC
*Notes: ΔT=TI-TO TI: Inner temperature TO: Outer temperature
HUAWEI TECHNOLOGIES
6
Typical scenario configuration Typical application A - Mini-sized indoor macro site •• In high-temperature areas, intelligent heat exchanger
Scenario •• Street site or rooftop site in large city, site acquisition is hard
system saving energy 40-60%
•• Better grid, no electric time is less than 2 hours per day •• Expecting Lower TCO
site configuration
Benefits •• 2-unit-combination Mini-shelter cutting down
BTS equipment
BTS3900
TRX configuration
S4/4/4
60% footprint, decreasing the site acquisition and
shelter
Mini-shelter (2units)
deployment cost
power system
TP48300/A
storage battery
150AH 12V AGM
backup time
4hours
•• In non-high-temperature areas, independent temperature control method saving energy 50-80%
Wiring Space(1U)
Wiring Space(4U) Spare Space(9U) EMUA(1U) AC/DC(16U) TP48300/A
ACDB(4U) Wiring Space(4U)
DCDU-03A(1U) Spare Space(5U) BTS3900(21U)
TEC 150AH 12V
150AH 12V
150AH 12V
150AH 12V
Base
Configuration of non-high temperature environment
Wiring Space(1U) Spare Space(1U)
Wiring Space(4U)
EPAC(2U) ACDB(4U)
Air Return Vent
AC/DC(16U) TP48300/A
Wiring Space(7U)
Heat Exchanger
DCDU-03A(1U) A/C
Air Supply Vent
IDU(4U) BTS3900(21U)
TEC 150AH 12V
150AH 12V
150AH 12V
Base
Configuration of high temperature environment
7
HUAWEI TECHNOLOGIES
150AH 12V
Typical application B - High integration solution for DBS site Scenario •• Off-grid or unreliable grid •• Lots of auxiliary equipment, site acquisition is difficult •• Expecting Lower OPEX Benefits •• 3-unit-combination Mini-shelter cutting down 40% footprint •• High integration with BBU, battery, monitor, power system, environment control equipment, ACDC … •• Independent temperature control method saving energy 50-80%, D.G-battery hybrid power saving fuel 50%
site configuration BTS equipment
DBS3900
TRX configuration
S2/2/2
shelter
Mini-shelter (3 units)
power system
TP48300/A
storage battery
490Ah deep cycle battery
backup time
8hours
diesel generator
1pcs 8 KVA
controller
IPS
Wiring Space(4U)
AC/DC(16U) TP48300/A
BAT
Heat Exchanger Direct cooling or TEC
DCDU-03B(1U) Spare Space(1U) BBU(2U) EMUA(1U)
BAT
Spare Space(10U)
ACDB(4U) Spare Space(1U)
Base
HUAWEI TECHNOLOGIES
8
Typical application C - Battery cabinet with independent cooling Scenario •• Traditional shelter with A/C (above 1000w) cooling •• A/C start-temperature set at 20~25oC, high cooling energy consumption Benefits •• Providing independent cooling for battery with TEC(380w) •• A/C start-temperature set at28~35oC, saving energy up to 70% •• Supporting indoor assembly
Scenario •• Outdoor site, outdoor BTS equipment •• Ambient temperature has great influence on battery's life Benefits •• Providing direct cooling/TEC cooling for battery •• Comparing with ordinary battery cabinet with natural cooling, Mini-shelter will prolong battery lifespan 2~5 years •• Support onsite assembly, suit for rooftop site and mountain site, individual component weight≤50kg
BAT
BAT
Direct cooling or TEC BAT
BAT
Base
9
HUAWEI TECHNOLOGIES
Typical application D - Outdoor cabinet for power system Scenario
Benefits
•• Outdoor site, outdoor BTS equipment
•• Outdoor cabinet for power system with TP48300/A, offering
•• Outdoor power system with large capacity •• Some other indoor equipment
30A or 50 A rectifier module, max capacity to 300A •• Providing 20U spare space for other equipments
Wiring Space(4U)
AC/DC(16U) TP48300/A
Heat Exchanger Spare Space(20U)
Base
Scenario
Benefits
•• Outdoor site, outdoor BTS equipment
•• Outdoor cabinet for power system with EPS4890,
•• Outdoor power system with small capacity •• Some other indoor equipment
max capacity to 90A •• Providing 32U spare space for other equipment
Wiring Space(3U) TP4890(5U)
Heat Exchanger Spare Space(13U)
TEC 150AH 150AH 150AH 150AH 12V 12V 12V 12V
150AH 150AH 150AH 150AH 12V 12V 12V 12V
Base
HUAWEI TECHNOLOGIES
10
Huawei Mini-shelter Solution
Copyright © Huawei Technologies Co., Ltd. 2009. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd. Trademark Notice , HUAWEI, and
are trademarks or registered trademarks of Huawei Technologies Co., Ltd.
Other trademarks, product, service and company names mentioned are the property of their respective owners. NO WARRANTY THE CONTENTS OF THIS MANUAL ARE PROVIDED “AS IS”. EXCEPT AS REQUIRED BY APPLICABLE LAWS, NO WARRANTIES OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE MADE IN RELATION TO THE ACCURACY, RELIABILITY OR CONTENTS OF THIS MANUAL. TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, IN NO CASE SHALL HUAWEI TECHNOLOGIES CO., LTD BE LIABLE FOR ANY SPECIAL, INCIDENTAL, INDIRECT, OR CONSEQUENTIAL
HUAWEI TECHNOLOGIES CO., LTD. Huawei Industrial Base Bantian Longgang Shenzhen 518129, P.R. China Tel: +86-755-28780808 Version No.: M3-308130299-20090722-C-1.0
DAMAGES, OR LOST PROFITS, BUSINESS, REVENUE, DATA, GOODWILL OR ANTICIPATED SAVINGS ARISING OUT OF OR IN CONNECTION WITH THE USE OF THIS MANUAL.
www.huawei.com