Lionel Ng, LPBS LPBS - Low Voltage Voltage Products
Welcome To ABB Welcome Technical Sharing Session
Circuit Breakers Standards Guidelines IEC 60947-2
Agenda
IEC 60947-2
Circuit Breaker Standard, for industrial application –
Definitions for MCCBs and ACBs
–
Choice criteria based on rated and limit values
© ABB Group
Standard for LV apparatus
IEC 60947 Standard for industrial application
–
International Standard
IEC 60947
–
European Standard
EN 60947
© ABB Group
IEC 60947-1
Part 1: General rules
IEC 60947-2
Part 2: Circuit breakers
IEC 60947-3
Part 3: Switch disconnectors
IEC 60947-4-1
Part 4: Contactors
IEC 60947-5-1
Part 5: Control circuit devices
IEC 60947-6-1
Part 6: Multifunction devices
IEC 60947-7-1
Part 7: Auxiliary materials
IEC Standard definitions
Circuit Breaker - IEC 60947-2
A mechanical switching device capable of breaking, carrying and making currents under normal circuit conditions and also making, carrying, for a specified time, and breaking currents under specified abnormal circuit conditions such as those of short-circuit.
© ABB Group
BREAKING
Breaking Capacity
WITHSTAND
Short time withstand
MAKING
Making Capacity
IEC Standard definitions
Switch Disconnector - IEC 60947-3
A mechanical switching device capable of breaking, making and carrying currents under normal circuit conditions but only making and carrying, for a specified time, currents under specified abnormal circuit conditions such as those of short-circuit.
© ABB Group
BREAKING
Breaking Capacity
WITHSTAND
Short time withstand
MAKING
Making Capacity
IEC Standard definitions
Moulded case circuit breaker (MCCB): a circuit breaker having a supporting housing of moulding insulating material, forming an integral part of the circuit breaker (Tmax-XT).
© ABB Group
IEC Standard definitions Air circuit breaker (ACB): a circuit breaker having a supporting housing of moulding insulating material and a metallic frame, forming an integral part of the circuit breaker (Emax & Emax 2).
© ABB Group
Current limiting circuit breaker
Current limiting circuit breaker (IEC 60947-2 def. 2.3)
A circuit breaker with a break-time short enough to prevent the short-circuit current from reaching its peak value.
A current-limiting circuit breaker is able to reduce the stress, both thermal and dynamic, because it has been designed to start the opening operation before the shortcircuit current has reached its first peak, and to quickly extinguish the arc between the contacts.
© ABB Group
Current limiting circuit breaker
A
R
A
I
R
A = Direction of arc due to the magnetic field R= Repulsion of moving contacts due to the short circuit current
© ABB Group
Current limiting circuit breaker
Energy limitation Current
Time
© ABB Group
Current limiting circuit breaker
Peak limitation curves Value of the limited peak of the short circuit current according to the value of the symmetrical short circuit current Irms.
© ABB Group
Current limiting circuit breaker
I2t curves
Value of the let-through energy according to the value of the symmetrical short circuit current I rms.
© ABB Group
Current limiting circuit breaker
Energy limitation Protection against short-circuit (IEC 60364) To protect a cable against short-circuit, the specific let-through energy of the protective device must be lower or equal to the withstanding energy of the cable: Specific let through energy curve LLL
1E3MA²s
100MA²s
where – I2 t is the specific let-through energy of the protective device which can be read on the curves supplied by the manufacturer; – S is the cable cross section [mm 2]; in the case of conductors in parallel it is the cross section of the single conductor; – k is a factor that depends on the cable insulating and conducting material.
10MA²s
1MA²s
0.1MA²s
1E-2MA²s
0.1kA
© ABB Group
1kA
10kA
100kA
Choice criteria
Rated values (Iu, Ue)
Limit values (Icu, Ics, Icw, Icm)
© ABB Group
Insulation values (U i, Uimp)
Rated value I u
Rated uninterrupted current Iu the rated uninterrupted current of an equipment is a value of current, stated by the manufacturer, that the equipment can carry in uninterrupted duty (at 40 °C)
IEC 60947-1 def. 4.3.2.4
© ABB Group
Rated value I u The rated uninterrupted current I u is different from the rated current In, which is the rated current of the thermomagnetic or electronic trip unit and is lower or equal to I u.
A new concept for setting the current In: the rating plug
© ABB Group
Rated value I u
Rated uninterrupted current I u Some factors may reduce the I u of a circuit breaker like temperature, altitude or frequency. XT1 160
XT4 250
Rated value U e
Rated operational voltage U e the rated operational voltage of an equipment is a value of voltage which, combined with a rated operational current, determines the application of the equipment and to which the relevant tests and the utilization categories are referred.
IEC 60947-1 def. 4.3.1.1
© ABB Group
Rated value U e
Rated operational voltage U e Breaking capacity is always referred to the operational voltage; the breaking capacity decreases when the voltage increases.
Rated value U e
Some factors may reduce the Ue of a circuit breaker
Choice criteria
Rated values (Iu, Ue)
Limit values (I cu, Ics, Icw, Icm)
© ABB Group
Insulation values (U i, Uimp)
Limit value Icu Icu = RATED ULTIMATE SHORT CIRCUIT BREAKING CAPACITY
IEC 60947-2 def. 4.3.5.2.1
Breaking capacity according to a specified test sequence. Do not include after the short circuit test, the capability of the circuit breaker to carry its rated current continuously. - test sequence: O - 3 min - CO - dielectric withstand at 2 x Ue - verification of overload release at 2.5 x I1
© ABB Group
Limit value Ics Ics = RATED SERVICE SHORT CIRCUIT BREAKING CAPACITY
IEC 60947-2 def. 4.3.5.2.2
Breaking capacity according to a specified test sequence. Include after the short circuit test, the capability of the circuit breaker to carry its rated current continuously - test sequence: O - 3 min - CO - 3 min – CO - dielectric withstand at 2 x Ue - verification of temperature rise at I u - verification of overload release at 1.45 x I1 - verification of the electrical life
© ABB Group
Limit values I cu and Ics
Relation between I cs and Icu
This relation is always true!!!
Ics ≤ Icu The service breaking capacity I cs can be expressed as a value of breaking current, in kA; a percentage of I cu, rounded up to the lowest whole number, in accordance with the table (for example Ics = 25% Icu). Standard ratios between
© ABB Group
and I I cs cu
When is Icu required?
Where continuity of service is not a fundamental requirement.
For protection of single terminal load.
For motor protection.
Where maintenance work is easily carried out without much disruption. Generally for circuit breaker installed on terminals part of plant.
When is Ics required?
Where continuity of service is a fundamental requirement.
For installation in power center.
Where is more difficult to make maintenance.
When is difficult to manage spare breakers.
Generally for installation in main distribution board immediately downstream transformer or generator.
Limit values I cu and Ics
Icu and Ics: selection criteria
Main circuit breakers or circuit breakers for which a long out-of-service period can not be accepted (for example naval installation) Ics CB selection based on Icu
circuit breakers tor termlnal circuits or circuit breakers for economic application
© ABB Group
Icu or Ics ?
Application of Icu / Ics circuit breakers
When Isc = 100 % of Icu is not necessary ?
When the real short circuit current in the point of installation is lower than the maximum Ics breaking capacity. Breaker A: Icu =100 kA with Ics = 100 % of Icu Breaker B: Icu = 100 kA with Ics = 75 % of Icu Please also consider that short circuit current at the end of the line is still lower
A
70 kA B
50 kA !!! U
LOAD
When Isc = 100 % of Icu is not necessary ?
Motor Protection according to IEC 60947- 4-1
Duty cycle: O - 3mins - CO at “Iq” current (maximum short circuit current) O - 3mins - CO at “r” current (critical short circuit current depending from the contactor size)
Where: O: Tripping of the circuit breaker under short circuit condition. CO: Closing by the contactor under short circuit condition and tripping of the circuit breaker.
Icu or Ics ? Conclusion
Consider that not always Ics = 100% of Icu for all the employ voltage range, i.e. (from 220 V a.c. to 690 V a.c.duty, and 250 V d.c.). Selection of circuit breaker with breaking capacity Icu or Ics must be done according to the real technical installation requirement. Independently from the duty cycle selected the safety of the plant is strictly dependent from the maximum circuit breaking capacity (in most of cases Icu).
Limit value Icw IEC 60947-2 def. 4.3.5.4
Icw = RATED SHORT-TIME WITHSTAND CURRENT Example of use of category B circuit breakers in electrical plant Trafo 630kVA Ucc%=4%
ACB E1B12 400V
22.7kA MCCB XT4
© ABB Group
MCCB XT3
The upstream circuit breaker can withstand the fault current up to 1 sec, thus guaranteeing an excellent selectivity with downstream apparatus
Limit value Icw CATEGORY B CIRCUIT BREAKER
IEC 60947-2 Table 4
Circuit breakers specifically intended for selectivity in short circuit conditions in relation to other protection devices in load-side series, that is with an intentional delay (adjustable) applicable in short circuit conditions. These circuit breakers have a specified rated short-time withstand current I cw.
© ABB Group
Limit value Icw CATEGORY A CIRCUIT BREAKER
IEC 60947-2 Table 4
Circuit-breakers “not specifically” intended for selectivity under short circuit conditions with respect to other protection devices in series on the load side, that is without intentional short-time delay provided for selectivity under short-circuit conditions. These circuit-breakers have not a specified rated short-time withstand current value I cw.
© ABB Group
Limit value Icw Icw = RATED SHORT-TIME WITHSTAND CURRENT
IEC 60947-2 Table 3
It is the value of short-time withstand current assigned to the circuit-breaker by the manufacturer under specified test conditions. This value is referred to a specified time (usually 1s or 3s). It must be stated when the circuit-breaker is classified in category B and its value must be greater than:
The highest value between 12 I u and 5 kA
for CBs with Iu 2500A
30 kA
for CBs with Iu > 2500A
Circuit breakers without I cw value are classified in category A
© ABB Group
Selectivity Categories
Limit value Icm Icm = RATED SHORT-CIRCUIT MAKING CAPACITY
IEC 60947-2 def. 4.3.5.1
Making capacity for which the prescribed conditions according to a specified test sequence include the capability of the circuit breaker to make the peak current corresponding to that rated capacity at the appropriate applied voltage. It is always necessary to verify that: Icm Ipeak
© ABB Group
Limit value Icm For a.c. the rated short-circuit making capacity of a circuit-breaker shall be not less than its rated ultimate short-circuit breaking capacity, multiplied by the factor n of the table.
© ABB Group
IEC 60947-2 Table 2 Icm ≥ n x Icu
Current limiting circuit breaker Example Peak 105kA 100kA
T6L800 In800 54kA
16,8kA
XT2L 160 In160
10kA
10kA
© ABB Group
50kA
100kA
Irms
Limit value Icm
If the cos of the plant is higher than the standard prescribed value, it is not necessary to take into account the rated shortcircuit making capacity of the circuit-breakers (Icm).
If the cos of the plant is lower than the standard prescribed value, usually near to the transformer and/or generator, it is necessary to verify Icm Ipeak.
© ABB Group
Limit value Icm Sometimes it can happen Short circuit current of the plant is Icc = 75kA ; The used circuit breaker has an Icu = 75 kA; According to the table 2, cosk=0.2 and n=2,2 so Icm = n x Icu = 165 kA.
If the cos k of the plant is equal to 0.16 (lower than the standard prescribed value) the evaluated Ip = 175 kA.
Since Ip > Icm the CB selected is not correct. I will use a CB with a greater value of Icu in order to have an Icm value suitable to the peak current of the plant.
© ABB Group
Limit value Icm
© ABB Group
Choice criteria
Rated values (Iu, Ue)
Limit values (Icu, Ics, Icw, Icm)
© ABB Group
Insulation values (U i, Uimp)
Limit value Ui IEC 60947-1 def. 4.3.1.2
Ui = RATED INSULATION VOLTAGE
The rated insulation voltage of an equipment is the value of voltage to which dielectric tests and creepage distances are referred.
It shall be always verified that:
Ue < Ui
© ABB Group
Limit value Uimp Uimp = RATED IMPULSE WITHSTAND VOLTAGE
IEC 60947-1 def. 4.3.1.3
The peak value of an impulse voltage of prescribed form and polarity (1,2/50ms) which the equipment is capable of withstanding without failure under specified conditions of test and to which the values of the clearances are referred. It shall be always verified that: Uimp > transient overvoltage in the plant
© ABB Group
Temperature-rise for terminals and accessible parts IEC 60947- 2 Table 7
© ABB Group
Overload protection
IEC 60947- 2 Table 6
t
© ABB Group
i
Short circuit protection
IEC 60947- 2 8.3.3.1.2
t
S I
© ABB Group
i
Type Tests IEC 60947- 2 8.3
The tests to verify the characteristics of circuit breakers are: • type tests carried out on samples:
Type Tests
© ABB Group
Routine Tests IEC 60947- 2 8.4
• routine tests carried out on all circuit breakers and including the following tests:
© ABB Group
Annex F - J Tests of EMC for circuit breakers with electronic overcurrent protection •Electrostatic discharges •Radiated radio-frequency electromagnetic fields
Immunity
•Electrical fast transients/bursts •Surges •Conducted disturbances induced by radio-frequency fields •Harmonics •Voltage fluctuations
Emission
•Conducted disturbances •Radiated disturbances •Dry heat test Damp heat test
Climatic tests
•Temperature variation cycles at a specified rate of change
CE Marking
According to european directives:
© ABB Group
Low Voltage Directive 73/23 EEC
Electromagnetic Compatibility 89/336 EEC
Annex H
Test sequence for circuit-breakers for IT systems This test is intended to cover the case of a second fault to earth in presence of a first fault on the opposite side of a circuit breaker when installed in IT systems.
In this test at each pole the applied voltage shall be the phase-to-phase voltage corresponding to the maximum rated operational voltage of the circuit breaker at which it is suitable for applications on IT systems.
Circuit Breakers Standards Guidelines IEC 60898
IEC Standard definitions Miniature Circuit Breakers MCB International Standard References IEC 60898
Applicable to circuit-breakers for protection of wiring installation in buildings and similar applications, and designed for use by uninstructed persons, and for not being maintained. Part 1: Circuit-breakers for a.c. operation Part 2: Circuit-breakers for a.c. and d.c. operation
(additional requirements)
Choice criteria
Rated values (In, Ue)
Limit values (Icn, Ics)
Rated value I n Rated uninterrupted current (I n): the rated uninterrupted current of an equipment is a value of current, stated by the manufacturer, which the equipment can carry in uninterrupted duty, at a specified reference ambient air temperature (30 °C).
The rated current doesn’t exceed the 125A.
IEC 60898-1 def. 5.2.2
Rated value U e
Rated operational voltage (U e): • The rated operational voltage of a circuit-breaker is the value of voltage, assigned by the manufacturer, to which its performances (particularly the short-circuit performance) are referred. • The rated operational voltage doesn’t exceed the 440Vac 220Vdc. IEC 60898-1 def. 5.2.1.1
Choice criteria
Rated values (In, Ue)
Limit values (Icn cn, Ics cs)
Limit value Icn Icn = RATED SHORT CIRCUIT CAPACITY
IEC 60898-1 def. 5.2.4
The rated short-circuit capacity is the value of the ultimate short-circuit breaking capacity for which the prescribed conditions, according to a specified test sequence, do not include the capability of the circuit-breaker to carry 0.85 times its non-tripping current for the conventional time. test test sequ sequen ence ce:: O - 3 min min - CO - leakage leakage current current at at 1.1 1.1 U e (< 2 mA) - dielectri dielectric c strength strength test test at 900 900 V - verificat verification ion of overloa overload d release release at 2.8 x I n The rated short circuit capacity doesn’t exceed the 25kA in ac and 10kA in dc
Limit value Ics Ics = RATED SERVICE SHORT CIRCUIT CAPACITY CAPACITY
IEC 60898-1 def. 3.5.5.2
The service short-circuit capacity of a circuit-breaker is the value of the breaking capacity for which the prescribed conditions according to a specified test sequence include the capability of the circuit-breaker to carry 0.85 times its nontripping current for the conventional time.
Limit value Ics Service Short Circuit capacity (I cs): - test seq. :
O - 3 min - O - 3 min – CO O - 3 min - CO - 3 min – CO - leakage current at 1.1 Ue (< 2 mA) - dielectric strength test - verification of no tripping at 0,85 x In
(for one or two poles cb) (for three or four poles cb)
A circuit-breaker with a rated short-circuit capacity (Icn) has a corresponding service shortcircuit capacity (I cs) as from this table: The circuit breaker with
Icn < 6000A 6000A < Icn < 10000A Icn > 10000A
Ics is equal to 1xIcn Ics is equal to 0,75xIcn Minimum value of Ics is 6000A. Ics is equal to 0,5xIcn Minimum value of Ics is 7500A.
Ics Test
Tripping Curves Overload characteristics The main difference between the overload protection curve of the CBs responding to IEC 60947 or IEC 60898 are referred to the conventional non tripping current. The prescibed conditions are given in this table:
Tripping Curves Magnetic characteristics The CBs according to IEC 60947 usually have the instantaneous threshold at 5 or 10 times the rated current with a tolerance of + 20%.
The CBs according to IEC 60898-1 (ac applications) have different instantaneous threshold referred to the type B , C , D as indicated in the table below:
Tripping Curves
Tripping Curves
In some cases, the conditions IB < In < IZ and I2 < 1.45 IZ do not guarantee complete protection, e.g. when overcurrents are present for long periods which are smaller than I2. They also do not necessarily lead to an economical solution. It is therefore assumed that the circuit is designed so that minor overloads of a long duration will not occur regularly.
IEC 60364-4-43
Tripping Curves
Comparison IEC 60947-2 vs IEC 60898 IEC 60947-2
IEC 60898-1
People
Instructed
Uninstructed
Maintenance
Possible
Not possible
< 1000 Vac
< 440 Vac
< 1500 Vdc
< 220 Vdc
40° C
30° C
Rated Voltage (Ue) Ambient Temperature
No limits Rated Current
(Iu < 6300 A) Short circuit breaking current
No limits for Icu
In = 125 A Icn = 25 kA (ac) Icn = 10 kA (dc)
Selection of protective Devices
Generalities about the main electrical parameters
Don’t forget
Ue Un Icu or Ics Ik Icm Ip
Ue, Icu, Ics, Icm?
Selection of protective Devices
Protection of feeders
against overload
I ≤ In or I1 ≤ Iz
b
against short-circuit
In Iz S
I2t ≤ k2S2
Ib
Selection of protective Devices The correct circuit breaker must be selected to satisfy the following conditions: •It
must own short circuit breaking power (lcu or eventually lcs) greater or equal to the short circuit current lcc •It
must use a protection release so that its overload setting current ln (l1) satisfies the relation lB < ln < lZ let through energy (l 2t) that flows through the circuit breaker must be lesser or equal to the maximal one allowed by the cable (K²S²) •The
Selection of protective Devices
Selection of protective Devices
As far as the verification required by IEC 60364, according to which the overload protection must have an intervention current lf that assures the operation for a value lesser than 1,45 lz (lf < 1,45 lz), we must state that it is always verified for ABB Circuit breakers, since according to IEC 60947-2 the required value is less than 1,3 ln.
Selection of protective Devices
Selection of protective Devices
Protection of generators I ≤ I1 I3 or I2 ≤ 2.5 -4 x Ingen ngen
G
Selection of protective Devices
Protection of transformers I ≤ I1 Upstream CB nT
I3 or I2 Iinrush
Selection of protective Devices 20kV
Steps determining the short-circuit currents choosing the CB setting of the MV overcurrent protection … setting of the LV overcurrent protection …
400V
Selection of protective Devices 20kV
400V
Selection of protective Devices 20kV
400V
Protection of Transformers
As to be able to protect LV/MV transformers LV side, we must mainly take into account: Rated current of the protected transformer, LV side, from which the rated current of the circuit breaker and the setting depend on (In); •
The maximum estimated short circuit current in the installation point which defines the minimal breaking power of the protection circuit breaker (Isc). •
Protection of Transformers Switchboards with one transformer
Sn
U20
In Isc
The rated current of the transformers LV side is defined by the following expression Sn x 103 In = 3 x U20 where Sn = rated power of the transformer [kVA] U20 = rated secondary voltage (no load) of the transformer [V] ln = rated current of the transformer, LV side [A]
Protection of Transformers
The full voltage three-phase short circuit current immediately after the LV side of the transformer can be expressed by the following relation once we suppose infinite power at the primary: Isc =
In x 100 Ucc %
where Ucc %= short circuit voltage of the transformer [%] ln
= rated current, LV side, [A]
lsc = three-phase rated short circuit current, LV side, [A]
Protection of Transformers
The short circuit current is normally lesser than the preceding deduced value if the circuit breaker is installed at a certain distance by means of a cable or bar connection, according to the connection impedance.
Protection of Transformers
The following table shows some possible choices within the SACE Emax ACB range according to the characteristics of the CB to protect. Attention Those indications are valid at the conditions that we declare in the table; different conditions will lead us to repeat calculations and modify the choices.
Protection of Transformers Sn
[kVA]
500
630
800
1000
1250
1600
2000
2500
3150
Ucc (1)
%
4
4
5
5
5
6,25
6,25
6,25
6,25
In (2)
[A]
722
909
1154
1443
1804
2309
2887
3608
4547
Isc (2)
[kA]
18
22.7
23.1
28.9
36.1
37
46.2
57.7
72.7
E1B12
E2B16
E2B20
E3B25
E3B32
E4S40
E6H50
SACE Emax
E1B08
E1B12
(1) For values of the percent short circuit voltage U’cc % different from the Ucc% values as per table, the rated three-phase short circuit current I’cn becomes: I’sc =
Isc
Ucc % U’cc %
(2) The calculated values refer to a U20 voltage of 400 V. for different U’20 values, do multiply In and Isc the f ollowing k times:
U’20
k
[V]
220
380
400
415
440
480
500
660
690
1.82
1.05
1
0.96
0.91
0.83
0.8
0.606
0.580
Protection of Transformers Switchboards with more than 1 transformer in Parallel
3
2
1 Isc2 + Isc3
I2
I1
C i r c u i t b r e a k e r A
I3
Isc1
I4
I5
Isc1 + Isc2 + Isc3
C i r c u i t b r e a k e r B
Protection of Transformers
As far as the calculation of the rated current of the transformer is concerned, the rules beforehand indicated are completely valid. The minimum breaking capacity of each circuit breaker LV side must be greater than the highest of the following values: (the example refers to machine 1 of the figure and it is valid for the three machines in parallel): •lsc
1 (short circuit current of transformer 1) in case of fault immediately downstream circuit breaker 1; •lsc2
+ lsc3 (short circuit currents of transformer 2 and 3) in case of fault immediately upstream circuit breaker 1;
Protection of Transformers
Circuit breakers l4 and l5 on the load side must have a short circuit capacity greater than lsc1 + lsc2 + lsc3; naturally every transformer contribution in the short circuit current calculation is to be lessened by the connection line transformer - circuit breaker (to be defined case by case).
Low voltage selectivity with ABB circuit breakers Selectivity definitions and Standards
Agenda Low voltage selectivity with ABB circuit breakers
Definitions and Standards
Selectivity techniques
Back-up protection
Introduction What is selectivity? Selectivity (or discrimination)
A is the supply side circuit breaker (or upstream)
is a type of coordination of two or more protective devices in series.
Selectivity is done between one circuit breaker on the supply side and one circuit breaker, or more than one, on the load side.
B and C are the load side circuit breakers (or downstream)
Introduction Protection system philosophy
Reduce the stress and prevent damage Minimize the area and the duration of power loss
DAMAGE REDUCTION
Better selectivity
FAULT
CONTINUITY OF SERVICE
Fast fault elimination
Main purposes of coordination Selectivity purpose Selective coordination among devices is fundamental for economical and technical reasons It is studied in order to:
rapidly identify the area involved in the problem; bound the effects of a fault by excluding just the affected zone of the network; preserve the continuity of service and good power quality to the sound parts of the network; provide a quick and precise identification of the fault to the personnel in charge of maintenance or to management system, in order to restore the service as rapidly as possible;
achieve a valid compromise between reliability, simplicity and cost effectiveness.
Standards definition Selectivity The definition of selectivity
IEC 60947-1 Standard: “Low voltage equipment Part 1: General rules for low voltage equipment”
IEC 60947-1 def. 2.5.23
“Trip selectivity (for overcurrent) is a coordination between the operating characteristics of two or more overcurrent protection devices, so that, when an overcurrent within established limits occurs, the device destined to operate within those limits trips whereas the others do not trip”
Overcurrent selectivity Example In occurrence of a fault (an overload or a short circuit) if selectivity is provided only the downstream circuit breaker opens.
Overcurren Overcur rentt sel select ectivi ivity ty Example In occurrence of a fault (an overload or a short circuit) if selectivity is not provided both the upstream and the downstream circuit breakers could could open open All the system is out of service!
Standards definition Partial and total selectivity IEC 60947-2 def. def. 2.17.2 2.17.2 - 2.17.3 2.17.3
A and B connected in series: part partia iall sele select ctiv ivit ity y and and tota totall sele select ctiv ivit ity y.
Standards definition Partial selectivity “Partial selectivity is an overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load side protection device carries out the protection up to a given iven leve levell of overc vercu urre rrent, with witho out makin king the the othe otherr devi device ce trip trip..”
Is is the ultimate selectivity value!
B opens only according to fault current c urrent lower than a certain current value; values equal or greater than I s will give the t he trip of both A and B. Is = ImA
Standards definition Total selectivity “Total selectivity is an overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load side protection device carries out the protection without making the other device trip.”
B
A
Only B trips for every current value lower or equal to the maximum short-circuit current. Is = Ik
Standards definition Partial and total selectivity Upstream circuit breaker A T4N 250 PR221DS In = 250 (Icu = 36kA) Downstream circuit breaker B
S 294 C100 (Icu = 15kA)
Selectivity analysis Time-current curves
Overload zone Thermal protection L protection
Time-current selectivity
Short-circuit zone Magnetic protection S, D, I and EF protections
Current, time, energy, zone, directional, zone directional selectivity
Selectivity analysis Real currents Real currents circulating through the circuit breakers
A
I>
B
I>
A
B
I A = IB tA
I>
A
I>
I>
B
I>
I A = IB + Iloads
I>
I>
I>
I>
I>
I A = (IB + Iloads) / 2
tA tA
tB tB
tB
IA=IB
IB IA
IA
IB
Agenda Low voltage selectivity with ABB circuit breakers
Definitions and Standards
Selectivity techniques
Back-up protection
Introduction Selectivity techniques
Current selectivity
Time selectivity
Energy selectivity
Zone (logical) selectivity
Current selectivity Base concept
Current selectivity: closer to the t he power supply the fault point is, higher the fault f ault current is 3kA
In order to guarantee selectivity, the protections must be set to different values of current thresholds 1kA
tA
tA
B
A
The ultimate selectivity value is equal to the instantaneous trip threshold of the upstream protection device
Ultimate selectivity value tB
ImB
ImA
Other methods are needed to have a total selectivity
Current selectivity Example Circuit breaker A will be set to a value which does not trip for faults which occur on the load side of B. (I3Amin >1kA)
Circuit breaker B will be set to trip for faults which occur on its load side (I3Bmax < 1kA) 104s
Is
103s
Is = I3Amin
A
102s 10s
Here the selectivity is a total selectivity, selectivity, because it is guaranteed up to the maximum value of the short-circuit current, 1kA.
1s B 10-1s 10-2s
0.1kA
1kA
3kA
10kA
Current selectivity Plus and minus Plus Easy to be realized Economic Instantaneous
CURRENT SELECTIVITY Minus Sele Select ctiv ivit ity y is often ften only part partia iall Curr rren entt thre thresh sho olds lds rise ise very very quickl ickly y
Time selectivity Base concept
Time selectivity is based on a trip delay of the upstream circuit breaker, so to let to the downstream protection the time suitable to trip
B
A
Setting strategy: progressively increase the trip delays getting closer to the power supply source On the supply side the S function is required
Time selectivity Example A will be set with the current threshold I2 adjusted so as not to create trip overlapping and with a trip time t2 adjusted so that B always clears the fault before A
B will be set with an instantaneous trip against short-circuit
I k 104s
Is
The ultimate selectivity value is:
103s 102s 10s
B
1s
I2 t2
10-1s 10-2s 0.1kA
1kA
10kA
100kA
Is = Icw A
(if function I = OFF)
Is = I3minA
(if function I = ON)
Time selectivity Example Which is the problem of time selectivity?
In the case of fault occurring at the busbars, circuit breaker A takes a delayed trip time t 2
I k
The network must withstand high values of let-through energy!
104s 103s 102s 10s
If there are many hierarchical levels, the progressive delays could be significant!
B
1s
t2
10-1s 10-2s 0.1kA
1kA
10kA
100kA
Time selectivity Plus and minus Plus Economic solution Easy to be realized
TIME SELECTIVITY Minus Quick rise of setting levels High values of let-through energy
Energy selectivity Base concept Energy selectivity is based on the currentlimiting characteristics of some circuit breakers
104s 103s A
102s 10s 1s B 10-1s 10-2s
0.1kA
1kA
The ultimate current selectivity values is given by the manufacturer (Coordination tables)
10kA
Current-limiting circuit breaker has an extremely fast trip time, short enough to prevent the current from reaching its peak
Energy selectivity Example
104s 103s
Is = 20kA
A
Circuit breaker A conditions:
102s B 10s
I3=OFF
1s
S as for time selectivity
10-1s 10-2s
0.1kA
1kA
10kA
Energy selectivity Plus and minus PLUS High selectivity values Reduced tripping times Low stress and network disturbance
ENERGY SELECTIVITY MINUS Increasing of circuit breakers size
Zone selectivity Base concept
Zone selectivity is an evolution of the time selectivity, obtained by means of a electrical interlock between devices locking signal
The circuit breaker which detects a fault communicates this to the one on the supply side, sending a locking signal
Only the downstream circuit breaker opens, with no need to increase the intentional time delay
Fault
Zone selectivity Example
1 e n o Z
A
B Does Not Open
2 e n o Z
3 e n o Z
A Does Not Open
B
C
C Opens
Zone selectivity Specifications Zone selectivity needs:
a shielded twisted pair cable
an external source of 24V
dedicated trip units
PR223EF for Tmax T4, T5 and T6
PR332/P for Tmax T7 and T8
PR122/P and PR123/P for Emax
PR332/P and PR333/P for X1
1 e n o Z
2 e n o Z
3 e n o Z
Is up to 100kA for Tmax
Is up to Icw for Emax
It is possible to obtain zone selectivity between Tmax and Emax
Zone selectivity Plus and minus
PLUS Trip times reduced Low thermal and dynamic stress High number of hierarchical levels Can be made between same size circuit breakers
ZONE SELECTIVITY MINUS Cost and complexity of the installation Additional wiring and components
Agenda Low voltage selectivity with ABB circuit breakers
Definitions and Standards
Selectivity techniques
Back-up protection
Back-up protection What is back-up protection? Back-up protection (or cascading) is a type of coordination of two protective devices in series which is done in electrical installations where continuous operation is not an essential requirement.
Back-up protection excludes the use of selectivity!!!
Back-up protection Standards definition The definition of back-up is given by the IEC 60947-1 Standard: “Low voltage equipment Part 1: General rules for low voltage equipment”
IEC 60947-1 def. 2.5.24
“Back -up is a coordination of two overcurrent protective devices in series, where the protective device on the supply side, with or without the assistance of the other protective device, trips first in order to prevents any excessive stress on downstream devices”.
Back-up protection Base concept
Back-up is used by those who need to contain the plant costs The use of a current-limiting circuit breaker on the supply side permits the installation of lower performance circuit breakers on the load side
Both the continuity of service and the selectivity are sacrificed
Back-up protection Application example
T4L 250
Ik = 100 kA Icu (T4L+T1N) = 100kA
T4L 250
T4L 250
T4L 250
Icu = 120kA
T1N 160
T1N 160
T1N 160
Icu = 36kA
Back-up protection tables
Back-up protection Application example
T4L 250 A
B
C
Ik = 100kA
Icu (T4L+T1N) = 100kA
D
Ik = 100kA T1N 160
T1N 160
T1N 160
General power supply is always lost
Back-up protection Plus and minus
Plus
Economic solution Quick tripping times
BACK-UP PROTECTION Minus
No selectivity Low power quality
Example of Selectivity
~ T5H 630A
70kA
T3N 160A
36kA
Incoming = T5H 630A (70kA rating) Outgoing = T3N 160A (36kA rating) Results: The co-ordination resulted in a conditional shortcircuit of 65kA for the T3 mccb!
Iz
The discrimination is up to 20kA.
65kA
Example of Selectivity Discrimination
Example of Selectivity Back-Up
Example of Selectivity Meaning of Selectivity Value
T5H 70kA
T5H
70kA
T3N 36kA T3N
Fault level at Y is 20kA Y is 20kA
36kA
Example of Selectivity Meaning of Selectivity Value T5H
T3N
70kA
T5H 20kA T3N
36kA
Example of Selectivity Meaning of Selectivity Value
5kA fault
T5H ON
T3N Trip
T5H
70kA
T3N
36kA
5kA
Example of Selectivity Meaning of Selectivity Value
5kA fault
T5H ON
T3N Trip
10kA fault
ON
Trip
T5H
70kA
T3N
36kA
10kA
Example of Selectivity Meaning of Selectivity Value
5kA fault
T5H ON
T3N Trip
10kA fault
ON
Trip
20kA fault
Trip
Trip
T5H
70kA
T3N
36kA 20kA
Example of Selectivity Meaning of Selectivity Value
5kA fault
T5H ON
T3N Trip
10kA fault
ON
Trip
20kA fault
Trip
Trip
36kA fault
Trip
Trip
T5H
70kA
T3N
36kA 36kA
Example of Selectivity Meaning of Selectivity Value
5kA fault
T5H ON
T3N Trip
10kA fault
ON
Trip
20kA fault
Trip
Trip
36kA fault
Trip
Trip
65kA fault
Trip
Trip
T5H
70kA
T3N
36kA
65kA
MV/LV Transformer Substations Selection of Protective & Control Devices
Motor co-ordination ABB offers co-ordination tables
MV/LV Transformer Substations Selection of Protective & Control Devices
Co-ordination between CBs and switch-disconnectors 400V
T2S160
T1D160
Power Factor Correction
Power Factor Correction Generalities on Power Factor Correction In alternating current circuits, current is absorbed by a load which can be represented by two components:
The Active component
In phase with the supply voltage
Directly related to the output
The Reactive component
© ABB Group
Quadrature to the voltage Used to generate the flow necessary for the conversion of powers through the electric or magnetic field
In most installations the presence of inductive type loads, the current lags the active component (IR).
Power Factor Correction Generalities Generalities on Power Factor Correction In order to generate and transmit active power (P) a certain reactive power (Q) is essential for the conversion of the electrical energy but is not available to the load. The power generated and transmitted make up the apparent power (S). Power factor (cos ) is defined as the ratio between the active component (IR) and the total value of current (I). is the phase angle between the voltage and the current.
© ABB Group
Power Factor Correction Generalities Generalities on Power Factor Correction
© ABB Group
Power Factor Correction Typical Power Factors of some electrical equipment Generalities
© ABB Group
Power Factor Correction Advantages Generalities of Power Factor Correction
© ABB Group
Power Factor Correction Advantages Generalities of Power Factor Correction
Better utilization of electrical machines
Better utilization of cables
© ABB Group
Generators & transformers are sized according to the apparent power (S). With the same active power (P), the smaller the reactive power (Q) delivered, the apparent power will be smaller.
The reduction in current allows the use of smaller cables in the installation.
Power Factor Correction Generalities
Reduction in losses
Reduction in voltage drop
© ABB Group
By improving the power factor, power losses is reduced in all parts of the installation.
The higher the power factor the Voltage drop will be lower at the same level of Active power.
Power Factor Correction Generalities
Economical savings
© ABB Group
Power supply utilities apply penalties for energy used with poor factor. An improved power factor will reduce such penalties from the utilities.
Power Factor Correction Advantages Generalities of Power Factor Correction
Improve capacity of transformers and cables
By improving the power factor, you reduce the kVA load on the transformer and the current carried by the cables
Apparent Power (VA) e.g 2MVA Transformer At 100% capacity
Real Power (W) eg. 500kW Load
© ABB Group
Reactive Power (VAR) e.g Motors (inductive) 100kW at 0.7pf = 102kVAR Reactive Power (VAR) eg. 50kVAR Capacitors
Thus additional transformer capacity is available if upgrade or expansion is required in the future Or new cables might not be needed if new loads are connected to an existing switchboard
Power Factor Correction Different Methods
Distributed power factor correction
© ABB Group
It is achieved by connecting a capacitor bank properly sized according to the load and is connected directly to the terminals of the load.
Power Factor Correction Different Methods
Group power factor correction
© ABB Group
It is achieved by connecting a capacitor bank properly sized according to a group of loads and is connected to the upstream of the loads to be corrected.
Power Factor Correction Types of Power Factor correction Different Methods
Centralized power factor correction
© ABB Group
It is achieved by installing an automatic power factor correction bank capacitor bank directly to the main distribution boards.
Power Factor Correction Types of Power Factor correction Different Methods
Combined power factor correction
This solution is derived from a compromise between a distributed & centralized power factor correction.
© ABB Group
Distributed power factor correction is used mainly for higher loads and a smaller centralized power factor correction is used for the small loads.
Power Factor Correction Switching Protection Capacitor and Switching
Electrical switching phenomena
© ABB Group
The switching of a capacitor bank causes an electric transient due to the phenomena of electric charging of the bank.
The overcurrents at the moment of switching depends greatly on both the inductance of the upstream network as well as from the number of connected capacitor banks.
Power Factor Correction Switching Protection Capacitor and Switching
© ABB Group
Choice of protective device
Power Factor Correction Capacitor Switching
Resistance
Motor
In
In
In AC-1
Capacitor
AC-3
AC-6b
Power Factor Correction Capacitor Switching Single step capacitor
30 times In
In
Power Factor Correction Capacitor Switching Multi steps capacitor bank
> 100 times In
In
Power Factor Correction Contactor Sizing Contactor sizing: Thermal current + peak current Thermal current Up to 30% for harmonics and voltage fluctuations on main Up to 15% for tolerances on capacitor power Contactor have to support I th
I = 1.3 1. 3 x 1. 1.15 15 x I = 1.5 I t h n c n c
Power Factor Correction Example Example kVARh kVARh is billed if it is higher than the contracted contract ed level.
kVA kVA kVar
kW
Apparent power (kVA) (kVA) is significantly higher higher than the Active power (kW) The excess current causes losses (kWh) which is billed.
1MVA
The design of the installation has to be over-dimensioned. The installation requires 850kW at power factor of 0.75.
400V
The transformer will have to be overloaded to 850k / 0.75 = 1.133MVA. Current taken by the system is P I = = 1636A 3 * U * Cos Losses in the cables P = I2R Cos = 0.75 850kW Load © ABB Group
I = 1636A
Cos = 0.75 The Transformer, Transformer, Circuit breaker & Cable has to be increased.
Power Factor Correction Example Example kVA kVA
kVARh kVARh is reduced to lower than the t he contracted level or eliminated.
kVar
kW
Apparent power (kVA) (kVA) is significantly higher than the Active power (kW) The charges based on the contracted kVA demand demand is close to the active power.
1MVA
The installation requires 850kW at a power factor of 0.9. 400V
The transformer will not be overloaded to 850k / 0.90 = 945 kVA. Current taken by the system is P I = = 1364A 3 * U * Cos Losses in the cables P = I2R
Cos = 0.90 850kW Load © ABB Group
I = 1364A
Cos = 0.90 There is not need to increase the t he Transformer, Transformer, Circuit breaker & Cable.
Power Factor Correction Technical Application Paper
© ABB Group