This Document is Used to Verify the Sizing of Transformer for a Motor Starting.Full description
Full description
EARTHING CALCULATION FOR TOUCH AND STEP VOLTAGEFull description
Full description
To describe the voltage drop of street lighting.Full description
To describe the voltage drop of street lighting.
excel calculator
Lets you calculate voltage for holiday testerFull description
In this guide, a design engineer works on a converter drive design and determines the voltage change coefficient during the drive start, compares it to permissible levels and suggests solutions to ...
In this guide, a design engineer works on a converter drive design and determines the voltage change coefficient during the drive start, compares it to permissible levels and suggests solutions to ...
In this guide, a design engineer works on a converter drive design and determines the voltage change coefficient during the drive start, compares it to permissible levels and suggests solutions to ...Full description
Knee exercises from a Chikung perspective, article extracted from prestigiuos Qi magazine by Master Michael Tse
Full description
dislokasi sendi lutut. genu. pembagian anatomi dan posisional.Full description
1Full description
NiceFull description
Full description
Knee point calculation for 765kV CT's CT Ratio :3000-2000-1000-500/lA CT Class :PS Secondary Winding Resistance: · 15 ohm at 3000 tap · 10 ohm at 2000 tap . 5 ohm at 1000 tap . 2.5 ohm at 500 tap Length of line assumed =25 kms.
Where IF= Max. secondary fault current at zone-l reachpoint. X/R = Primary system reactance/resistance ratio System short circuit Fault Calculations System Impedance,Zs =Vs/ IF 765xl03
IF = 40 kA(Fault Level)
- ,J3x40x 103 =11.042 ohms
-.
Line parameters are Rr. = 1.9513 X 10-6 Pu/kM/Ckt
XL= 4.475 X 10-5pu/kM/ckt
]
On a 100 MVA ,765 kV Base
XL _ 4.475xlO-s RL -1.9513x10-6
= 22.93 =23
e=tan-I
4.475XlO-S
( 1.953
x 1O-{i
)
= 87.5°
Page 1 of 4
Knee point calculation for 765kV CT's Therefore ('
Xs = Zs sin 87.5° = 11.042 X 0.999 = 11.031 ohms Rs = Zs cos 87.5° = 11.042 X 0.0436 = 0.481 ohms Zs = 0.481 + j11.031 Line Impedance: Rr. = 1.9513 X 10-6 pulkM/ckt.: XL= 4.475 X 10-5pu/kM/ckt :
On a 100 MVA ,765 kV Base
Therefore Base Impedance =765 X 765/100 = 5852.25 ohms Rr. = 1.9513 X 10-6X 5852.25 = 0.01142 ohmslkM XL= 4.475 X 10-5X 5852.25 = 0.2619 ohmslkM For a Line length of25 kMs (zone-1 reach=20 kMs) Rr.' = 0.01142 X 20 = 0.2284 ohms XL'= 0.2619 X 20 = 5.238 ohms
Therefore Total Fault Impedance upto zone-1 reach point R= Rr.'+ Rs = 0.2284+0.481 = 0.7902 ohms X=Xs+ XL' = 11.031+ 5.238 = 16.269 ohms Z = 0.7094 + j 16.269 Z = 16.284 ohms Therefore Fault current at zone-1 reach
= IF' 765x103
- J3 x16.284 = 27123.12 A
IF'= 27.12 kA (fault level at zone-1 reach point)
Page 2 of 4
Knee point calculation for 765kV CT's Lead Burden: Cable Length= 800 m Lead resistance = 8.71 ohms/kM ( x 2.5 mm2 copper cable is used) Therefore 2R L
= 2x 800 x 8.71 = 6.968 2 1000
= 7.0ohms CT secondaryresistance, Rcr = 15.00 at 3000/1 A tap Knee point voltage requirement VK~0.6IF( 1
+;)Rcr +RL)
Relay burden is negligible .Therefore Rrelay=0. 27120 VK~ 0.6x-(1 +23)(15 +7.0) 3000 For 3000/1 A tap VK~ 2863.87Vat30001lTap Selected knee point voltage for 3000/1 A tap =6000 V(plese see note below) RCf ~15.00hm
Imag < 20mAatVK
"For 2000 A tap,
27120 VK(2000)=0.6x-x(I+23)(10+7.0) 2000
= 3319.5 V Selected knee point voltage for 2000/1 A tap = 4000V(same as that for 400 kV CTs) Note: 1. Since the requirement at 2000/1 A tap is 2V per turn,the selected knee point voltage for 3000/1 A tap is 6000V.This is in line with the knee point voltage requirement being specified for 400 kV CT's . 2. It is intended to use only 3000/1 A or 000/1 A taps for 765 kV line protection.
Page 3 of4
Knee point calculation for 765kV CT's 3. 1000/1 A and 500/1 A taps shall be used for Generator circuits (Protection Overall Differential,Overhead Line Differential). CT requirement for busbar protection IF
= 40 kA
VK~2IF(RCT+RL) For 3000 A tap Rcr = 15.0ohms Rr.= 7.0 ohms 40000 VK~2x-x(15.0+7.0) 3000
Selected VK at 3000/1 A tap = 3000V For 2000 A tap Rcr = 10.0 ohms Rr.= 7.0 ohms 40000 VK~2x-x(IO.0+7.0) 2000
Selected VK at 2000/1 A tap = 2000V VK~ 680V For 1000 A tap Rcr = 5.0 ohms Rr.= 7.0 ohms 40000 VK~2x-x(5.0+7.0) 1000
Selected VK at 1000/1 A tap = 1000V Note: 1. 500/1 A tap shall not be used for bus-bar protection. 2. 500/1 A tap shall be used for Generator circuit protection(Overall Differential, Overhead Line Differential)