Cable sizing calculation sheet with formulaFull description
Full description
Full description
11kV or 33kV cable sizing calculationFull description
Full description
Calcualted the MV Capacitor Calculation for the plant loadFull description
Full description
Full description
33kV cable sizing
Full description
Cable sizing guidelinesFull description
LV Cable sizing (1)Full description
Full description
Full description
CABLE SIZING CALCULATION FOR 2500kVA COMMON TRANSFORMER INCOMING CABLE CONSIDERATIONS: 1. Line to Line Voltage = 2. Frequency = 3. Max. Allowable Voltage Drop % of Line to Line Voltage Starting = Running = 4. Cable Overall Derating Factor D 5. Length of the cable, L =
4320 60
Volts Hz
15% 5% 0.7 100
(As per tender specification: CEM/ISGEC/700558-60- SECTION -II -Design basis-serial no.19) m (Assumed)
Transformer Parameters: Transformer Rating Transformer Efficiency at Full Load Hence, Transformer FLC Im
= = =
1600 kVA 0.97 kVA/(1.732*kV*Efficiency)
=
I/D
=
228.93 A
Cable Sizing Based on Ampacity: Cable equivalent current at 45 degree C, Ic Cable Size Selected Cable Rated Current in Air, Ca Cable Resistance at 90 deg. C (ohm/km) , R Cable Reactance (ohm/km) at 60 Hz , X No.of parallel cables required
327.05 A 2 185 mm
= = = = Ic/Ca
453 A 0.127 0.10056 1
CU, XLPE INSULATED, ARMOURED CABLE (As per KEI catalogue) (As per KEI Catalogue) (As per KEI Catalogue)
Cable Sizing Based on Shortcircuit withstanding capacity: A sample calculation has been done below for minimum cable size required for a motor feeder for the specified short circuit rating. As per IEC 60364-5-54, Clause No.543.1.1, S = (Isc x √t) / K Where, S: Cross sectional area, in Square milimeters Isc: Value (a.c. rms) of fault current for a fault of negligible impedance, which can flow through the protective device in amperes. t: operating time of the disconnecting device, in seconds. K: factor depend on the material of the protective conductor. Transformer Rating Full Load Current 4320V Symmentrical SC current Isc Operating time t Required Cross sectional Area S
= = = =
1600 228.93 40000 0.16 111.89
K - Factor
XLPE Cables PVC Cables
kVA A A S Sqmm
Copper
Aluminium
143 115
94 76
Cable Voltage Drop: Transformer Running Voltage Drop (%) = = Where,
L *Sqrt(3) * IFL( R cosφr+X sin φr) (VL-L/100)* 1000 *No.of runs 0.12 %
L:Length of the cable in metres IFL: Full load current in Amps. IST: Starting current in Amps.
The % of Voltage drop is within the limit. Hence, the Selected Cable Size is 3.6/6 (7.2)kV, 1RX3Cx185 sq.mm, (2XFY) XLPE, Flat Armoured,Copper cable