External Alarm Solution Huawei OTA Project October 2014
1. BTS External Alarms Solution
1. BTS External Alarms Solution
BBU
UEIU
UPEU
Board
BBU Side PIN Port <—>Orange & White 1 <—> Orange 2 <—>Green & White 3 <—> Green 6 RJ45 <—>Blue & White 5 Connector <—> Blue 4 <—>Brown & White 7 <—> Brown 8 Color of core-cable
UIEU UPEU
Pin on the RJ45 BBU Alarm Port Connector in BBU X1.1
EXT-ALM1
EXT-ALM0
X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8 X1.1 X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8
Indicator
Port
Type
EXT-ALM0
0
RJ45
EXT-ALM1
1
RJ45
EXT-ALM0
2
RJ45
EXT-ALM1
3
RJ45
Wire Color
White and orange Orange White and green Green White and blue Blue White and brown Brown White and orange Orange White and green Green White and blue Blue White and brown Brown
Wire Type
Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair
Pin on the DDF
Description
X2.1
Boolean input 4+
X2.2
Boolean input 4- (GND)
X2.3 X2.6 X2.5 X2.4 X2.7 X2.8 X2.1 X2.2 X2.3 X2.6 X2.5 X2.4 X2.7 X2.8
Boolean input 5+ Boolean input 5- (GND) Boolean input 6+ Boolean input 6- (GND) Boolean input 7+ Boolean input 7- (GND) Boolean input 0+ Boolean input 0+ (GND) Boolean input 1+ Boolean input 1- (GND) Boolean input 2+ Boolean input 2- (GND) Boolean input 3+ Boolean input 3- (GND)
Alarm Name High temperature (35 ) Very high temperature (40 ) Air Cond. Alarm Fire alarm Smoke Alarm Door Open GE working Battery status(battery deep discharge) Commercial power down(Main power down) Rectifier fault Overvoltage protection °
°
Alarm Name
Commercial power down (Main power down) DC output overvoltage/under voltage alarm
Rectifier fault alarm Door status alarm (PS) TCU fault alarm (HAU/fan/TEC fault)
Alarm ID 65033 65034 65035 65036 65037 65038 65039 65040 65041 65042 65043
65049 65050 65051 65055 65056
Alarm Name Category BBU Pin-arrangement High temperature (35 ) Major UEIU hite and orange/Orange 0 Very high temperature (40 ) Critical UEIU hite and green/Green 1 Air Cond. Alarm Major UEIU hite and Blue/Blue 2 Fire alarm Critical UEIU hite and brown/Brown 3 Smoke Alarm Minor UEIU hite and orange/Orange 4 Door Open Minor UEIU hite and green/Green 5 GE working Critical UEIU hite and Blue/Blue 6 Battery status(battery deep discharge) Critical UEIU hite and brown/Brown 7 Commercial power down(Main power down) Critical UPEU White and orange/Orange 0 Rectifier fault Critical UPEU hite and green/Green 1 Overvoltage protection Major UPEU hite and Blue/Blue 2 °
°
Commercial power down (Main power down) DC output under voltage alarm Rectifier fault alarm Door status alarm (PS) TCU fault alarm port (HAU/fan/TEC fault)
Critical
UPEU
hite and orange/Orange
0
Critical
UPEU
hite and Blue/Blue hite and green/Green
1
Critical Minor
UPEU UPEU
hite and Blue/Blue
2 6
Critical
UPEU
hite and brown/Brown
7
Custom DDF port arg. 8 9 7 UEIU EXT-ALM0 5 12 3 16 UEIU EXT ALM1 11
UPEU EXT-ALM0
UPEU EXT-ALM0 UPEU EXT-ALM1
1 2 4
Indoor ( Reuse Power) √ √ √ √ √ √ √
Indoor (Swap Power) √ √ √ √ √ √ √
Outdoor (Reuse Power)
Outdoor (Swap Power)
√
√
√
√
√ √ √
√ √ √
1
√
√
11(4)
√
√
2 14
√
√ √
15
√
UPEU :
UEIU :
0 - High temperature (35
1 - Very high temperature (40
0 to 3
0 - Commercial power down(Main power down)
) (DDF port 8)
(DDF port 1)
) (DDF port 9)
0 to 3
2 - Air Cond. Alarm (DDF port 7)
1 - Rectifier fault (DDF port 2) 2 - Overvoltage protection (DDF port 4)
3 - Fire alarm (DDF port 5)
3-
4 to 7
4 - Smoke Alarm (DDF port 12)
4-
5 - Door Open (DDF port 3)
5-
6 - GE working (DDF port 16)
4 to 7
7 - Battery status(battery deep discharge) (DDF port 11)
67-
UPEU :
UEIU :
0 - Commercial power down(Main power down) 1 - Rectifier fault
0 to 3
2 - Overvoltage protection 3-
6 - GE working 7 - Battery status(battery deep discharge)
4 to 7
UEIU :
0 - High temperature (35
) (DDF port 8)
1 - Very high temperature (40
0 to 3
) (DDF port 9)
2 - Air Cond. Alarm (DDF port 7) 3 - Fi re Alarm (DDF port 5)
4 - Smoke Alarm (DDF port 12) 5 - Door Open (DDF port 3)
4 to 7
6 - GE working (DDF port 16) 7 -Battery status(battery deep discharge) (DDF port 11)
UPEU :
0 - Commercial power down (Main power down) (DDF port 1) BTS3900
1 - Rectifier fault alarm (DDF port 2)
0 to 3
DDF
External alarm cable
2 – DC input under voltage alarm (DDF port 4)
UEIU :
6 - GE working
4 to 7
USLP
UPEU
BTS3900A
0 - Commercial power down (Main power down) 1 - Rectifier fault alarm
External alarm cable
0 to 3
2 - DC output undervoltage alarm
6 - Door status alarm (PS) 7 - TCU fault alarm (HAU/fan/TEC fault)
4 to 7
ALM0
ALM1 BBU
OUT0
OUT1
ALM1
ALM0
Board 1
USLP2 OUT0 OUT1
Board 0 To Custom DDF/PS
BBU Alarm Port/USLP2 Port
USLP2 Side
Color of core-cable <—>Orange & White
PIN 1
<—> Orange
2
<—>Green & White
3
<—> Green
6
<—>Blue & White
5
<—> Blue
4
<—>Brown & White
7
<—> Brown
8
Port
EXT ALM1/OUT1
RJ45 Connector EXT ALM0/OUT0
Pin on the RJ45 Connector in USLP2
Wire Color
X1.1
White and orange
X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8 X1.1 X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8
Orange White and green Green White and blue Blue White and brown Brown White and orange Orange White and green Green White and blue Blue White and brown Brown
Wire Type
USLP2 port IN0.1
Twisted pair Twisted pair Twisted pair Twisted pair
Twisted pair Twisted pair Twisted pair Twisted pair
IN0.2
IN1.1 IN1.2 IN0.4 IN0.3 IN1.3 IN1.4 IN2.1 IN2.2 IN3.1 IN3.2 IN2.4 IN2.3 IN3.3 IN3.4
Alarm ID 65033 65034 65035 65036 65037 65038 65039 65040 65041 65042 65043
65049 65051 65050 65055 65056
Alarm Name High temperature (35 ) Very high temperature (40 ) Air Cond. Alarm Fire alarm Smoke Alarm Door Open GE working Battery status(battery deep discharge) Commercial power down(Main power down) Rectifier fault Overvoltage protection °
°
Commercial power down (Main power down) Rectifier fault alarm DC output under voltage alarm Door status alarm (PS) TCU fault alarm port (HAU/fan/TEC fault)
Category Major Critical Major Critical Minor Minor Critical
UEIU UEIU UEIU UEIU UEIU UEIU UEIU
BBU Pin-arrangement White and orange/Orange 0 White and green/Green 1 White and Blue/Blue 2 White and brown/Brown 3 White and orange/Orange 4 White and green/Green 5 White and Blue/Blue 6
Critical
UEIU White and brown/Brown
7
Critical Critical Major
UPEU White and orange/Orange UPEU White and green/Green UPEU White and Blue/Blue
0 1 2
Critical Critical
UPEU White and orange/Orange UPEU White and green/Green
0 1
Critical Minor Critical
UPEU White and Blue/Blue UPEU White and Blue/Blue UPEU White and brown/Brown
2 6 7
UEIU EXT-ALM0
Custom DDF port arg. 8 9 7 5 12 3 16
Outdoor (Reuse Power)
USLP2 USLP2 OUT to Board UEP/IU
IN3.1/IN3.2
OUT0
N2.4/IN2.3
IN3.3/IN3.4 IN0.1/IN0.2
Board 1
IN1.1/IN1.2
√
11
√
UPEU EXT-ALM0
1 2 4
√ √ √
UPEU EXT-ALM1
USLP2 IN IN2.1/IN2.2
UEIU EXT ALM1
UPEU EXT-ALM0
Outdoor (Swap Power)
√
OUT1
IN0.4/IN0.3 IN1.3/IN1.4 IN2.1/IN2.2
OUT0
IN3.1/IN3.2 N2.4/IN2.3
IN2.1/IN2.2
1 2
√ √
11(4) 14
√ √
IN0.4/IN0.3
15
√
IN1.3/IN1.4
IN3.1/IN3.2
Board 0 OUT0
N2.4/IN2.3
OUT1
Board 1: USLP 2 OUT 0
UEIU EXT-ALM0
Board 1: USLP 2 OUT 1
UEIU EXT-ALM1
Board 1
Board 0
Board 0: USLP 2 OUT 1
Board 0: USLP 2 OUT 0
UPEU EXT-ALM1
UPEU EXT-ALM0
Board 1
Board 0
GE working
Rectifier fault alarm Battery status(battery deep discharge)
Main power
Overvoltage Protection
Board 1
Board 0
GE working
Door status alarm (Battery Rack)
Rectifier fault alarm TCU fault alarm port (HAU/fan/ TEC fault)
Main power
DC input under voltage Alarm
Board 1
Board 0
Main power
DC output overvoltage under voltage alarm (BDD)
Rectifier fault alarm
Door status alarm (Battery Rack)
TCU fault alarm
Scenario 1,2 :
Scenario 3,4 :
Define all external alarms for BTS, once per BSC: SET ENVALMPARA:AID=65033, ANM="High temperature (35 )", ALVL=Major, ASS=env; SET ENVALMPARA:AID=65034, ANM="Very high temperature (40 )", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65035, ANM="Air Con d. Alarm", ALVL=Major, ASS=env; SET ENVALMPARA:AID=65036, ANM="Fire alarm", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65037, ANM="Smoke Alarm", ALVL=Minor, ASS=env; SET ENVALMPARA:AID=65038, ANM="Door Open", ALVL=Minor, ASS=env; SET ENVALMPARA:AID=65039, ANM="GE working", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65040, ANM="Battery status(battery de ep discharge)", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65041, ANM="Commercial power down(Main power do wn)", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65042, ANM="Rectifier fault", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65043, ANM="Overvoltage protection", ALVL=Major, ASS=env; °
°
SET ENVALMPARA:AID=65049, ANM="Commercial power down (Main power down) ", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65050, ANM="DC output overvoltage/un der voltage alarm", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65051, ANM="Rectifier fault alarm ", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65052, ANM="AC/DC surge protection alarm", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65053, ANM="Load/battery fuse and circuit failure alarm", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65054, ANM="Battery over-temperature and un der-temperature alarm", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65055, ANM="Door status alarm (PS)", ALVL=Minor, ASS=env; SET ENVALMPARA:AID=65056, ANM="TCU fault alarm port (HAU/fan/TEC fault)", ALVL=Critical, ASS=env;
2. BSC External Alarms Solution
BSC6900 J2
EMUA
5 to 8
1 to 4
(1) Six ports for Boolean signal output
(2) Port for water sensors
(3) Port for door status sensors
(4) Port for smoke sensors
(5) Port for humidity/temperature sensors (6) Port for infrared sensors
Power
(7) Four ports for analog signal sensors
(8) RS-232 port
(9) Active/standby power port
(10) Two RS-485 ports (12) Thirty-two ports for Boolean signal sensors
(11) Grounding screw
OTA request
(2) Port for water sensors
(3) Port for door status sensors
(4) Port for smoke sensors
(5) Port for humidity/temperature sensors
Alarm ID Alarm Name
Severity
Alarm Type
20043
Water Damage
Critical
Fault
20045
Ambient Temperature Abnormal
Major
Fault
20046
Ambient Humidity Abnormal
Major
Fault
20047
Smoke
Critical
Fault
20048
Theft Proof
Critical
Fault
Alarm ID
Alarm Name
Alarm Severity
Alarm Type
Cabinet
Subrack
Port
Alarm Voltage
65334
Air Cond Alarm
Major
Fault
0
0
1
High
65335
HEAT_VENT
Major
Fault
0
0
2
High
65336
High Temp 35
65337
High Temp 40
65338
°
Major
Alarm
0
0
3
High
°
Critical
Alarm
0
0
4
High
Main Power Down
Critical
Alarm
0
0
5
High
65339
Rectifier Fault
Major
Alarm
0
0
6
High
65340
Battery discharge Fault Critical
Alarm
0
0
7
High
65341
GE Fault
Critical
Alarm
0
0
8
High
65342
Door Open
Minor
Alarm
0
0
9
High
humidity/temperature ON-ON SW_THE
ON-ON-OFF-OFF
SW_ADDR
water/smoke/optical/gate OFF-ON-ON-ON
SW_BKE
BSC External Alarm Name Definition SET ENVALMPARA:AID=65334, ANM="Air Cond Alarm", ALVL=Major, ASS=env; SET ENVALMPARA:AID=65335, ANM="HEAT_VENT", ALVL=Critical, ASS=power; SET ENVALMPARA:AID=65336, ANM=“ High temperature (35 )", ALVL=Major, ASS=env; SET ENVALMPARA:AID=65337, ANM ="Very high temperature (40 )", ALVL=Critical, ASS=env; SET ENVALMPARA:AID=65338, ANM="Main Power Down", ALVL=Critical, ASS=power; SET ENVALMPARA:AID=65339, ANM="Rectifier Fault", ALVL=Major, ASS=power; SET ENVALMPARA:AID=65340, ANM="Battery discharge Fault", ALVL=Critical, ASS=power; SET ENVALMPARA:AID=65341, ANM="GE Fault", ALVL=Critical, ASS=power; SET ENVALMPARA:AID=65342, ANM="Door Open", ALVL=Minor, ASS=env; °
°
BSC external alarm activation Script SET SET SET SET SET SET SET SET SET
ALMPORT:SRN=0, ALMPORT:SRN=0, ALMPORT:SRN=0, ALMPORT:SRN=0, ALMPORT:SRN=0, ALMPORT:SRN=0, ALMPORT:SRN=0, ALMPORT:SRN=0, ALMPORT:SRN=0,
PN=1, PN=2, PN=3, PN=4, PN=5, PN=6, PN=7, PN=8, PN=9,
PT=BOOL, PT=BOOL, PT=BOOL, PT=BOOL, PT=BOOL, PT=BOOL, PT=BOOL, PT=BOOL, PT=BOOL,
SW=OPEN, SW=OPEN, SW=OPEN, SW=OPEN, SW=OPEN, SW=OPEN, SW=OPEN, SW=OPEN, SW=OPEN,
AID=65334, AID=65335, AID=65336, AID=65337, AID=65338, AID=65339, AID=65340, AID=65341, AID=65342,
AVOL=HIGH; AVOL=HIGH; AVOL=HIGH; AVOL=HIGH; AVOL=HIGH; AVOL=HIGH; AVOL=HIGH; AVOL=HIGH; AVOL=HIGH;
•
The remaining alarm can be used for the special cases as: Power Down for a Transmission site.
•
For 3G overlay sites: Huawei PS alarms will be connected to the existing 2G BTS.
•
The status (open or closed) can be changed according to each alarm.
•
More special alarms can be created according to each actual BSC alarms (exp: alarm power for site Trans, or others);
•
Special modifications can be done on the created alarms
•
For 3G only sites (in the future), the external alarms will be connected to the 3G NodeB.