DOCUMENT TITLE RELAY SETTING CHART FOR 33KV SWITCHYARD
DOCUMENT NO.
IKE-ISGEC-KWL61-DOC-233
REVISION
00
DATE
11.10.2013
NO. OF SHEETS
PREPARED BY
CHECKED BY
APPROVED BY
**Sheets (Including Title Sheet)
ARD
KBD
ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No Protection Description Type ref. 33KV Transformer Control and Relay Panel I 1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Protection Relay
Setting Range Differential Protection (87GT) Idiff>=0.1-2.5 Iref Idiff>=2.5-30 Iref Idiff>>>=2.5-30 Iref m1: 0.15-1.5 m2: 0.15-1.5 IR,m2 (1.5-10.0 Iref) Op.del, trip signal:0-100S Restricted earthfault protection(64R) Effective setting: 10% High Impedance relay Stabilising resistor (0-1000) Ohm
2
50/51 50N/51N 67/67N, 50LBB 78, 27Z, 59, 81 60, 81R, 99, 27
PREPARED BY: ARD
Numerical Interconnection Protection Relay
MICOM P341
Recommended Setting
Idiff>:0.1
Remarks
LV: CTR: 500/1A HV: CTR: 200/1 A NCTR: *** A
m1: 0.2 m2: 0.7 4
10%In NCTR: *** A Rst: 200
ohm
Overcurrent protection (51) In: 0.08-4In T: 0-100 sec
0.75*In 0.1
sec
IDMT characterictics 3 Sec Curve
Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec
6*In 0
sec (Inst)
CTR: 200/1A PTR: 33KV/110V
Earth fault protection (51N) Ie: 0.08-4In T: 0-100 sec
0.2*In 0.1
Sec
IDMT characterictics 3 Sec Curve
Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
0.3*In 0.5
sec
1 of 10 CHECKED BY: KBD
APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No
Protection Description Type ref. 33KV Transformer Control and Relay Panel
PREPARED BY: ARD
Recommended Setting
Setting Range Dir. Overcurrent protection (67) In: 0.08-32In T: 0-100 sec
0.75*In 0.35
Dir. Earth fault protection (67N) Ie: 0.08-32In T: 0-100 sec
0.1*In 0.35
sec
Under volatge protection (27) U<: 10-120V T: 0-100 sec
80 2
V sec
Over voltage protection (59) U>: 60-185V T: 0-100 sec
121 3
V sec
Under frequency protection (81U) f<: 45-65Hz T: 0-100 sec
47.7 2
Hz sec
Over frequency protection (81O) f>: 45-65Hz T: 0-100 sec
52 2
Hz sec
Local Breaker back-up protection (50LBB) In: 0.4-4*In Time delay
1*In 0.3
sec
df/dt protection (81R) df/dt: 0.1-10Hz/sec T: 0-100 sec
4 Inst
Hz/ sec Inst
2 of 10 CHECKED BY: KBD
Remarks RCA: 30 deg
sec
RCA: 45 deg
PTR: 33KV/110V
CTR: 200/1A
APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No
Protection Description Type ref. 33KV Transformer Control and Relay Panel
Recommended Setting
Setting Range Dead band lower frequency 45-65Hz
Remarks
49
Hz
Dead band upper frequency 45-65Hz
51
Hz
Vector surge protection (78) dv/dt: 2-30 deg
7
deg
Standby Earth fault protection (51G) Ie: 0.08-4In T: 0-100 sec
0.3 * In 0.3
Sec
CTR: 200/1 A IDMT curve (3 sec)
0.9 * In 0.1
Sec
IDMT curve (3 sec)
6 * In 0
Sec
CTR: 500 / 1 A PTR: 11kV / 110 V
Voltage Balance Relay (60) *** *** Overfluxing Protection Relay (99) *** ***
3
50/51 Numerical 50N/51N protection relay (LV side of GT)
MICOM P111L IDMT overcurrent protection (51) In: 0.08-4In TMS: 0.025-1 Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec
PREPARED BY: ARD
3 of 10 CHECKED BY: KBD
APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No
4
Protection Description Type ref. 33KV Transformer Control and Relay Panel
27, 59 59D
Numerical protection relay
MICOM P921
Recommended Setting
Setting Range IDMT Earth fault protection (51N) Ie: 0.08-4In TMS: 0.1-1
0.2 * In 0.3
Sec
Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
0.3 * In 0.3
Sec
Under voltage protection (27) U<: 10-120V T: 0-100 sec
0.8 0.5
sec
Over voltage protection (59) U>: 60-185V T: 0-100 sec
1.1 0.5
sec
Neutral displacement protection (59DLV) V: 5.4 -20V TMS
5.4 0.1
V sec
Remarks IDMT curve (3 sec)
NOTE: a) All settings are referred with respect to secondary values. b) All the other functions which are not mentioned in this chart shall be disabled.
PREPARED BY: ARD
4 of 10 CHECKED BY: KBD
APPROVED BY: ABH
CLIENT
M/s. KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA
CONSULTANT
M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH
EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP
PROJECT
EPC ELECTRICAL CONTRACTOR
1x18 MW CO-GEN POWER PLANT
IKE ELECTRIC PVT. LTD. 601 - 602, MARIEGOLD NECO GARDENS, VIMAN NAGAR, PUNE - 411 014 MAHARASHTRA INDIA PHONE - 020 - 66290300 / 301 TELEFAX - 020 - 66290302
DOCUMENT TITLE RELAY SETTING CHART FOR 132KV SWITCHYARD
DOCUMENT NO.
IKE-ISGEC-KWL61-DOC-133
REVISION
00
DATE
11.10.2013
NO. OF SHEETS
PREPARED BY
CHECKED BY
APPROVED BY
**Sheets (Including Title Sheet)
ARD
KBD
ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Sr.No Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel I 1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT) Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 Idiff>=2.5-30 Iref Idiff>>>=2.5-30 Iref m1: 0.15-1.5 m1: 0.2 m2: 0.15-1.5 m2: 0.7 IR, m2 (1.5-10.0 Iref) 4 Op.del, trip signal:0-100S Restricted earthfault protection(64R) Effective setting: 10% High Impedance relay Stabilising resistor (0-1000) Ohm 2
PREPARED BY: ARD
50/51 50N/51N 67/67N, 50LBB 78, 27Z, 59, 81 60, 81R, 99, 27
Numerical Interconnection Protection Relay
MICOM P341
LV: CTR: 1500/1A HV: CTR: 150/1 A NCTR: *** A
10%In NCTR: *** A Rst:200
Overcurrent protection (51) In: 0.08-4In T: 0-100 sec
0.75*In 0.1
Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec
6*In 0
Earth fault protection (51N) Ie: 0.08-4In T: 0-100 sec Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
1 of 10 CHECKED BY: KBD
Remarks
ohm IDMT characterictics 3 Sec Curve
sec (Inst)
CTR: 150/1A PTR: 132KV/110V
0.2*In 0.1
Sec
IDMT characterictics 3 Sec Curve
0.3*In 0.5
sec
APPROVED BY: ABH
Sr.No
PREPARED BY: ARD
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel Dir. Overcurrent protection (67) In: 0.08-32In 0.75*In T: 0-100 sec 0.35 sec Dir. Earth fault protection (67N) Ie: 0.08-32In T: 0-100 sec
0.1*In 0.35
sec
Under volatge protection (27) U<: 10-120V T: 0-100 sec
80 2
V sec
Over voltage protection (59) U>: 60-185V T: 0-100 sec
121 3
V sec
Under frequency protection (81U) f<: 45-65Hz T: 0-100 sec
47.7 2
Hz sec
Over frequency protection (81O) f>: 45-65Hz T: 0-100 sec
52 2
Hz sec
Local Breaker back-up protection (50LBB) In: 0.4-4*In Time delay
1*In 0.3
sec
df/dt protection (81R) df/dt: 0.1-10Hz/sec T: 0-100 sec
4 Inst
2 of 10 CHECKED BY: KBD
Remarks RCA: 30 deg
RCA: 45 deg
PTR: 132KV/110V
CTR: 150/1A
Hz/ sec
APPROVED BY: ABH
Sr.No
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel Dead band lower frequency 45-65Hz 49 Hz Dead band upper frequency 45-65Hz
Remarks
51
Hz
Vector surge protection (78) dv/dt: 2-30 deg
7
deg
Standby Earth fault protection (51G) Ie: 0.08-4In T: 0-100 sec
0.3 * In 0.3
Sec
CTR: 150/1 A IDMT curve (3 sec)
0.7 * In 0.1
Sec
IDMT curve (3 sec)
6 * In 0
Sec
CTR: 1500 / 1 A PTR: 11kV / 110 V
Voltage Balance Relay (60) *** *** Overfluxing Protection Relay (99) *** ***
3
50/51 50N/51N (LV side of GT)
Numerical protection relay
MICOM P111L IDMT overcurrent protection (51) In: 0.08-4In TMS: 0.025-1 Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec
PREPARED BY: ARD
3 of 10 CHECKED BY: KBD
APPROVED BY: ABH
Sr.No
4
5
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel IDMT Earth fault protection (51N) Ie: 0.08-4In 0.2 * In TMS: 0.1-1 0.3 Sec
50/51 Numerical 50N/51N protection relay (HV side of GT)
27, 59 59D
Numerical protection relay
MICOM P127
MICOM P921
Remarks IDMT curve (3 sec)
Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
0.3 * In 0.3
Sec
IDMT overcurrent protection (51) In: 0.08-4In TMS: 0.025-1
0.7 * In 0.1
Sec
IDMT curve (3 sec)
Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec
6 * In 0
Sec
CTR: 1500 / 1 A PTR: 132kV / 110 V
IDMT Earth fault protection (51N) Ie: 0.08-4In TMS: 0.1-1
0.2 * In 0.3
Sec
Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
0.3 * In 0.3
Sec
Under voltage protection (27) U<: 10-120V T: 0-100 sec
0.8 0.5
sec
Over voltage protection (59) U>: 60-185V T: 0-100 sec
1.1 0.5
sec
Neutral displacement protection (59DLV) V: 5.4 -20V TMS
5.4 0.1
V sec
IDMT curve (3 sec)
NOTE: a) All settings are referred with respect to secondary values. b) All the other functions which are not mentioned in this chart shall be disabled.
PREPARED BY: ARD
4 of 10 CHECKED BY: KBD
APPROVED BY: ABH