Section 6: Static Switch Operation & Control
Chapter 1 - Static Switch Principles
1.1 Introduction ........................................ .............................................................. ............................................ ................................ .......... 6-1 1.2 Static switch construction ......................................................... ......................................................................... ................ 6-2 1.3 Static switch control system .......................................... ................................................................ ........................... ..... 6-4 1.3.1 Control Control system overview ............................................ ............................................................. ................. 6-4 1.3.3 Control Control power supplies supplies ........................................... ................................................................ ..................... 6-7 Chapter 2 - Static Switch Driver Board (4542043 Z)
2.1 Chapter overview ........................................ ............................................................. ........................................... ........................ .. 6-9 2.2 General description ........................................ .............................................................. ........................................... ..................... 6-9 2.2.1 Circuit board board functions ............................................. ................................................................ ................... 6-9 2.2.2 Input/Output connections connections ............................................................. ............................................................. 6-9 2.2.3 Block Diagram ...................................................... ........................................................................... ..................... 6-10 2.3 Detailed circuit description ........................................ .............................................................. ............................ ...... 6-11 2.3.1 Introduction ...................................................... ............................................................................. .......................... ... 6-11 2.4 Summary information ........................................................... ............................................................................. .................. 6-15 Chapter 3 - Static Switch Driver Board (4542041 X)
3.1 Chapter overview ........................................ ............................................................. ........................................... ..........................17 ....17 3.2 General Gene ral description ........................................ .............................................................. ............................................ .......................17 .17 3.2.1 Circuit board functions ............................................... ..................................................................17 ...................17 3.2.2 Input/Output connections c onnections .............................................. ...............................................................17 .................17 3.2.3 Block Diagram Diagra m ......................................... ................................................................ ......................................18 ...............18 3.3 Detailed circuit description .......................................... ................................................................. ..............................19 .......19 3.3.1 Introduction ......................................... ................................................................ ...........................................19 ....................19 3.4 Summary information .......................................... ................................................................. .......................................23 ................23
S-6.FM5 - Issue 2 Dated 21/08/97
i
SECTION 6 - St at i c Sw Sw i t ch ch Op er at at io io n & Co n tr tr o l
ii
7200 Ser i es es UPS Ser v i c e Man u al
S-6.FM5 - Issue 2 Dated 21/08/97 21/08/97
Section 6:
Chapter 1 - Static Switch Principles
1.1
Introduction The static switch assembly is responsible for controlling the transfer of critical load power between the bypass mains supply and the inverter output supply. Figure 6-1: Static switch power block Static Switch As sem bl y Static Switch
Bypass Mains Supply
Bypass-Side
Static Switch Driver Board
UPS Logic Board
Inverter Output Supply
Static Switch Inverter-Side
Critical Load Supply
In order to perform this function, the static switch assembly contains two 3-phase switching circuits; one is connected between the UPS output switch and the bypass mains supply, and the other between the UPS output switch and the inverter supply (See Figure 6-1). For reasons of clarity, these are referred to in this manual as the “bypass-side” and “inverter-side” static switches respectively. Bypass-side static switch
The bypass-side static switch comprises a pair of inverse-parallel-configured SCRs connected in series with each bypass mains supply line (See Figure 6-2). Figure 6-2: Bypass-side static switch
U Bypass Mains Supply
To Critical Load
V W
Static Switch Driver Board
s6-c1.f m5 - Issu e 2 Dated 21/08/97
6-1
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 1 - Static Switch Principles
7200 Seri es UPS Service Manual
When the static switch control logic decides to connect the load to the bypass mains supply it signals the Static Switch Driver Board to trigger all six SCRs simultaneously; thus allowing passage of the bypass supply a.c. mains through to the critical load – i.e. all six SCRs receive a gate drive signal for the whole time that the ‘bypass-side’ is required to be turned on. Inverter-side static switch
The term “static switch” might be considered a misnomer when describing the ‘inverter-side’ circuit; as in a standard 7200 module this normally comprises a straightforward three-phase circuit breaker connected in series with the inverter output. If necessary, provision has been made to allow this contactor to be re placed with a solid state circuit (as used in the bypass-side static switch) as the product is developed. The contactor is controlled by the Static Switch Driver Board.
1.2
Static switch constru ction The static switch power components and the rectifier power components are assembled on the same heatsink , as illustrated below. Figure 6-3: Static switch assembly wiring details
4 5 4 2 0 4 3 Z
6-2
s6-c1.f m5 - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vice Man ual
SECTION 6 - Static Swit ch Operation & Con tr ol CHAPTER 1 - Static Switch Principles
Figure 6-4: Static switch construction
Connections to snubber boards and gate drivers
Bypass SCRs
S S D A E P E Y F B S C I N I T A A M T S h P - D 3 E E R F E I S F I N T I A C M E R
RECTIFIER OUTPUT Gate Driver (trigger) board
Snubber board
4 5 4 2 0 4 3 Z
s6-c1.f m5 - Issu e 2 Dated 21/08/97
6-3
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 1 - Static Switch Principles
7200 Seri es UPS Service Manual
Figure 6-5: System control overview
Load U-Phase Mains
U-Phase Inverter
ON
ON Transfer Logic PCB Logic Boards
Mains-side switch enable
Transfer Contr ol
Inverter-side switch enable
a) Bypass voltage OK (±10%)
Transfer Mains-to-Inverter
a) Inverter voltage OK (±10%)
b) No bypass frequency error
a) Sync OK (Inv/Mains ±9° with respect to each other
b) No inverter frequency error
c) No Open-circuit bypass SCR d) Bypass Disable Switch “enabled” – i.e. not in “inhibit” position. e) Permission to close static bypass gained from Parallel Logic Board (in 1+1 system only)
c) No Overload timeout 150% (1 min) 125% (10 min) 110% (1 Hr) 101% (9 Hrs)
b) Inverter voltage OK (±10%) c) Parallel condition satisfactory (1+1 system only) (a) + (b) + (c) = OK to transfer
d) Inverter Disable Switch “enabled” – i.e. not in “inhibit” position.
Transfer Inverter-to-Mains a) Critical bus volts fail (±10%)
e) Permission to close output contactor gained from Parallel Logic Board (in 1+1 system only)
b) Sync OK = No break Sync not OK = 1 cycle break
Transfer Lockout a) More than 8 transfer attempt in 1 minute = load locked on bypass
1.3 1.3.1
Static switch control system Contro l system overview Figure 6-6 illustrates the basic static switch control circuit. The decision making logic which determines whether to close the ‘bypass-side’ or ‘inverter-side’ static switch is contained on the UPS Logic Board under software control – (see chart 7-12 on page 7-183) – and provides the Static Switch Driver Board with independent “load on bypass” and “load on inverter” command signals. The Static Switch Driver Board processes these signals and provides suitable outputs to control the ‘bypass-side’ SCRs and ‘inverter-side’ contactor.
6-4
s6-c1.f m5 - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vice Man ual
SECTION 6 - Static Swit ch Operation & Con tr ol CHAPTER 1 - Static Switch Principles
Figure 6-6: Static switch control system Bypass-side Static Switch Bypass Mains Supply e g a t l o v s s a p y B
Bypass Supply
Output voltage sense
e s n e s
Output current sense
High Voltage Interface Board
UPS Logic Board
Static Switch Driver Board
Operator Logic Board e s n e s t n e r r u c r e t r e v n I
Operator Control Panel
e s n e s y r a i l i x u A 1 K
e s n e s e g a t l o v r e t r e v n I
DC Bus Pos 3 Phase Power Inverter
d a o L l a c i t i r C
Output Tfrmr
DC Bus Neg Inverter-side Contactor (K1)
1.3.1.1
Analogue contr ol signals Inverter voltage sense
The 3-phase inverter voltage is sensed at a point between the output transformer and inverter-side static switch (contactor), and should therefore be at the nominal UPS output voltage whenever the inverter is operating. The three independent line-to-neutral sense signals are attenuated to 1% on the High Voltage Interface Board and then passed to the UPS Logic Board where they are converted to a digital form and monitored by the board’s microprocessor system. Note: these same signals also pass straight through the UPS Logic Board to the Inverter Logic Board where they serve as the output voltage feedback signals. Bypass mains voltage sense
The 3-phase bypass mains voltage is sensed at a point between the bypass supply isolator and the ‘bypass-side’ static switch, and should therefore be at the nominal mains voltage whenever the bypass switch is closed. The three independent lineto-neutral sense signals are attenuated to 1% on the High Voltage Interface Board and then passed to the UPS Logic Board where they are converted to a digital form and monitored by the board’s microprocessor system.
s6-c1.f m5 - Issu e 2 Dated 21/08/97
6-5
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 1 - Static Switch Principles
7200 Seri es UPS Service Manual
Output (critical load) voltage sense
The 3-phase UPS output voltage is s ensed immediately ahead of the output isolator (on the hot side of the output contactor K1) and therefore accurately represents the voltage offered to the critical load. The three independent line-to-neutral sense signals are attenuated to 1% on the High V oltage Interface Board and then passed to the UPS Logic Board where they are c onverted to a digital form and monitored by the board’s microprocessor system. Output (critical load) current sense
The output current is sensed by three individual current transformers (CTs) located immediately ahead of the output isolator (on the hot side of the output current transformers) and therefore monitors the critical load current. These current sense signals are calibrated by jumpers fitted to the High Voltage Interface Board and then passed to the UPS Logic Board where they are summed and converted to a digital form and monitored by the board’s microprocessor system. 1.3.1.2
Digital contr ol signals UPS Logic Board
Various digital signals affecting the static switch operation are passed between the UPS Logic Board and the other boards connect to it. These can broadly be categorised as: •
• • • •
static switch status and alarm data generated on the UPS Logic Board and passed to the Operator Control Panel via the Operator Logic Board – also to the Alarms Interface Board (for remote indication) where fitted. transfer control logic signals passed to the Static Switch Driver Board. metering data generated on the UPS Logic Board and passed to the Operator Control Panel. control data entered at the Operator Control Panel which is stored by the UPS Logic Board – e.g. manual load transfer selection. external control options – e.g. emergency shutdown, ‘on-generator’ syncinhibit, isolator status.
Static Switch Driver Board
In addition to the transfer control signals obtained from the UPS Logic Board, the Static Switch Driver Board also receives a status signal from auxiliary contacts of the ‘inverter-side’ contactor to detect its operational status.
1.3.2
Transfer con trol phi loso phy Under normal circumstances the UPS Logic Board will request the Static Switch Driver Board to connect the load to the inverter supply – i.e. ‘bypass-side’ open and ‘inverter-side’ closed. This situation will be maintained unless an inverter fault renders it incapable of providing the required load supply parameters (e.g. ‘low battery voltage’, inverter over/under voltage, inverter overload shutdown) or it is manually selected OFF (from Operator Control Panel or UPS Logic Board ‘inverter enable’ switch) etc. Note: if the cause of the transfer clears when the load is ‘on-bypass’ the load will automatically transfer back to the inverter-side after a brief period to allow the inverter control time to re-establish itself. For example, a fault on an inverter phase may cause an erroneous overload to be detected, or the output volts to dip below the ‘undervoltage’ threshold, and initiate a load transfer to bypass. However, once
6-6
s6-c1.f m5 - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vice Man ual
SECTION 6 - Static Swit ch Operation & Con tr ol CHAPTER 1 - Static Switch Principles
the load is removed from the inverter its output will return to normal and request the load to be returned to the inverter. This type of fault could cause the load to “tick-tock” between the inverter and by pass; and to overcome this problem the transfer control l ogic permanently transfers the load to bypass if more than 8 transfers occur within 60 seconds. Bypass-to-inverter transfer mechanism
When the load is transferred from bypass to inverter the signal to close the ‘inverter-side’ contactor is applied 150ms before the ‘bypass-side’ SCR drive signals are removed. This is to allow time for the contactor to close before the bypass SCRs are turned OFF . In practice the contactor should close well within 50ms.; consequently, there will be an overlap period where both ‘sides’ of the static switch are closed simultaneously, and the inverter and bypass voltages are effectively connected in parallel. Once the contactor is closed an auxiliary contact signals the bypass SCRs to open immediately. This type of transfer is referred to as a “closed transfer” as the load is transferred without a supply break. Note: if the contactor does not close, as indicated by the auxiliary contact, the UPS Logic Board will re-establish the ‘load-on-bypass’ command before the 150ms time-out period, keeping the load on bypass.
Before the transfer control logic will allow a closed transfer from bypass to inverter it must verify that the inverter voltage is synchronised to the bypass supply. If this condition is not met then the transfer action is prohibited. Also, as this is a “controlled” transfer (i.e. not initiated by a fault condition) the inverter voltage regulation circuit is momentarily increased to matched the bypass voltage while the transfer takes place – once the load is ‘on-inverter’ the inverter reverts to its nominal voltage. This is to limit any volts difference across the ‘inverter-side’ contactor while it is being closed, and so prolong contactor life. Inverter-to-bypass transfer mechanism
A load transfer from inverter to bypass can be initiated by manual selection (controlled transfer) or by a fault condition (uncontrolled); however the results are similar in that a “closed transfer”, as described above, will take place providing the two supplies are synchronised. That is, the ‘bypass-side’ SCRs are requested to turn ON before the ‘inverter-side’ contactor is de-energised, thus effecting a no-break transfer. If the inverter is not synchronised to the bypass supply when the load transfer is requested then the ‘inverter-side’ contactor is opened before the ‘bypass-side’ SCRs are turned ON and the load will experience a slight power-break of up to 1 cycle. This type of transfer is referred to as an “open transfer”, and protects the load from out-of-phase voltage differences which could put twice the phase voltage potential on the critical load busbar.
1.3.3
Contro l pow er supp lies All circuit boards concerned with the static switch control function are powered from either the AC-DC Power Supply Board or the DC-DC Power Supply Board and are active when either supply is ‘live’.
s6-c1.f m5 - Issu e 2 Dated 21/08/97
6-7
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 1 - Static Switch Principles
6-8
7200 Seri es UPS Service Manual
s6-c1.f m5 - Issu e 2 Dated 21/08/97
Section 6:
Chapter 2 - Static Switch Driver Board (4542043 Z)
2.1
Chapter overview This chapter contains a circuit description of the Static Switch Driver Board currently used across the whole 7200 Series UPS model range, and should be read in conjunction with circuit diagram SE-4542043-Z (1 page). Part N º SE-4542043-Z is a direct replacement for Part Nº SE-4542041-X which may be fitted to units manufactured prior to February 1997. Although there are only minor differences between the two boards a full explanation of the Static Switch Driver Board Part Nº SE-4542041-X can be found in Section 19 Chapter 3.
2.2 2.2.1
General descri pti on Circuit board functio ns This board is responsible for providing the ‘bypass-side’ static switch SCRs with their gate drive signals when the UPS L ogic Board requests Load-on-bypass, and for energising the ‘inverter-side’ contactor when it requests Load-on-inverter . In so doing, the board contains interlocking controls to prevent simultaneous operation of both circuits: thereby controlling the load transfer characteristics. It also provides the necessary galvanic signal isolation between the low-voltage environment of the control electronics and the high-voltage environment surrounding the bypass SCR devices and ‘inverter-side’ contactor.
2.2.2
Input/Outpu t con nectio ns The Static Switch Driver Board has eleven connectors, all of which are described below: • • • • • •
WARNING
X1 to X6 – Output gate drive signals to static switch SCRs X7 – Not used X8 – DC supply for the ‘inverter-side’ contactor X9 – Switched energising supply for the ‘inverter-side’ contactor X10 – ‘inverter-side’ contactor auxiliary contacts (used for contactor status monitoring) X13 – Ribbon cable to the UPS Logic Board: carrying control logic signals and power supplies etc.
TAKE EXTREME CARE WHEN WORKING ON THIS BOARD IN SITU. The ‘inverter-side’ contactor energising supply at connectors X8 and X9 is obtained from the DC Busbar and is at a potentially dangerous DC voltage whenever the rectifier is operating or the UPS battery circuit breaker is closed. Similarly, mains a.c. voltage is present on the SCR drive connectors at all times when the load is on ‘inverter’ or ‘bypass”.
s6-c2.f m5 - Issu e 2 Dated 21/08/97
6-9
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 2 - Static Switc h Driver B oard (4542043 Z)
2.2.3
7200 Seri es UPS Service Manual
Blo ck Diagram The following illustration shows the Static Switch Driver Board at its most basic functional block diagram level – the function of each of the blocks shown is described in the following text. Figure 6-7: Static Switch Driver Board basic block diagram
Contactor Switching Logic
DC Bus Volts
Inverter Contactor
l h o r c t t i n w o s c
Contactor Auxiliary
Transfer Interlock Logic
Load-on-inverter Load-on-bypass
Modulator Oscillator
Mixer Gate
Supply Monitor
Output Driver Circuit
Static Switch SCR Gates
+12V Control Power –12V Supply
Power Supply
+12V +5V
Transfer interlock logic
The ‘transfer interlock logic’ is at the heart of the board’s operation. It determines whether the ‘inverter-side’ contactor is closed or the static bypass SCRs are turned on; and in so doing, it controls the load transfer operation between the inverter and bypass supplies. There are three inputs to this static logic block. The ‘load-on-inverter’ and ‘loadon-bypass’ signals are produced on the UPS Logic Board and are the primary load transfer request inputs. The interlocking function also employs a signal derived from auxiliary contacts of the ‘inverter-side’ contactor which confirms the contactor’s status. Contactor switching logic
The ‘contactor switching logic’ block contains a solid-state switching circuit which is controlled by the ‘transfer interlock logic’ and connects the DC busbar (battery) voltage through to the ‘inverter-side’ contactor’s closi ng coil. Mixer gate
The ‘mixer gate’ combines the load-on-bypass command signal from the ‘transfer interlock logic’ with a 30kHz modulating signal to provide the ‘output driver circuit’ with a modulated drive waveform. This type of drive signal is used to mini-
6-10
s6-c2.f m5 - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vi ce Man ual
SECTION 6 - St at ic Sw it ch Op er at io n & Co nt ro l CHAPTER 2 - Static Swit ch Driv er Board (4542043 Z)
mise the size of the transformers in the ‘output driver circuit’, which are necessary to provide signal isolation. Note that the ‘mixer gate’ output is inhibited by t he ‘supply monitor’ circuit if it detects a ‘low’ control power supply voltage: this also provides a reset pulse on initial power-up. Modulation oscillator
This is a free running oscillator of approximately 30kHz which provides a modulating signal to the ‘mixer gate’ as described immediately above. Output driver circuit
This circuit contains three pairs of power drivers which are all driven by the modulated signal from the ‘mixer gate’. Each pair of drivers is connected in a push pull configuration across the output transformers’ primary windings to provide adequate drive power. Supply monitor
The ‘supply monitor’ senses the voltage on the +12V control power rail and serves two functions: first, it provides reset signal to the ‘mixer gate’ to prevent it turning on the static switch SCRs during power-up, until the supply rail has had chance to stabilise. Second, it inhibits the mixer gate if it detects that the +12V rail falls below 8V. Power Supply
±12V power rails are connected to this board from the UPS Logic Board via X13 pins 1-12. These are connected to a voltage regulator circuit which provides a sta bilised +5V rail which is required by the board’s electronic devices.
2.3 2.3.1
Detailed cir cui t descrip tio n Introduction This description, which refers to the ‘circuit blocks’ shown in Figure 6-7, should be read in conjunction with diagram SE-4542043-Z. ‘inverter-side’ contactor control
The ‘inverter-side’ contactor is energised by the high DC voltage present on the DC busbar. The full bus voltage is applied to X8 pins 1-3 and the coil is connected to X9 pins 1-3. Note that the positive supply is directly connected via pins 3 and the contactor is controlled by switching the bus negative supply to X9 pin 1. The contactor is energised by a logic ‘high’ [INV-L> signal applied to X13 pin 15 from the UPS Logic Board. This signal turns on V32 which, via opto-isolator V41, then turns on V31 and thus connects the contactor coil negative side to the negative DC busbar supply at X8-1. The contactor should close within 50ms. Note: the supply to V31 gate is obtained from the positive DC bus (battery) voltage present at X8 pins 3 via V41, R23 and R24; however it is limited to 13V by zener V21. V12 and V13 are flywheel diodes to protect V41 and V31.
When the contactor closes, its auxiliary contacts short out X10 pins 1-2 which then pulls D5-8 to a logic ‘low’ and informs the ‘transfer interlock logic’ of the contactor’s status. The contactor should take between 60-100ms to open.
s6-c2.f m5 - Issu e 2 Dated 21/08/97
6-11
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 2 - Static Switc h Driver B oard (4542043 Z)
7200 Seri es UPS Service Manual
Static switch SCR control
The ‘bypass-side’ SCRs are controlled by the ‘transfer interlock logic’ circuit output at D5 pin 12 (best monitored at X11: 0-3 which should be made). When this point goes ‘high’ it drives N2 pin 7 ‘high’ which then takes D2 pin 2 and 3 high, which ‘triggers’ the SCRs, vi the driver FET’s V2 and V11. D2 is annotated ‘mixer gate’ in the block diagram (See Figure 6-7) and turns on the static switch SCRs when its outputs (D2 pins 6 & 9) are high. The input to D2 pin 2 and 3 is connected to the output of N3, which is a power supply monitor, and goes ‘low’ to inhibit the SCR drive signal in the event of a power failure (and during initial power-up). The input to D2 pin 1 and 5 is a 30kHz square wave signal provided by D1, which is a free running oscillator: thus, provided there is no problem with the power rails, when the output from N2 pin 7 goes ‘high’ it ‘enables’ D2 to pass the 30kHz modulating signal through to the output driver gates of V2 and V11. Note: V2 and V11 are supplied from the -12V rail to provide suitable output switching levels to the isolating pulse transformers driving the power SCRs. Output driver circuit
The 30kHz output from the ‘mixer gate’ (D2 pins 6 & 9) are connected to the gates of V2 & V11, which are the output line driver devices. Taking V2 as an example: when the 30kHz drive signal to D2 pin 6 is ‘high’ FET V2 turns on. This connects the -12V through to T1, T3 and T5 primaries with the +12V rail. When the 30kHz drive signal is ‘low’ D2 outputs go to a high impedance state; thus the ±12V output at V2 is switched on and off at a 30kHz rate. As can be seen on the circuit diagram, V2 and V11 output is connected to the SCRs’ gate drive connectors via pulse transformers T1 to T6 which provide the necessary signal isolation. Suppression capacitors C34 and C35 protect the driver FETs from the transformers’ reactive currents. Transfer interlock logic
Figure 6-8: Transfer interlock logic D6 1 3
V10
[MNS-L> 1 = Load on Bypass [INV-L> 1 = Load on Inverter Contactor Aux Fdbk 1 = Contactor Open
R48
D5 3
2
D5 1
12 11
470k R28
4
D6 2
C6 330n
13
470k
U5 5
U5 6
11
10
D6 D6 5
D5
D5
8 10 13
12
1 = Turn on bypass SCRs
4 9 9
8
6
1 = Close Output Contactor
As explained in the previous paragraphs, the ‘transfer interlock logic’ controls the signal which initiates the static switch SCR driver circuit – i.e. the output from D5-12 turns on the static switch when ‘high’ and vice versa.
6-12
s6-c2.f m5 - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vi ce Man ual
SECTION 6 - St at ic Sw it ch Op er at io n & Co nt ro l CHAPTER 2 - Static Swit ch Driv er Board (4542043 Z)
This circuit is controlled by three inputs shown in the diagram above. These are: • • •
[INV-L> which goes ‘high’ when the UPS Logic Board is requesting load-
on-inverter (i.e. contactor closed). [MNS-L> which goes ‘high’ when the UPS Logic Board is requesting loadon-bypass (i.e. static switch SCRs turned on). Auxiliary contacts from the ‘inverter-side’ contactor which is logic ‘low’ when the contactor is closed and vice versa.
The [INV-L> and [MNS-L> signals are mutually exclusive – i.e. the control system on the UPS Logic Board prevents it from requesting both conditions simultaneously. The following paragraphs described the circuit action when the load is transferred between one power source and the other.
Load transfer from bypass to inverter - When the UPS Logic Board requires a load transfer to inverter it simultaneously drives the [MNS-L> ‘low’ and the [INV-L> ‘high’. 1. Prior to the transfer, the load is on the bypass supply, which means that D6 pin 10 is ‘low’ (turning on the bypass SCRs). 2. The ‘low’ [MNS-L> signal is inverted to a ‘high’ at D5 pin 4 which takes D6 pin 1 high. 3. The same ‘high’ [MNS-L> signal is also inverted to a ‘low’ at D5-2, however R28/C6 applies a 150ms time delay on this signal before it reaches D6 pin 12. This is to hold on the bypass SCRs until the ‘inverter-side’ contactor has had time to close (contactor should close within 50ms). 4. After 150ms D6 pins 1 & 2 will both be ‘high’ and this will drive D6 pin 3 ‘low’ which drives D6 pin 10 ‘high’ and D5 pin 12 ‘low’ – turning off the bypass SCRs. 5. The ‘high’ [INV-L> signal: a) is inverted twice, at D5-6 and D5-10, and applies a ‘high’ at D6 pin 5. However this has no immediate effect on the circuit. b) turns on V32, which switches on the ‘inverter-side’ contactor energising supply (see earlier ‘output contactor control’ earlier in this section). 6. When the ‘inverter-side’ contactor closes it applies a ‘low’ to D5-9 which is inverted to a ‘high’ at D5-8 and D6 pin 6. 7. With D6 pins 5 and 6 now both ‘high’, the output at D6 pin 4 goes ‘low’ which drives D6 pin 10 ‘high’ and D6 pin 11 ‘low’, which then turns off the bypass SCRs. That is, if the ‘inverter-side’ contactor has closed it will open the bypass SCRs immediately and doesn’t wait 150ms. Note 1: the above description shows that when transferring normally from ‘by pass’ to ‘inverter’ the bypass SCRs are held on until the ‘inverter-side’ contactor is closed (auxiliary contacts closed), therefore the load is transferred without a supply break – i.e. closed transfer. Note 2: Once the UPS Logic Board software decides to transfer to inverter, the bypass SCRs are held on for a 150ms period. The contactor, if OK, should close within 50ms. If this is the case, as indicated by the contactor auxiliary contacts, the bypass SCRs are opened immediately. If this is NOT the case then the UPS
s6-c2.f m5 - Issu e 2 Dated 21/08/97
6-13
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 2 - Static Switc h Driver B oard (4542043 Z)
7200 Seri es UPS Service Manual
Logic Board software will re-establish the load on bypass command and remove the load on inverter request to close the ‘inverter-side’ contactor. Note 3: The load on inverter request is given 5 seconds to achieve its objective, otherwise the micro will annunciate an alarm (#41) [Output: No Voltage] on the Operator Control Panel and will not attempt further transfers.
Load transfer from inverter to bypass - When the UPS Logic Board requires a load transfer to bypass it simultaneously drives the [MNS-L> ‘high’ and the [INV-L> ‘low’. 1. Prior to the transfer, the load is on the inverter supply, which means that D5 pin 12 is ‘low’ (turning off the bypass SCRs). 2. The ‘high’ [MNS-L> signal is: a) inverted to a ‘low’ at D5 pin 4 which takes D6 pin 1 ‘low’. b) inverted to a ‘high’ at D5 pin 2 which takes D6 pin 2 ‘low’. Note: that in this instance there is no delay on the signal reaching D6 pin 2 as the time delay is bypassed by V10. 3. A logic ‘low’ at either of D6 pins 1 or 2 will drive D6 pin 8 high; however this has no immediate effect on the circuit (step 4a below). 4. The ‘low’ [INV-L> signal: a) is inverted twice, at D5-6 and D5-10, and applies a ‘low’ at D6 pin 5 which results in a ‘high’ at D6 pin 9. b) turns off V32, which switches off the ‘inverter-side’ contactor energising supply (see ‘output contactor control’ earlier in this section). 5. With logic highs at D6 pin 8 (step 3) and pin 9 (step 4a), the output from D8 pin 10 now switches ‘low’ and D5 pin 12 ‘high’ which is the state necessary to turn on the bypass SCRs. 6. When the ‘inverter-side’ contactor opens it applies a ‘high’ to D5-9 which is inverted to a ‘low’ at D5-8 and D6 pin 6 which then holds D6 pin 9 ‘high’ and reinforces (overrides) the effect of the [INV-L> signal on D6 pin 5. Note: the above description shows that when transferring normally from ‘inverter’ to ‘bypass’ the bypass SCRs are turned on immediately the [INV-L> signal requests the ‘inverter-side’ contactor to open, therefore the load is transferred without a supply break – i.e. closed transfer. The contactor should open within 60100ms. Power supplies
The devices on this board require various operating voltages. The main ±12V supply rails are provided by the UPS Logic Board and connected via X13 pins 1 to 12. +12V and 0V are then connected to a simple three-terminal regulator which provides a +5V supply rail, as shown. Note that D1 and D2 are both 5V operating devices but are fed from the -12V and 0V power rails. This is to shift their output signal levels to that required to switch the ‘output drivers’ (V2 and V11).
6-14
s6-c2.f m5 - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vi ce Man ual
SECTION 6 - St at ic Sw it ch Op er at io n & Co nt ro l CHAPTER 2 - Static Swit ch Driv er Board (4542043 Z)
Power supply monitor
N3 monitors the +12V rail and -12V rail and its output pin 5 goes ‘low’ if the +12V falls below approximately 6.8V or the -12 falls below approximately -10.6V. This inhibits the ‘mixer gate’ D2 and the output line driver devices and so prevents the bypass SCRs from being turned on. Power supply failure could cause intermittent SCR triggering and, in the worst case, present a half-wave load supply. The power supply monitor avoids such occurrences.
2.4
Summary inf orm ation Table 6-1: Static Switch Driver Board configuration jumpers
Jumper
Link Positio n
Function
open
Enable load on inverter command (Standard)
closed
Disable load on inverter command
open
Enable load on bypass command(Standard)
closed
Disable load on bypass command
open
Disables bypass fire command
closed
Enable bypass fire command (Standard)
N/A
Not used
open
Test static switch temperature monitor
closed
Inhibit static switch temperature monitor (standard)
0 - 1
0 - 2
X11
0 - 3 0-4
0-5
s6-c2.f m5 - Issu e 2 Dated 21/08/97
6-15
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 2 - Static Switc h Driver B oard (4542043 Z)
6-16
7200 Seri es UPS Service Manual
s6-c2.f m5 - Issu e 2 Dated 21/08/97
Section 19:
Chapter 3 - Static Switch Driver Board (4542041 X)
3.1
Chapter overview This chapter contains a circuit description of the Static Switch Driver Board 4542041X which was used across the whole 7200 Series UPS model range prior to February ‘97, when it was superseded by Part No. 4542043Z (see Chapter 2). This chapter should be read in conjunction with circuit diagram SE-4542041-X (1 page).
3.2 3.2.1
General descri pti on Circuit board functio ns This board is responsible for providing the ‘bypass-side’ static switch SCRs with their gate drive signals when the UPS L ogic Board requests Load-on-bypass, and for energising the ‘inverter-side’ contactor when it requests Load-on-inverter . In so doing, the board contains interlocking controls to prevent simultaneous operation of both circuits: thereby controlling the load transfer characteristics. It also provides the necessary galvanic signal isolation between the low-voltage environment of the control electronics and the high-voltage environment surrounding the bypass SCR devices and ‘inverter-side’ contactor.
3.2.2
Input/Outpu t con nectio ns The Static Switch Driver Board has eleven connectors, all of which are described below: • • • • • •
WARNING
X1 to X6 – Output gate drive signals to static switch SCRs X7 – Not used X8 – DC supply for the ‘inverter-side’ contactor X9 – Switched energising supply for the ‘inverter-side’ contactor X10 – ‘inverter-side’ contactor auxiliary contacts (used for contactor status monitoring) X13 – Ribbon cable to the UPS Logic Board: carrying control logic signals and power supplies etc.
TAKE EXTREME CARE WHEN WORKING ON THIS BOARD IN SITU. The ‘inverter-side’ contactor energising supply at connectors X8 and X9 is obtained from the DC Busbar and is at a potentially dangerous DC voltage whenever the rectifier is operating or the UPS battery circuit breaker is closed. Similarly, mains a.c. voltage is present on the SCR drive connectors at all times when the load is on ‘inverter’ or ‘bypass”.
s6-c2OL D.fm - Iss ue 2 Dated 21/08/97
19-285
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 3 - Static Switc h Driver B oard (4542041 X)
3.2.3
7200 Seri es UPS Service Manual
Blo ck Diagram The following illustration shows the Static Switch Driver Board at its most basic functional block diagram level – the function of each of the blocks shown is described in the following text. Figure 19-9: Static Switch Driver Board basic block diagram
Contactor Switching Logic
DC Bus Volts
Inverter Contactor
l h o r c t t i n w o s c
Contactor Auxiliary
Transfer Interlock Logic
Load-on-inverter Load-on-bypass
Control Power Supply
Modulator Oscillator
Mixer Gate
Supply Monitor
Output Driver Circuit
Power Supply
Static Switch SCR Gates
±12V +5V -7V
Transfer interlock logic
The ‘transfer interlock logic’ is at the heart of the board’s operation. It determines whether the ‘inverter-side’ contactor is closed or the static bypass SCRs are turned on; and in so doing, it controls the load transfer operation between the inverter and bypass supplies. There are three inputs to this static logic block. The ‘load-on-inverter’ and ‘loadon-bypass’ signals are produced on the UPS Logic Board and are the primary load transfer request inputs. The interlocking function also employs a signal derived from auxiliary contacts of the ‘inverter-side’ contactor which confirms the contactor’s status. Contactor switching logic
The ‘contactor switching logic’ block contains a solid-state switching circuit which is controlled by the ‘transfer interlock logic’ and connects the DC busbar (battery) voltage through to the ‘inverter-side’ contactor’s closi ng coil. Mixer gate
The ‘mixer gate’ combines the load-on-bypass command signal from the ‘transfer interlock logic’ with a 30kHz modulating signal to provide the ‘output driver circuit’ with a modulated drive waveform. This type of drive signal is used to mini-
19-286
s6-c2OLD.f m - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vi ce Man ual
SECTION 6 - St at ic Sw it ch Op er at io n & Co nt ro l CHAPTER 3 - Static Switc h Driver B oard (4542041 X)
mise the size of the transformers in the ‘output driver circuit’, which are necessary to provide signal isolation. Note that the ‘mixer gate’ output is inhibited by t he ‘supply monitor’ circuit if it detects a ‘low’ control power supply voltage: this also provides a reset pulse on initial power-up. Modulation oscillator
This is a free running oscillator of approximately 30kHz which provides a modulating signal to the ‘mixer gate’ as described immediately above. Output driver circuit
This circuit contains three pairs of power drivers which are all driven by the modulated signal from the ‘mixer gate’. Each pair of drivers is connected in a push pull configuration across the output transformers’ primary windings to provide adequate drive power. Supply monitor
The ‘supply monitor’ senses the voltage on the +12V control power rail and serves two functions: first, it provides reset signal to the ‘mixer gate’ to prevent it turning on the static switch SCRs during power-up, until the supply rail has had chance to stabilise. Second, it inhibits the mixer gate if it detects that the +12V rail falls below 8V. Power Supply
±12V power rails are connected to this board from the UPS Logic Board via X13 pins 1-12. These are connected to two voltage regulator circuits which provide stabilised +5 and -7V supply rails which are required by several of the board’s devices.
3.3 3.3.1
Detailed cir cui t descrip tio n Introduction This description, which refers to the ‘circuit blocks’ shown in Figure 19-9, should be read in conjunction with diagram SE-4542041-X. ‘inverter-side’ contactor control
The ‘inverter-side’ contactor is energised by the high DC voltage present on the DC busbar. The full bus voltage is applied to X8 pins 1-3 and the coil is connected to X9 pins 1-3. Note that the positive supply is directly connected via pins 3 and the contactor is controlled by switching the bus negative supply to X9 pin 1. The contactor is energised by a logic ‘high’ [INV-L> signal applied to X13 pin 15 from the UPS Logic Board. This signal turns on V32 which, via opto-isolator V41, then turns on V31 and thus connects the contactor coil negative side to the negative DC busbar supply at X8-1. The contactor should close within 50ms. Note: the supply to V31 gate is obtained from the positive DC bus (battery) voltage present at X8 pins 3 via V41, R23 and R24; however it is limited to 13V by zener V21. V12 and V13 are flywheel diodes to protect V41 and V31.
When the contactor closes, its auxiliary contacts short out X10 pins 1-2 which then pulls D5-8 to a logic ‘low’ and informs the ‘transfer interlock logic’ of the contactor’s status. The contactor should take between 60-100ms to open.
s6-c2OL D.fm - Iss ue 2 Dated 21/08/97
19-287
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 3 - Static Switc h Driver B oard (4542041 X)
7200 Seri es UPS Service Manual
Static switch SCR control
The ‘bypass-side’ SCRs are controlled by the ‘transfer interlock logic’ circuit output at D6 pin 11 (best monitored at X12-3 which should be made). When this point goes ‘high’ it drives N3 pin 7 ‘high’ which then takes D2 pin 4 and D3/D4 pins 7 and 16 high, which ‘triggers’ the SCRs. D2 is annotated ‘mixer gate’ in the block diagram (See Figure 19-9) and turns on the static switch SCRs when its output (D2 pin 6) is high. The input to D2 pin 3 is connected to the output of N4, which i s a power supply monitor, and goes ‘low’ to inhibit the SCR drive signal in the event of a power failure (and during initial power-up). The input to D2 pin 5 is a 30kHz square wave signal provided by D1, which is a free running oscillator: thus, provided there is no problem with the power rails, when the output from N3 pin 7 goes ‘high’ it ‘enables’ D2 to pass the 30kHz modulating signal through to the output driver gates of D3 and D4. Note: D1 and D2 are supplied from the -7V and -12V power rails to shift their output switching levels to that required for driving the output line drivers D3/D4. Output driver circuit
The 30kHz output from the ‘mixer gate’ (D2-8) is connected to the gates of Q3/ Q4, which are the output line driver devices. Taking D4a a s an example: when the 30kHz drive signal to D4-1 is ‘high’ the two drivers wit hin D4a turn on. This connects the -12V at D4-2 through to D4-3 and +12V (from N3 output) at D4-7 through to D4-6. When the 30kHz drive signal is ‘low’ D4 outputs go to a high impedance state; thus the ±12V outputs at D4 pins 3 and 6 are switched on and off at a 30kHz rate. As can be seen on the circuit diagram, D4 outputs are connected to the SCRs’ gate drive connectors via pulse transformers T1 and T2 which provide the necessary signal isolation. V3 to V4 are flywheel diodes and protect the driver devices from the transformers’ reactive currents. Transfer interlock logic
Figure 19-10: Transfer interlock logic
D5 1
[MNS-L> 1 = Load on Bypass
2
D6 1 3
V10 2
D5 3
R29
4
C6 330n
470k
D6 8
D6 10 12
[INV-L> 1 = Load on Inverter
9
D5 5
6
11
11 13
D5 10
1 = Turn on bypass SCRs
D6 5 4 6
D5
Contactor Aux Fdbk 1 = Contactor Open
19-288
9
8
1 = Close Output Contactor
s6-c2OLD.f m - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vi ce Man ual
SECTION 6 - St at ic Sw it ch Op er at io n & Co nt ro l CHAPTER 3 - Static Switc h Driver B oard (4542041 X)
As explained in the previous paragraphs, the ‘transfer interlock logic’ controls the signal which initiates the static switch SCR driver circuit – i.e. the output from D6-11 turns on the static switch when ‘high’ and vice versa. This circuit is controlled by three inputs shown in the diagram above. These are: • • •
[INV-L> which goes ‘high’ when the UPS Logic Board is requesting load-
on-inverter (i.e. contactor closed). [MNS-L> which goes ‘high’ when the UPS Logic Board is requesting loadon-bypass (i.e. static switch SCRs turned on). Auxiliary contacts from the ‘inverter-side’ contactor which is logic ‘low’ when the contactor is closed and vice versa.
The [INV-L> and [MNS-L> signals are mutually exclusive – i.e. the control system on the UPS Logic Board prevents it from requesting both conditions simultaneously. The following paragraphs described the circuit action when the load is transferred between one power source and the other.
Load transfer from bypass to inverter - When the UPS Logic Board requires a load transfer to inverter it simultaneously drives the [MNS-L> ‘low’ and the [INV-L> ‘high’. 1. Prior to the transfer, the load is on the bypass supply, which means that D6 pin 11 is ‘high’ (turning on the bypass SCRs). 2. The ‘low’ [MNS-L> signal is inverted to a ‘high’ at D5 pin 2 which takes D6 pin 1 high. 3. The ‘low’ [MNS-L> signal is also inverted to a ‘high’ at D5-4, however R29/ C6 applies a 150ms time delay on this signal before it reaches D6 pin 2. This is to hold on the bypass SCRs until the ‘inverter-side’ contactor has had time to close (contactor should close within 50ms). 4. After 150ms D6 pins 1 & 2 will both be ‘high’ and this will drive D6 pin 3 ‘low’ which drives D6 pin 10 ‘high’ and D6 pin 11 ‘low’ – turning off the bypass SCRs. 5. The ‘high’ [INV-L> signal: a) is inverted twice, at D5-6 and D5-10, and applies a ‘high’ at D6 pin 5. However this has no immediate effect on the circuit. b) turns on V32, which switches on the ‘inverter-side’ contactor energising supply (see earlier ‘output contactor control’ earlier in this section). 6. When the ‘inverter-side’ contactor closes it applies a ‘low’ to D5-9 which is inverted to a ‘high’ at D5-8 and D6 pin 6. 7. With D6 pins 5 and 6 now both ‘high’, the output at D6 pin 4 goes ‘low’ which drives D6 pin 10 ‘high’ and D6 pin 11 ‘low’, which then turns off the bypass SCRs. That is, if the ‘inverter-side’ contactor has closed it will open the bypass SCRs immediately and doesn’t wait 150ms. Note 1: the above description shows that when transferring normally from ‘by pass’ to ‘inverter’ the bypass SCRs are held on until the ‘inverter-side’ contactor is closed (auxiliary contacts closed), therefore the load is transferred without a supply break – i.e. closed transfer.
s6-c2OL D.fm - Iss ue 2 Dated 21/08/97
19-289
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 3 - Static Switc h Driver B oard (4542041 X)
7200 Seri es UPS Service Manual
Note 2: Once the UPS Logic Board software decides to transfer to inverter, the bypass SCRs are held on for a 150ms period. The contactor, if OK, should close within 50ms. If this is the case, as indicated by the contactor auxiliary contacts, the bypass SCRs are opened immediately. If this is NOT the case then the UPS Logic Board software will re-establish the load on bypass command and remove the load on inverter request to close the ‘inverter-side’ contactor.
Note 3: The load on inverter request is given 5 seconds to achieve its objective, otherwise the micro will annunciate an alarm (#41) [Inverter: No Voltage] on the Operator Control Panel and will not attempt further transfers.
Load transfer from inverter to bypass - When the UPS Logic Board requires a load transfer to bypass it simultaneously drives the [MNS-L> ‘high’ and the [INV-L> ‘low’. 1. Prior to the transfer, the load is on the inverter supply, which means that D6 pin 11 is ‘low’ (turning off the bypass SCRs). 2. The ‘high’ [MNS-L> signal is: a) inverted to a ‘low’ at D5 pin 2 which takes D6 pin 1 ‘low’. b) inverted to a ‘low’ at D5-4 which takes D6 pin 2 ‘low’. Note: that in this instance there is no delay on the signal reaching D6 pin 2 as the time delay is bypassed by V10. 3. A logic ‘low’ at either of D6 pins 1 or 2 will drive D6 pin 8 high; however this has no immediate effect on the circuit (step 4a below). 4. The ‘low’ [INV-L> signal: a) is inverted twice, at D5-6 and D5-10, and applies a ‘low’ at D6 pin 5 which results in a ‘high’ at D6 pin 9. b) turns off V32, which switches off the ‘inverter-side’ contactor energising supply (see earlier ‘output contactor control’ earlier in this section). 5. With logic highs at D6 pin 8 (step 3) and pin 9 (step 4a), the output from D8 pin 10 now switches ‘low’ and D6 pin 11 ‘high’ which is the state necessary to turn on the bypass SCRs. 6. When the ‘inverter-side’ contactor opens it applies a ‘high’ to D5-9 which is inverted to a ‘low’ at D5-8 and D6 pin 6 which then hold D6 pin 9 ‘high’ and reinforces (overrides) the effect of the [INV-L> signal on D6 pin 5. Note: the above description shows that when transferring normally from ‘inverter’ to ‘bypass’ the bypass SCRs are turned on immediately the [INV-L> signal requests the ‘inverter-side’ contactor to open, therefore the load is transferred without a supply break – i.e. closed transfer. The contactor should open within 60100ms. Power supplies
The devices on this board require various operating voltages. The main ±12V supply rails are provided by the UPS Logic Board and connected via X13 pins 1 to 12. These are then connected to two simple three-terminal regulators which provide +5V and -7V supply rails, as shown. Note that D1 and D2 are both 5V operating devices but are fed from the -12V and -7V power rails. This is to shift their output signal levels to that required to switch
19-290
s6-c2OLD.f m - Issu e 2 Dated 21/08/97
7200 Ser ies UPS Ser vi ce Man ual
SECTION 6 - St at ic Sw it ch Op er at io n & Co nt ro l CHAPTER 3 - Static Switc h Driver B oard (4542041 X)
the ‘output drivers’ (D3 and D4). The -7V rail also offsets the output from N3 to the ‘mixer gate’ input. Power supply monitor
N4 monitors the +12V rail and -12V rail and its output pin 6 goes ‘low’ if the +12V falls below approximately 6.8V or the -12 falls below approximately -10.6V. This inhibits the ‘mixer gate’ and the output line driver devices (via V11) and so prevents the bypass SCRs from being turned on. Power supply failure could cause intermittent SCR triggering and, in the worst case, present a halfwave load supply. The power supply monitor avoids such occurrences.
3.4
Summary inf orm ation Table 19-2: Static Switch Driver Board configuration jumpers
Jumper
Link Position
X11
1-2
Inhibit static switch temperature monitor
2-3
Enable static switch temperature monitor (Standard)
X12
Function
0-1
OPEN
0-1
CLOSED
0-2
OPEN
0-2
CLOSED
0-3
OPEN
0-3
CLOSED
s6-c2OL D.fm - Iss ue 2 Dated 21/08/97
Enable load on inverter command (Standard) Disable load on inverter command Enable load on bypass command(Standard) Disable load on bypass command Disables bypass fire command Enable bypass fire command (Standard)
19-291
SECTION 6 - Static Swit ch Oper at io n & Con tro l CHAPTER 3 - Static Switc h Driver B oard (4542041 X)
19-292
7200 Seri es UPS Service Manual
s6-c2OLD.f m - Issu e 2 Dated 21/08/97