Together og ether We Power The Wor World ld
SFRA SFR A Tra raini ining ng
SFRA History Initial research started in the 60’s. In the 80’s Engineers mainly used HP network analyzers First generation of SFRA purpose built test sets developed by Doble in 1990. Now SFRA technique has gained world wide acceptance with several manufacturers producing dedicated instruments for SFRA
SFRA History
Today Doble’s SFRA has become the de facto SFRA standard in North America and wordwide with > 700 Instruments sold Doble has been cataloging results for ten years Doble has developed standardized SFRA procedures for IEEE & CIGRE Doble develops support network for SFRA analysis and interpretation
National Grid FRA experience
• started ev evaluating FR FRA in in late 1980’s • initially used an impulse technique (KEMA digital LVI) • changed to swept frequency ( Ontario Hydro ) • hundreds of tests • several ex examples of failures • standardised test procedure ( ‘Euro Doble’ ) • Meth ethod no now used by many other her utilities in Europe, Far East, Australia, North America
Support: Integration
SFRA is one tool in the tool box Capacitance
OC: Open Circuit
Exciting Currents
DC Resistance
SFRA
SC: Open Circuit
Leakage Reactance
Together og ether We Power The Wor World ld
SFRA SFR A Tra raini ining ng Why Use SFRA?
Doble Doble SFRA SFRA – summar summary y SFRA is a test set for transformers, reactors, and rotating machines SFRA can tell you if anything is damaged or broken inside your transformer without going inside. SFRA is used alongside other o ther electrical tests such as the M4000 and oil analysis
Transformer Decisions • There are many decisions relating to transformers: – Is it safe to go back in service after a fault? – Has it been damaged in transit? – Is it deteriorating as it ages? – Will it fail unexpectedly? • Decision making for transformers is not easy • Quality data and engineers support good decisions
Transformer Data • Data may relate to different transformer areas: – Dielectric – ability to carry voltage – Mechanical – ability to carry current – Thermal – ability to sustain power transfer • Field Testing provides the engineer with a group of tools to assess the condition of a transformer in each area • Engineer should choose the right tool for the job
Which Transformer Tests?
• Tests depend on the decision you need to make!
Motivation: SFRA When & Why? • Acceptance • Establish a Baseline • Assess Condition after Electrical Disturbance • Assess Condition after a Relocation • Asset Management - Ranking and Prioritizing • Reduce Catastrophic Failures • Winding technology hasn’t changed much in 100 years • Available tools have changed a great deal
Why Do Things Move?
• Mechanical Shock during Shipping • Loosening of Internal Structural Components – loss of clamping pressure • Fault Duty
Mechanical Failure
Mechanical Failure
Failure Mode •
The very large electromagnetic forces on windings during fault conditions can cause winding movement and even permanent winding and core deformation
•
This may result in insulation damage.
•
Turn to turn faults are the most likely.
•
Insulation damage usually results in a failure of the transformer which is uneconomic to repair.
Design issues
• Transformers should be designed to withstand through faults. • However, transformers are rarely short-circuit tested because of the costs involved. • So the short-circuit strengths of designs are not often checked. • Many new transformers fail short circuit tests, so the shortcircuit strength of many designs must be suspect.
Design limitations
• Desi Design gn cal calcu cula lati tion onss don’ don’tt take take int into o acco accoun untt the the effe effect ctss of twisting forces. • Desi Design gner erss can can’t ’t desi design gn agai agains nstt tap tap to tap tap fau fault lts. s. • Tap Tap wind windin ings gs are are dif diffi ficu cult lt to des desig ign n for for shor shortt-ci circ rcui uitt strength.
Specification
• Impedance
20 %
5%
• Short-circuit current
5 p.u.
20 p.u.
• Short-circuit fo forces
1
:
16
Detection • Dissolved gas analysis (DGA) will only indicate a problem when the insulation has been damaged (usually too late to repair). • Internal visual inspections often inconclusive • Winding failures can usually be diagnosed by various electrical tests ( but not always ). • But latent damage is much harder to detect. So your transformer may be critically damaged without you being aware of it !
Service • The number and severity of short-circuit events suffered are important. • Close-up lightning strikes are a common cause of winding movement failures. • Tap-changer faults can cause tap winding failures. • Faulty synchronisation can cause winding damage and failure.
Ageing
• As a transformer ages th the insulation shrinks and clamping pressure is lost. - reduces strength. • Any Any min minor or wind windin ing g def defor orma mati tion on usua usuall lly y results in mis-alig mis-alignmen nmentt of electrom electromagne agnetic tic centres - increases stresses during
subsequent faults.
Failure Mode • Hoop buc uck klin ing g of inn nne er winding • Conductor ti tipping • Conductor tele lesscopin ing g • Coil cla lam mpin ing g fail ilu ure • End insulation collapse
• Spiral ti tightening • Lead displacement
Bushing failure….
This bushing failed catastrophically
This bushing was hit by porcelain and failed Neutral bushing lifted from turret and is no longer vertical SFRA 2009
Bushing….
But did the windings move because of the pressure wave in the oil? SFRA showed that the windings were in good shape. SFRA 2009
Transformer impact….
Or maybe we hit a bridge?
Bridge Impact
Paint scrapes on delivery are suspicious? How did the scrapes get there, and what does the impact recorder say? Do we know if anything moved inside the transformer?
Transport Issues
t
Transformer Arrives by Barge
Almost!
Symptoms - black box scenario
• How can we tell if anything has moved?
SFRA as a transformer test
Sweep Frequency Response Analysis
A method to measure the frequency response of the passive elements (RLC) of a transformer. The result is a transfer function which produces a fingerprint related to the mechanical geometry of the transformer. SFRA relates to Mechanical Integrity
SFRA – What do you get?
Main winding
Tap leads Core
Tap windings
Conclusions SFRA is a means to provide data about transformer mechanical integrity Good results lead to good decisions Doble support means you can extract value from your SFRA measurements
Together We Power The World
SFRA Training Introduction: RLC, dB & MHz
SFRA Theory and Practice
• In a passive device there are three basic components: – resistors – capacitors – inductors • They each have a different response to an AC signal • Their response is closely related to their geometry: both internal and in relation to other components
FRA theory
What is a winding ?
Inductance
Series capacitance
Shunt capacitance
High frequency model
Winding
• inductance • series capacitance ( turn to turn ) • shunt capacitance ( turn to earth )
• winding geometry determines values of L and C
Winding frequency responses
• windings have frequency dependent response for transmitted signals • the detailed form of the frequency response depends on winding geometry • a change in geometry will change the frequency response
FRA theory
If we can measure changes in the frequency response of a winding caused by winding movement, then we can detect winding movement
SFRA Theory and Practice • Impedance of an ideal resistor, capacitor and inductor 450 400
Resistance:
s350 m h300 O , e250 c n a200 d e150 p m100 I
flat response v. frequency
Inductor: Increased impedance with increased frequency; dead short at low frequency
50 0 0.1
Capacitor:
1
10
100
1000
Frequency, Hz
Reduced impedance with increased frequency; open circuit at low frequency
SFRA Theory and Practice
• dB’s: as impedance increases, Vout falls V in
V out Impedance, Z
Response in dB’s = 20 log10 (Vout /Vin)
• Each 20 dB drop means we are looking at a tenth of the previous Vout/Vin
SFRA Theory and Practice Each 20 dB drop means we are looking at a tenth of the previous Vout/Vin Response in dB’s = 20 log10(Vout/Vin) +20 dBs 0
Vout = 10 * Vin
-20
Vout = 0.1 * Vin
Vout = Vin
-40
Vout = 0.01 * Vin
-60
Vout = 0.001 * Vin
SFRA Theory and Practice Need to reference each measurement to ground V signal
50 Coax Signal Lead
V in
V out Im pedance, Z
50 Coax Reference Measurement Lead
50 Coax Test Measurement Lead
Means we get a consistent measurement
SFRA Theory and Practice
Response of a short circuit 0 Response, dB -25
Response
-50 Frequency, Hz
0 dB across the frequency range
SFRA Theory and Practice Response of ideal resistors - no inductance or capacitance present 0 Response, dB
50 Response
-25 500 Response -50 Frequency, Hz
Flat across the frequency range
SFRA Theory and Practice
Response of an ideal inductor
0 dB down at low frequency means it looks like a dead short
Inductive roll off
Larger inductances start to roll off at lower frequencies
SFRA Theory and Practice
Response of ideal capacitor ‘Knee’ point depends on size of capacitor
Low frequency response is like an open circuit
Capacitive climb back
0 dB down at high frequency like a dead short
SFRA Theory and Practice Parallel RLC Circuit:
Constant dBs down v. frequency
Dead short at low frequency
Open circuit at high frequency
Open circuit at low frequency
Dead short at high frequency
SFRA Theory and Practice Impedance of the Parallel RLC Circuit:
R affects size of resonance peak
Resonant frequency depends only on L and C values 6 s 5 m h O4 , e c 3 n a d 2 e p m1 I
0 0.1
1
10 Frequency, Hz
100
1000
SFRA Theory and Practice Response of the RLC Circuit:
Inductive roll off
Capacitive climb back
Resonance
4. Understanding SFRA - Basic Principle Response of Multiple Circuits:
System 1
Vin
Vout
System 2
0 -20 -40 -60 -80 -100
Resonance ?
Resonance ? 100
Resonance ?
1010
SFRA Theory and Practice • We get a resonance for an inductor-capacitor (LC) combination • Changing L or changing C gives a new resonance • L and C are dependent on geometry • Changing R changes the size of the resonance
Real World Measurements
HV
A real C Winding C transformer has R many inductance and C capacitances
T
H
C
CT
H
LH
C H
LH
RH
H
H
L
RL
LV Winding
CL
Inter CH
CH
L
L
LL CT
CL
RL
LL
Winding
Each LC pair C givesC a resonance T
L
SFRA Theory and Practice
• Need to reference each measurement to ground V signal
50 Coax Signal Lead
V in
V out Im pedance, Z
50 Coax Reference Measurement Lead
Means we get a consistent measurement
50 Coax Test Measurement Lead
SFRA is really many measurements
Some individual resonances
Hardware Test Leads • Three lead system Signal + Reference Measure Ground Ground Signal
M5x00
Signal & Reference Leads Measurement lead
5. SFR SFRA A – M5 M5000 000 Se Seri ries es
M5200
M5300
M5400
5. M5000 Test Cable At Test Test Set Set - Color Color Cod Coded ed Lead Leadss Yellow - Sign Signal al (Giv (Gives es Vin Vin))
Red -- Refere Red Reference nce (Mea (Measur sures es Vin) Vin) Black Black - Test Test (Meas (Measure ure Vout Vout))
At Transformer Red => Red => Vin Black => Vout Lead Grounds Lead Grounds to Base of Bushings Safety Safety Ground Ground - Twist Twist Lock Lock to to Tran Transfo sforme rmer r
A note about Test Leads
• 60 ft /18 m • Cabl Cablee Trun Trunk k
30 ft to the the spli splitt
• Shie Shield ld Grou Ground nd
12 ft
• Appl Applic icat atio ion n
use use if <= 362 362 kV
• 100 ft /30 m • Cabl Cablee Trun Trunk k
55 ft to the the spli splitt
• Shie Shield ld Grou Ground nd
18 ft
• Appl Applic icat atio ion n
use use if > 362 362 kV
• No long longeer usi using ng the the whi white te jum jumpers pers
Hardware Test Leads IEC Definitions Source lead The lead connected to the voltage source of the measuring equipment used to supply an input voltage to the test object. Reference lead (Vin) The lead connected to the reference channel of the measuring equipment used to measure the input voltage to the test object ( Vin). Response lead (Vout) The lead connected to the response channel of the measuring equipment used to measure the output voltage of the test object ( Vout)
FRA test leads and equipment • Hig igh h fre frequ quen ency cy coo-ax axia iall ca cabl blee • Impe Impeda danc ncee mat match ched ed ( 50 50 ohm ohmss ) at eq equi uipm pmen entt (to avoid reflections in test leads) • Separate S and R leads for applying and measuring signal at input terminal Only then will layout of test leads have no effect on measurement
• Any length ( 18 m popular )
Applied and measured signals
Vo
Vi
Res Re s p o n s e = Vo /V /Vii
Freque requenc ncy y Resp spon onse se An Ana aly lysi sis s
Sweep Frequency Method
V out H (dB ) 20 log10 V in 1 V out H ( ) tan V in
Most Useful Frequency Range 20 Hz - 2 MHz MHz
Tutorial Session - Frequency Response Analysis
Achieve a Two Port Network
Hardware Range & Resolution
Signal Generation: Range & Resolution Two independent measurement channels Oversample at up to 100 MS/s 20 V p-p 10 Hz-25 MHz Log Scale at 1.02% of frequency
Conclusions RLC components have different SFRA responses Even simple circuits may have complex responses ‘Real’ transformers have many resonances
Together og ether We Power The Wor World ld
SFRA SFR A Tra raini ining ng Test Procedures
SFRA Test Procedures There is a basic set of recommended tests for any transformer. Doble software comes complete with templates which have IEEE and CIGRE compliant tests. Further tests may be performed for diagnostic purposes: per phase short circuit circuit interwinding tests Reverse short circuit etc
Setting up the transformer
• Tran Transf sfor orme merr sho shoul uld d be be dis disco conn nnec ecte ted d from system. Bu Busb sbar arss re remo move ved d if possible. Line, neutral and any tertiary line connections shall be disconnected but tank earth, internal auxiliary equipment and internal current transformer connections shall remain connected. • Tran Transf sfor orme merr shou should ld be in norm normal al service condition (assembled, oilfilled).
Setting up the transformer
• Make Make conn connec ecti tion onss as as det deter ermi mine ned d by by winding configuration. Phases not under test are usually left floating. • In the the cas casee whe where re two two con conne nect ctio ions ns to one corner of a delta winding are brought out, the transformer shall be measured with the delta closed but not with the earth connected.
Setting up the transformer
• If spec specia iall conn connec ectio tions ns have have been been specif specified ied and are provided on the test object to enable a frequency response measurement to be made when it is arranged for transport then the measurement must be made in both the fully assembled (fluid filled) and transport configurations (drained if required for transport) before transport and subsequently as specified by the purchaser. • Bewa Beware re of diff differ eren entt state statess of of oil oil dra drain ining ing
Setting up the transformer
• It is important that SFRA measurements are always made in a consistent way and that all details of the measurement method are systematically recorded. This will help to avoid false discrepancies and ensure the compatibility of frequency responses during comparison.
Typical Measurements – two winding unit
• Connections - look at each winding separately: • Make measurements at extreme raise LTC and nominal DETC • With previous results – repeat those procedures HV - H1-H2, H2-H3, H3-H1 LV - X1-X0, X2-X0, X3-X0 Short Circuit - H1-H2, H2-H3, H3-H1 with X1-X2-X3-X1 shorted (all three phases, not X0)
FRA test connections
FRA test connections
Measurements
5. SFRA Test Procedure • Open-Circuit (OC) Tests • Short-Circuit (SC) Tests • Supplementary Test: Inter-Winding Tests LTC at extreme rise (16R or 1). DETC at nominal position. If possible to do additional tests - e.g. various tap
positions, short circuit tests, tertiary tests etc.
5. Typical Test Procedure Delta-Wye – Open Circuit (OC) Tests Red H1 H2 H3 -
Black H3 H1 H2
X1 X2 X3 -
X0 X0 X0
Supplementary H1 - X1 H2 - X2 H3 - X3
HV Winding Tests
LV Winding Tests
Inter-Winding Tests
5. Typical Test Connections Delta-Wye – Short Circuit (SC) Tests Red
Black
H1 - H3 H2 - H1 H3 - H2
Short-Circuiting X1X2X3X1 X1X2X3X1 X1X2X3X1
Other Test Connections
Software Nameplate Test Template
SFRA Trace Shorted Leads What – kind of trace?
SFRA Trace – Open in Test Circuit What kind of trace?
Open Circuit inside test specimen
Open Circuit within test leads
What would be the measurements ? Single phase two winding unit? Three phase three winding D-D-Y unit? Check Latest Doble connection guide
Measurements Example from Manual
S/C Connections
Measurements Example from Manual
Measurements
Typical Results - Conclusions
• Results should be expected form • Make sure connections are appropriate for transformers • Check with previous results for consistency
Troubleshooting
• Shorted cable measurement • Shorted cable – open ground measurement • Open cable measurement • Ground check on transformer • Repeat measurements on ‘good’ winding • Does it make sense????
Troubleshooting
If differences are observed when comparing with a finger print result, it is important to first verify the measurement by repeating to ensure that the differences are not caused by bad measurement practice or by making different measurement connection.
Together We Power The World
SFRA Training Typical Results
Wye-wye : HV’s Note low frequency variations
Wye-wye: LV’s Less dB down than HV
Wye-wye HV Short Circuit LV windings shorted
Another HV Wye HV winding – three phases one DETC positions
Another HV Wye Detail – three phases Center phase Two outer phases
Another HV Wye Detail – three phases
Center phase
Two outer phases
Delta-wye HV’s Typical response at low frequencies
Delta-Wye: LV’s Less dB down than HV
4. Simple Transformer Model Which Winding has higher impedance?
Which trace is highest and lowest? • OC HV Trace • OC LV Trace • SC Trace
Lowest Middle Highest
Open Circuit (OC) HV
LV
Vi
Vi
Vo
Vo Short Circuit (SC) HV
Vi Vo
LV
4. Simple Transformer Model
HV
• Which trace is VH
LV
Vi
Vi
VH
ZH > ZL: VH: Lower response or more attenuated
0 -20 VL -40 -60 -80 -100
VL
VH 100
1010
Delta-Wye HV Short Circuit LV windings shorted together
Autotransformer HV HV LV LV and Terti Tertiary ary compared compared
Tertiary winding
LV (common) winding
HV (series) winding
Measurement Sense: H1-H0 v. H0-H1
Effect Effect is smaller when the two bushings are simila similarr – e.g. e.g. H1-H H1-H3 3 v H3-H H3-H1 1 H0-H1
H1-H0
Variation with LTC position 16 Lower through 8 Lower for one winding
Variation with LTC position Mid frequency detail
16 Lower
8 Lower
Variation with and without oil LV winding
With oil – Lower resonant frequencies
Without oil Higher resonant frequencies
Effect of Bad grounds Original and Bad Red lead ground
Bad red lead ground
Original
Effect of Bad grounds Original and Bad Black lead ground
Original
Bad red lead ground
Effect of Magnetization Low frequency variation is severe – but identifiable Magnetization affects the core response
Magnetization & Grounding variation
HV winding High frequency variation due to grounding
Magnetized center phase
Magnetization affects the core response
Sister Units showing Magnetization HV winding
Magnetization variation
Sister Units showing Magnetization HV winding – same unit, more magnetization
Magnetization variation
HV Wye winding: Open and Short HV winding – same unit, more magnetization
Short circuit wye winding
Open circuit wye winding Very similar at high frequencies
HV Delta winding: Open and Short HV winding – same unit, more magnetization
Short Circuit
Open Circuit
Similar at high frequencies
Typical Results - Conclusions
• Results vary between units – depending on size and type of unit • Results vary with magnetization & grounding • Results vary with tap changer positions • Results vary with oil level • Know what to expect – see next slide!!!
4. Simple Transformer Model
HV
Vi VH
• Which trace is VCHL
LV
VCHL CHL
CHL: High-to-Low or Inter-Winding
0 -20 -40 -60 -80 -100
VCHL
VH 100
1010
One Transformer: HV, LV, SC & IW
IW = Interwinding measurement Short Circuit
LV Open Circuit
HV Open Circuit H-X interwinding
Wye : HV open circuit Note low frequency variations 2Highs and 1 Low V and W shape
Interpretation • Experience: Certain Frequency Bands Indicate Different Problem Conditions 400kHz to 2MHz: Movement of main and tap winding leads
<2kHz: Core Deformation, Open Circuits, Shorted Turns & Residual Magnetism
2kHz to 20kHz: Bulk Winding Movement Relative to Each Other, clamping structure
20 kHz to 400kHz: Deformation Within the main and tap windings
4. Simple Transformer Model High W shape = A/C Phase
Low
A Vi
V shape = B Phase
Vo
=> Exciting Currents = 2 similar Highs & 1 Low
B
High
C
2. SFRA – Logarithm Graph
100 Hz
1 MHz
2. What is SFRA? – Linear Graph
Impossible to see 100 Hz
Interpretation
Power of a Null Result
• 600 MVA GSU Transformer • SFRA results from factory and initial field • New SFRA results taken after the fire
Fire: factory to field comparison HV and LV results overlay almost exactly up to 2 MHz
Short circuit results to within 0.01 dB
Low frequency variations are due to core magnetization
Post fire conclusions • Results show no variation to 2 MHz using different: – Doble test sets – test personnel – test leads – lead positions etc
Post fire conclusions • SFRA results show no indication of a mechanical problem within the transformer – this is a NULL result • SFRA data was key in the decision to return the unit to service • Full details in 2005 Doble Conference Paper
Together We Power The World
SFRA Training Open and Short Circuit Test Variation
SFRA Typical Results This presentation gives typical results for open and short circuit tests It explains why the two tests are different and the value in each test A T-model of a transformer is used to make things clearer Only low frequencies are considered – no capacitive effects
Test Connections - SFRA Open Circuit Normal test on HVs the LVs float HV Winding Signal & Reference
LV Winding
R small
R small
Core
M5100
R high
Test
Model is relevant for LOW FREQUENCIES
Test Connections - SFRA Short Circuit Short circuit test on HVs - LVs shorted HV Winding Signal & Reference
LV Winding
R small
R small
Core
M5100
LV Short
R high
Test
Model is relevant for LOW FREQUENCIES
Short Circuit v. Open Circuit Open circuit responses dominated by core at low frequency – as with Exciting current Different magnetic paths lead to different responses – typical outer v center phase variation Short circuit responses remove effect of core at low frequencies – as with leakage Reactance All three short circuit responses should be identical
Short Circuit Test - Setup
• Short secondaries together, use proper size jumpers, close the delta, X1-X2-X3-X1 • Do not short multiple secondaries together • Test each phase – Phase A – Phase B – Phase C
Short Circuit (SC) Analysis
• Analyze the “inductive roll-off” region • This roll-off defines the primary winding inductance model • Very similar to the LRT
SC Analysis • The SC test the phases should be no further than 0.1 dB from each other • Roll-off should be close to -20dB/decade • Analysis will require you to zoom in very close
Step 1: Overlay the three HVSC Test Results
Step 2: Zoom in on the LF Region that shows the “Inductive Roll-off”
Step 3: Identify the key artifacts A) LF DC Section B) Inductive Roll-off Knee (Low-Pass Filter Cut-off Frequency) C) Inductive Roll-off Section D)End of Inductive Roll-off
Step 4: Analyze LF DC Section This is the few points that are at the very beginning – 20 Hz There should be very close offset between the three results. If there is a fan-out at the beginning this could indicate a winding resistance problem. Recommend a winding resistance test
This example is good
Step 5: Locating the Knee point. Starting at 20 Hz, look for maximum deflection point where the traces go into the inductive roll-off section (next slides explains this more) The LP Filter cut-off frequency by definition is the point where the frequency response goes from flat to -3db down
Start
“Inductive Roll-off”
Step 5: Find the start and end points of the “Inductive Roll-off” The inductive roll-off is the ramped linear section that drops at -20dB/Decade. On a logarithmic plot it appears as a linear ramp. One of the reasons logarithmic display is better than linear.
Stop
Use the ruler-method if you need to find where the ramp stays linear (straight line ramp down to the right). Find the start and stop points where is stays on a straight edge
“Inductive Roll-off”
Zoom in here
Step 6: Choose a point to analyze Select a point somewhere very close to the half way points between Start and Stop and zoom in very tight
Step 7: Calculate the offset 12.64-12.57=0.07dB = GOOD! In general, most transformers will be below 0.1 db offset, but up to 0.2 dB is not uncommon. This analysis is sensitive to the same issues as Leakage Reactance.
HV Wye winding: Open and Short HV winding – same unit, more magnetization
Short circuit wye winding
Open circuit wye winding Very similar at high frequencies
Good Short Circuit Results Good Transformer – Good Results – Lo Frequency
All three have same roll off All three have very similar resistance element at 20 Hz Resistive section in this case is not horizontal. This is common
SC Analysis
• If SC results do not match.... – at 20 Hz -> Check Winding Resistance Variation in results may occur near 20 Hz due to variation in resistance element of shorting leads. May indicate a need to check transformer with DC resistance tests
– Compare LRT results throughout roll off – Variation in inductive roll off is due to variation in winding impedance
• Center phase may be slightly different • We expect all three phases to be within 0.1 dB
Short Circuit Variation Recommended is a three phase equivalent short circuit test Can do a per phase equivalent by repeating tests and just shorting appropriate LV winding Can do LV short circuit (with HV’s shorted) Per phase and LV measurements are useful in diagnostic investigations
Short Circuit v. Open Circuit At open circuit the load on the LV side is ‘infinite’ At short circuit the load on the LV side is zero We should expect a result to lie between the open and short circuit results!
Case Studies 1 Shorted Turn 2 Hoop Buckling 3 Axial Collapse 4 Clamping Failure 5 Bushing Failure
Case 1: Shorted Turn
• Demonstrates need for good low frequency resolution • Many electrical tests should show a shorted turn • No baseline data required for diagnosis
Case 1: Normal Response Three normal open circuit responses
Results as expected and
Three phases respond differently at low frequencies acceptable
Case 1: Shorted Turn After an incident - one year later... One phase has clear inductive roll off associated with short circuit measurement
Variation is clear indicator of shorted turn on A phase
Case 1: Shorted Turn Low frequency responses clearly show inductive roll off associated with short circuit measurement Another transformer - no reference results
Results indicate shorted turn on one phase
Case 2: Hoop Buckling • Compressive Failure of Winding - also known as Hoop Buckling – Need repeatability to within 1 dB – Need low frequency repeatability to within 0.3 dB
• Expect increase in LC combination of winding bulk - seen as left shift of resonance at mid range • Consequent increase in winding impedance - seen in short circuit results
Case 2: Hoop Buckling
• Example here of two 28 MVA sister units • One known bad after internal inspection • Other unit suspect based on Dissolved Gas Analysis
Case 2: Hoop Buckling
Inspection of bad transformer revealed hoop buckling on TWO windings
Clear bulge in winding
Case 2: Hoop Buckling Open Circuit LV results
Two bad phases have shift to lower frequency at this frequency
The B phase is different which may be due to design and construction
By itself, this is not conclusive evidence as we have no reference results
Case 2: Hoop Buckling
Low frequency short circuit results show consistent increased impedance on bad phases
The variation was consistent and repeatable: attributable to variation within the transformer
Results are anomalous but symmetrical evidence is inconclusive
0.2 dB delta is significant here!
Case 2: Hoop Buckling
• For the bad transformer we have picked out two possible indicators of variation for the two bad phases • For the suspect unit, we look at the same areas
Case 2: Hoop Buckling Open circuit results show same effect on ONE phase
Clear shift left at same frequency range
In the known bad unit two phases had Now we have just one phase shift left a shift left and both had hoop buckling
Small change in frequency and dB
Case 2: Hoop Buckling
Both units - displayed for comparison
This is good evidence that one phase may have hoop buckling
Case 2: Hoop Buckling Suspect unit shows same increased impedance (more dB’s down) for one phase - the same one with the shift left on open circuit results
One phase appears to have symptoms of hoop buckling
0.2 dB delta is significant here!
Case 2: Hoop Buckling • Diagnosis is that suspect unit has one bad phase through hoop buckling • Transformer is bent, but not broken • Unit was returned to service for some months, under advice that it was less likely to withstand a close in fault • Subsequent internal inspection revealed hoop buckling on the suspect phase, as expected and predicted
Case 2: Hoop Buckling Inspection showed hoop buckling on suspect phase - as predicted
Transformer returned to service before being rewound
Case 2: Hoop Buckling
• Need good resolution - especially below 1 kHz for short circuit results • Need good repeatability over a range (less than 0.3 dB) • Use of results from similar unit as reference was key for diagnosis
Case 3: Axial Shift of a Winding
• Example uses reference results taken 7 years previously • Need range up over 1 MHz • Need repeatability to within 1% • Need confidence in results to avoid a false negative • Failure mode is reduction in LC combination • Resonances should shift right at higher frequencies as a consequence of LC reduction
Case 3: Axial Shift of a Winding
Scattered blocking under a collapsed winding
Case 3: Axial Shift of a Winding 0 Results from one GOOD phase taken in 1994 and 2001 -10 -20 B d n i -30 e d u t i l -40 p m A -50 -60
Small dB variations are acceptable: no 0.5 betweenFrequency tracesin implies MHz LC variation implied
-70 0
No variation that THIS PHASE has little change 22/11/94
8/11/01
1
Case 3: Axial Shift of a Winding 0 Results from bad phase taken in 1994 and 2001 -10 -20 B d n i -30 e d u t i l -40 p m A -50 -60
Low frequency results, up to -70 over 200 0 kHz, are acceptable
Clear and consistent shift to higher frequencies of several resonances 0.5
Variation implies we have Frequency in MHz a substantial problem 22/11/94
8/11/01
1
Case 3: Axial Shift of a Winding 0 -10
Good SFRA repeatability gives confidence in the integrity of the good phase
-20 B d n i -30 e d u t i l -40 p m A -50 0
-60 -10
-70 0
0.5
Good SFRA repeatability allows confident diagnosis of bad phase
-20 B d n i -30 e d u t i l -40 p m A -50
1
-60 -70 0
0.5
Frequency in MHz
1
Case 3: Axial Shift of a Winding
• Bad phase clearly identified • SFRA results up to >1 MHz required • SFRA results taken with different test sets by different test teams • Repeatability is key
Case 4: Clamping Failure
• 750 MVA transmission transformer • Close in fault caused center winding to ‘jump’ and break the clamping • Stress shield dropped on to winding, altering capacitance of that winding
Case 4: Clamping Failure
Clamping beam broken
Stress shield collapsed on to center phase
Case 4: Clamping Failure
Three HV phase results shown together 0
Center phase shows shift to lower frequency for first resonances
-10
-20
-30
B d n i e d -40 u t i l p m A
-50
-60
-70
-80
Low frequency results show expectedfurther form Transformer has a problem investigation required
0
5
Frequency in kHz10
15
20
Case 4: Clamping Failure
• Initial low frequency (< 2kHz) core related resonance unaffected • Resonances usually associated with bulk capacitance of windings to ground are moved to lower frequencies
Case 5: Bushing Failure
• Transmission Transformer had a bushing failure • No reference results available • Did the failure move the windings? • Sister unit available for reference
Case 5: Bushing Failure Minor variations in suspect unit at high frequencies may relate to some internal lead movement
Variation is small - but needs further investigation
Low frequency variation as expected between phases
Case 5: Bushing Failure Six traces here - suspect unit and sister unit
Variation is still a concern - need to do a phase-by-phase comparison of two sister units
Case 5: Bushing Failure There are two traces here - suspect phase of suspect unit and same phase of sister transformer
The two traces are clearly very similar can just see one trace behind the other
Sister unit has exactly the same variation - it must be design related as traces implies this sister is known good
No variation between phase is OK, despite bushing failure
Case 5: Bushing Failure
• Suspect phase does show some variation at high frequency • Sister unit shows same variation known to be a good transformer • Consequently - SFRA variation is due to design and construction
Case 5: Bushing Failure
• Sister Transformers may show variation between corresponding phases on each transformer • If two phases are similar between the two units, it is likely that the third phase is also similar • So we can use sister units as a reference, even if there are variations in response between the units
Interpretation • Experience: Certain Frequency Bands Indicate Different Problem Conditions
400kHz to 2MHz: Movement of main and tap winding leads
<2kHz: Core Deformation, Open Circuits, Shorted Turns & Residual Magnetism
2kHz to 20kHz: Bulk Winding Movement Relative to Each Other, clamping structure
20 kHz to 400kHz: Deformation Within the main and tap windings
Together We Power The World
SFRA Training Using the Software
Using the Software Communication protocol – Ethernet cable
Using the Software Communication protocol – CSMUAB (USB) Cable
USB Drivers
• Communication: Ethernet or USB over Ethernet • Ethernet 192.168.1.0 • USB over Ethernet 192.168.1.1 • Windows will ask to install the USB driver when the USB cable is plugged into the M5X00 for the first time. • Point to location of USB drivers
Windows Vista
• SFRA V5.1 will operate on Windows VISTA • The communication limitations still apply, regarding profiles and settings • One issue has surfaced.
VISTA Workaround
• Some people have had issues even when logged in as an administrator. • The workaround so far has been to tell the user to turn off the 'User Account Control' in the Vista User Manager. • Turning this off has fixed every issue we have had so far.
User Account Control
SFRA Software The best way to become familiar with the software is to use it Topics on the following slides may help direct discussion and experimentation
To try… Software installation Connect to an M5200 Data management: settings, folders and files Test philosophy: Set up data files Select particular files Run test Review results
To try… Choosing & Using templates Select Apparatus & Run test Reviewing, overlaying and comparing data Analysis tab Filenames & e-mailing files
Conclusions Key points: Collect data in an organized manner Always make notes for tap positions Backup for your test data regularly
Together We Power The World
SFRA Training Basic Analysis
3. Are Baseline Results Necessary? Not always - but they are preferable Phase-to-phase comparisons Comparison with sister units Comparison with units from the same manufacturer Results have a generally predictable shape
SFRA Analysis is Logical Analyzing SFRA data is a logical and methodical process Examples are given here to show the approach taken
SFRA Analysis : getting Started Make sure all results are available: Current SFRA results Any previous SFRA results Any results from similar units Any electrical test or DGA data Understand the context: why are these tests being performed?
In general Trace shapes: HV LV Short Circuit Do they look as expected? Any variance?
Analysis with benchmark Have the same measurements been made? LTC and DETC the same? Oil, bushings etc
Sister Units Real sister? Example
Phase-by-phase When it gets down to basics…
Causes of variation Check two useful documents: Practical variability Field and Factory variation
Integration
SFRA is one tool in the tool box Capacitance
OC: Open Circuit
Exciting Currents
DC Resistance
SFRA
SC: Short Circuit
Leakage Reactance
Context Link SFRA to other tests: DC resistance Leakage Reactance Exciting Currents Capacitance
Conclusions Analysis takes experience and time
Using Cross-Correlation Coefficients to Analyze Transformer SFRA Traces
The Problem
• Analyzing SFRA Traces can be Challenging • No simple categorization available • Natural desire to apply “limits” to SFRA results • “Smart” SFRA analysis routines may have dubious outputs
The Reality
• Human element needed - pictures • Every transformer is an individual • No perfect “pass/fail” criteria for any range • SFRA analysis is still prone to outlandish claims from some quarters • Someone has to know what they are doing…
The Stop-Gap
• Cross-correlation coefficients (CCF) are commonly used in a variety of industries to monitor signal integrity • CCF’s provide a method to: – Quantify SFRA Trace similarities – Communicate results – Apply limits to analysis – Don’t rely on hidden or secret “black box” analysis routines
What is a CCF really?
• Take two sets of numbers • Work out a ‘sameness’ value • Same… different… opposite… • Math is simple, as shown here
Still keeping the math simple....
2
CCF
( Xi X )(Yi Y ) ( Xi X ) * (Yi Y ) 2
2
In words, the CCF calculates the convoluted mean error and normalizes to the individual mean over a particular range of frequencies
Keeping the math simple....
• CCF is a number between 1.0 and 1.0. • For SFRA, it’s usually between 1.0 and 0.0 • The closer the value is to 1.0, the more similar the traces are. • The lower the value, the more the two traces diverge. • CCF can also be expressed in Percent
Example CCFs
CCF Good Match
0.95-1.0
Close Match
0.90-1.0
Poor Match
<.89
No or very poor match
<= 0.0
What you really need to know
Regions of Interest Region
Frequency Sub-Band
Components
1
< 2kHz
Main Core; Bulk Winding Inductance
2
2kHz to 20 kHz
Bulk Component Shunt Impedances
3
20 kHz to 400 kHz
Main Windings
4
400 kHz to ~1 Mhz
Main windings, Tap windings etc
Every transformer is different, these are just general guidelines
SFRA Regions
Select your Band and Calculate
Selecting Limits • Depending on the type of comparison , the CCFs limit should be adjusted. Starting Point! – Benchmark comparison:
– Phase to Phase (A/C) or sister units:
Case 1: Benchmark Comparison
• 675 MVA GSU built in 2002 • Suffered a fire on connected iso-phase bus • Bushing had been degraded during the fire – Expect some high frequency variation
• The unit was known to be magnetized – Expect some low frequency variation
Case 1: Benchmark Comparison: H2-H0
Frequency Sub Band
CCF
Region 1: 0 - 2 kHz
0.9879
Region 2: 2kHz – 20 kHz
0.9964
Region 3: 20 kHz – 400 kHz
0.9882
Region 4: 400 kHz – 1 MHz
0.9988
Case 2: Phase-to-phase : Bent Unit • 1960’s vintage GE 50 MVA transformer • Tripped out of server on protection • No reference SFRA results available • Phase to phase analysis required
Close up view of LV winding shift
Case 2: Bent Transformer: A/C Phase comparison
Frequency Sub Band
CCF
Region 1: 0 - 2 kHz
0.9831
Region 2: 2kHz – 20 kHz
0.9868
Region 3: 20 kHz – 400 kHz
0.8262
Region 4: 400 kHz – 1 MHz
0.9567
Case 3: Two Large Sister Units
• Two 370 MVA Alstom transformers • 345/14 kV • Routine health assessment of the units was conducted • SFRA was used to ascertain construction consistency between the units • Determines if two units are in fact identical
Case 3: Sister Units
Frequency Sub Band
CCF
Region 1: 0 - 2 kHz
0.9898
Region 2: 2kHz – 20 kHz
0.9994
Region 3: 20 kHz – 400 kHz
0.9914
Region 4: 400 kHz – 1 MHz
0.9923
Considerations
• Case studies did not change region limits – Not necessarily true in all cases – May change limits for different designs
• Recommended limits are starting points – Can adjust limits; situation may require fine tuning
• Still does not replace the trained SFRA user • Poor test technique can throw off results
Conclusion • CCF can help in the analysis of traces by drawing attention to various regions • CCF assign a “Figure of Merit” that can be used to quantify SFRA traces similarities • CCF can not diagnose the failure mode, only the trained human eye and experience can do that • Still does not replace the trained SFRA user
7. Conclusions
• SFRA is a useful and sensitive tool • Use in Conjunction with other Tools • SFRA is a reliable and repeatable means of making FRA measurements • Use on relocation or after an incident • Use as part of factory QA
7. Notes...
• Need for good grounds • Make sure transformer is in the same state as last time • Use a reference library
SFRA Case Studies: Dealing With Noise
Presented by Doble Engineering Company
Signal To Noise Ratio (SNR) Neighboring Transformers
The Test signal can become “swallowed” by neighboring sources of interference The Real World has Real Sources of Line interference Doble Provides 20 Vpp to prevent this problem.
Substation Equipment
Overhead Lines
Ground Grids 239
SNR: Why it’s important You may end up measuring the surrounding noise.
Results for a test set using low SNR
Doble SFRA Leads Clip-1
•Tests above 1 MHz are dominated by the test leads (IEC & IEEE) • Every test connection is a chance to make a mistake and mess up results; Doble keeps it simple
Done.
•We all test in every possible environment so don’t complicate it!
Clip-2
241
Inside Transformers
Adverse Weather
At Night
Advanced Analysis: Cross Correlation & Difference
Cross-Correlation Analysis - Assess Condition by Winding Region Difference Analysis - Compare offset variations for simple quick analysis
242
Technical – automated analysis •
Diagnosis by difference and cross correlation is most advanced available
•
Training and support mean we don’t lose sight of the ‘picture’, numbers can only tell you so much
•
Cross-correlation (CC) looks at curve shape – will be the basis of the Doble expert system
•
Some systems have a single CC value for the whole trace
243
Intermediate Frequency (IF) Bandwidth
Frequency to be measured
Doble follows Laboratory Best Practices of always ensuring IF Bandwidth is < 10 % In simple Terms: We don’t try to make the results look prettier by allowing other surrounding signals to smooth the result out.
Doble
Some Others
244
Nameplate Information
• Auto Transformer with Tertiary • 20 MVA • 138/69/13.2 kV • Year of manufacture: 2011 • Test configuration: – No Oil – Spark plug (transit) Bushings
The story unfolds
SFRA tests were performed on a transformer after delivery to the site and then compared to factory results Something didn’t quite agree…..
H1-X1 Comparison to Factory
X2-H0X0 Comparison to Factory
Hey why are these different? Site Test
Factory Results
HVSC Test Results
Summary of initial SFRA analysis • Both HVOC and LVOC results were satisfactory when compared to previous • Upon evaluation it was decided the HVSC results did not compare to factory tests • An investigation followed and ultimately the transformer was tested again
The Investigation showed …. • That the shorting leads for the HVSC tests were allowed to sag and come in contact with the transformer tank. • The leads were tightened up with no sagging and the short circuit tests were performed again.
Retest Satisfactory - 9 tests shown Shorting leads resting on tank
Factory results and Retest after fixi ng the leads
Nameplate Information
• Auto Transformer with Tertiary • 100 MVA • 220/132 kV • New unit • Test configuration: – Fully dressed
The story unfolds
SFRA tests were performed on a transformer after delivery to the site and then compared to factory results Field results were different when compared to previous (factory) tests Again, something didn’t quite agree…..
Series Winding Factory vs. Field
Field
Factory
Common Winding Factory vs. Field
Field
Factory
Field retest after Demagnetization But what is this here?
This is better
Let’s get a closer look
Series Winding
Field Retest
Common winding field retest
This isn’ t good
This is better
Conclusion Effects of magnetic viscosity were evident in both the series and common windings between tests. Cause of difference in field retest – Tertiary was ungrounded for the test
SFRA Case Studies: Field LV Anomaly
Presented by Doble Engineering Company
Nameplate Information
• 125 MVA • 220 kV Wye Delta • Three winding transformer • In service unit, DGA starting at the end of previous year showed rising trend • SFRA was performed
Initial SFRA analysis
• SFRA results indicated problems in the LV • Even to the untrained eye one should be able to pick out the differences
LVOC SFRA Test
Houston we have a problem!
Time to go inside
An internal investigation was conducted and visible evidence of the problem was found, Pictures tell the story
Internal inspection
Internal Inspection
Internal Inspection
SFRA LVOC after repair
SFRA Example Transformer Type: 3 Power Transformer Manufacturer: Waukesha Capacity: 30/40/50 MVA Voltage: 138/27 kV Tap Changer:
10% load tap changer; HV reconfiguration
tap changer, de-energized Entered service July 2002 Removed from service two weeks later
Transformer
SFRA Example Indications Tank temperature recorded at 480 F (230 C) Slight tank wall bulge Tank wall discoloration Strange noises while in service DGA
Acetylene from 0 to >300 Hydrogen from 10s to >500 FFAs from low to high
SFRA Example
Transformer Turns Ratio
Within 0.3% of nameplate and previous
results
SFRA Example DETC Pos C B A D E C C C C C C C C C C C C C C C C C
LTC Pos 1R 1R 1R 1R 1R N 1L 2L 3L 4L 5L 6L 7L 8L 9L 10L 11L 12L 13L 14L 15L 16L
H1-H2 X0-X2 7/22/02 8/5/02 8.809 8.811 9.033 9.035 9.258 9.260 8.575 8.574 8.336 8.340 8.861 N/P 8.919 8.911 8.976 8.964 9.033 9.018 9.090 9.075 9.149 9.133 9.208 9.190 9.268 9.250 9.329 9.310 9.391 9.370 9.460 9.433 9.516 9.495 9.580 9.559 9.645 9.623 9.711 9.688 9.785 9.745 9.846 9.821
H2-H3 X0-X3 % 7/22/02 8/5/02 8.808 -0.02% 8.809 9.032 -0.02% 9.033 9.257 -0.02% 9.258 8.572 0.01% 8.573 8.338 -0.05% 8.336 8.861 N/P N/A 8.918 0.09% 8.919 8.975 0.13% 8.976 9.031 0.17% 9.033 9.090 0.17% 9.090 9.149 0.17% 9.149 9.208 0.20% 9.211 9.268 9.268 0.19% 9.310 0.20% 9.329 9.391 0.22% 9.391 9.453 0.29% 9.453 9.518 0.22% 9.523 9.582 0.22% 9.588 9.647 0.23% 9.645 9.713 0.24% 9.711 9.780 0.41% 9.782 9.849 0.25% 9.846
H3-H1 X0-X1 % 7/22/02 8/5/02 8.808 0.01% 8.809 9.032 0.01% 9.033 9.257 0.01% 9.258 8.572 0.01% 8.573 8.338 -0.03% 8.336 8.864 N/P N/A 8.918 0.01% 8.919 8.975 0.01% 8.976 9.031 0.02% 9.033 9.090 0.00% 9.090 9.148 0.00% 9.149 9.208 0.03% 9.208 9.268 9.268 0.00% 9.310 0.20% 9.329 9.391 0.00% 9.391 9.453 0.00% 9.460 9.518 0.05% 9.516 9.582 0.06% 9.580 9.647 -0.02% 9.645 9.713 -0.02% 9.711 9.781 0.02% 9.785 9.849 -0.03% 9.849
% 0.01% 0.01% 0.01% 0.01% -0.03% N/A 0.01% 0.01% 0.02% 0.00% 0.01% 0.00% 0.00% 0.20% 0.00% 0.07% -0.02% -0.02% -0.02% -0.02% 0.04% 0.00%
Power Factor/Capacitance CHL rose by a factor of ~3; slight
capacitance rise Current (mA)
Watts-Loss (W)
7/22/02
8/13/02
%
7/22/02
8/13/02
%
CH
9.946
9.974
0.28
0.218
0.254
16.51
CHL
23.540
23.650
0.47
0.436
1.239
184.17
CL
59.410
59.660
0.42
1.371
1.420
3.57
% PF (Corrected to 20C)
Capacitance (pF)
7/22/02
8/13/02
%
7/22/02
8/13/02
%
CH
0.18
0.21
16.67
2638
2645
0.27
CHL
0.15
0.42
180.00
6245
6275
0.48
CL
0.18
0.19
5.56
15761
15825
0.41
Excitation Currents
Excitation Currents 10 9 8
H1-H2/mA
A 7 m
H2-H3/mA
6
H3-H1/mA
5 4
N
L 2
L 4
L 6
L 8
L 1 0
LTC Position
L 2 1
L 1 4
L 1 6
ea age Reactance Nameplate 9.39% Measured 3 phase equivalent 13.19%
Per Phase Impedance
H3-H1/ 596.60 32.36%
H1-H2/ H2-H3/ 174.00 173.30 9.15% 9.11%
SFRA Example
Discoloration and bulge
Fault pressure Relief valve (did not operate)
Low Voltage
High Voltage
High Voltage Short Circuit
Black specs...
Copper exposed on lead
Factory Inspection
Case Study
Autotransformer transportation damage found using SFRA
Transformer Before Shipment With oil and actual bushings –> H – X Open Circuit test
Transformer After Shipment No oil and w/spark plug bushings –> H – X Open Circuit test
Transformer After Shipment H2 – X2 Open Circuit test before and after comparison
Transformer After Shipment No oil and w/spark plug bushings –> Tertiary Open Circuit
Case Study # 1
As a result of the Swept Frequency Response Tests a decision was made to perform an internal inspection. The following was observed:
Internal Inspection
• Center winding clamping hardware loose resulting in loss of pressure on the stack • Y1 lead laying on top of core • Loose boards were found inside transformer
Internal Inspection
Internal Inspection
Internal Inspection
Loose Clamping
Internal Inspection
Internal Inspection
SFRA Case Studies: Possible Core Variation
Presented by Doble Engineering Company
Low Voltage Open Circuit Traces
Unit A Unit B Unit C
High Voltage Open Circuit Traces
Unit A Unit B Unit C
Before and after de-magnetizing
The suspect unit was de-magnetized at the plant by energizing the LV winding at 110% which is 15.2KV, 20 amps for 12 hours. There was very little change.
Suspect Unit, Low Voltage
Suspect Unit, High Voltage
Conclusion
Upon further investigation it was discovered that the core steels for all units was of the same grade (M4), however two of the transformers used the steel from one manufacturer and the third unit used the steel from a different manufacturer. This could have resulted in different core characteristics (e.g., permeability).
SFRA Case Studies: Magnetic Viscosity
Presented by Doble Engineering Company
Effect of Magnetization Low frequency variation may be severe
Magnetization affects the core response
Magnetic Viscosity
Drift can occur from demagnetized state to lowest energy state depending on internal geometry (see Spring 2010 paper)
SFRA Case Studies: Phase-to-Phase Find
Presented by Doble Engineering Company
Case Study
• 120 MVA, 245kV/144kV autotransformer • There was a fault and it was unclear if there had been damage to the unit • SFRA Testing was done to assess the condition of the unit • No historical data available
Nameplate data
SFRA HVOC results
Traces do not correlate well in this area
Suggests some kind of winding issue
SFRA HVSC results
Looking for less than 0.2 db phase separation; Zoom in to check
Some variation in magnitude & resonance
HVSC inductive roll-off region
0.13 db acceptable
Course of action
Based on the SFRA results a recommendation was made for internal inspection It was discovered that the tertiary winding connections had never been bolted together, and theorized that the energy from the fault had pushed the connection apart – There had been arcing across that opening
The missing Link
Internal Connection - Delta Link
Delta Link not made up
Conclusion
Although there wasn’t any previous data, a phase to phase comparison was enough to support the indication of a problem * This might have been caught at the factory if SFRA testing had been performed at that time
SFRA Case Studies: Field SFRA & LR Puzzle
Presented by Doble Engineering Company
Puzzle outline
• Transformer details – nameplate and history • The failure – LV bushing in pieces • Field test results – good, bad and inconsistent • Retest • Decision?
Transformer nameplate • 230/72 kV Federal Pioneer • 50/66.7/83.3 MVA Autotransformer • Built 1994 • Transformer suffered animal intrusion and tripped out after tertiary fault in late 1990’s • No testing performed • Unit successfully returned to service • Unit had also seen “a number” of short circuit faults
2006 Incident •
Unit tripped out in July with operation of:
– R and B phase elements – Gas accumulation/surge – Gas pressure relief •
Site inspection shows X3 gaskets compromised, oil leaking from flange; conservator isolated to limit spill
•
Inspection shows lower part of X3 bushing failed catastrophically
•
Porcelain shards throughout upper portion of core/coils
•
Arcing evident from lower part of X3 bushing to top of steel frame
Transformer nameplate
Investigation • ABB contacted regarding failure of 69kV 1200 A Type O+C • ABB suspect a known defect • Service advisories from August 1998 and April 1999 • ABB offer 3 replacement bushings
Investigation •
Transformer carefully cleaned and flushed with hot oil
•
X1 & X2 bushings removed, inspected, tested and re-installed
•
Routine electrical tests performed:
– Bushing C1 & C2 & power factor measurements – Winding power factor & capacitance – HV single phase excitation – DC winding resistance – Turns ratio – Leakage reactance – SFRA
Transformer
Investigation – Doble testing
• All as expected and all ‘Good’
Investigation – Doble tests on bushings
• All as expected and all ‘Good’
Investigation – Bushing C2 tests
• Some results are ‘Investigate’ on HV C2’
Investigation – IEx & Surge Arresters
• Surge arresters all as per nameplate
Investigation – LR results
Investigation – LR results
Investigation – SFRA results
Investigation – SFRA results
Investigation – SFRA results
Investigation – SFRA results
X3-X0
X1-X0 & X2-X0
Investigation – further results • Leakage reactance repeated with heavier shorting cables; results do not change much. • SFRA performed – all phases are consistent • Slight variation between phases not considered unusual; may relate to animal incident • SFRA and LR are inconsistent!!!
Time passes…
• Much thought
Time passes… more people needed
You can never have too many supervisors…
Repeat SFRA tests & LR tests
• January following year… • Repeat tests to review site procedures and confirm all test results • ALL Results confirmed • LR and SFRA still inconsistent
Variations on a theme – clutching at straws • Doble’s Lachman IEEE paper suggests perform LR tests from LV side • Wouldn’t necessarily explain the anomaly (X2 and X3 being different in LR) • LR Results confirmed from LV side as being unbalanced • LR Results reconfirmed unbalanced with three phase supply and clip on CT’s (energize H measure T)
Summary • Situation is difficult • LR indicates possible winding movement or anomaly • SFRA does not indicate significant winding movement • Other tests do not indicate a problem • What next? Internal inspection again? Energize and hope?
Action… • It was an LV bushing failure… • What could be anomalous about the tertiary? • Clutching at straws… • Everything else looks OK… • Let’s check the nameplate again…
Transformer nameplate – desperation…
Denoument…
Conclusion… • CT shorting block not shorted on tertiary • Affected high current LR • Marginal affect on low current SFRA • Everything is worth checking… • Transformer successfully returned to service