Training Guide
TM-1817 AVEVA Everything3D™ (1.1) Heating, Ventilation & Air Conditioning Modelling
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
2
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Revision Log Date
Revision
Description
Author
Reviewed
22/08/2013
0.1
Issued for Review
DW
01/09/2013
0.2
Reviewed
DW
SS
01/09/2013
1.0
Issued for Training AVEVA E3D™ (1.1)
DW
SS
Approved
KB
Updates Change highlighting will be employed for all revisions. Where new or changed information is presented section headings will be highlighted in Yellow.
Suggestion / Problems If you have a suggestion about this manual or the system to which it refers please report it to AVEVA Training & Product Support at
[email protected] This manual provides documentation relating to products to which you may not have access or which may not be licensed to you. For further information on which products are licensed to you please refer to your licence conditions. Visit our website at http://www.aveva.com
Disclaimer 1.1
AVEVA does not warrant that the use of the AVEVA software will be uninterrupted, error-free or free from viruses.
1.2
AVEVA shall not be liable for: loss of profits; loss of business; depletion of goodwill and/or similar losses; loss of anticipated savings; loss of goods; loss of contract; loss of use; loss or corruption of data or information; any special, indirect, consequential or pure economic loss, costs, damages, charges or expenses which may be suffered by the user, including any loss suffered by the user resulting from the inaccuracy or invalidity of any data created by the AVEVA software, irrespective of whether such losses are suffered directly or indirectly, or arise in contract, tort (including negligence) or otherwise.
1.3
AVEVA's total liability in contract, tort (including negligence), or otherwise, arising in connection with the performance of the AVEVA software shall be limited to 100% of the licence fees paid in the year in which the user's claim is brought.
1.4
Clauses 1.1 to 1.3 shall apply to the fullest extent permissible at law.
1.5
In the event of any conflict between the above clauses and the analogous clauses in the software licence under which the AVEVA software was purchased, the clauses in the software licence shall take precedence.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
3
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Copyright All intellectual property rights, including but not limited to, copyright in this manual and the associated software, (including source code, object code, and any data) belongs to or is validly licensed by AVEVA Solutions Limited or its subsidiaries. All rights are reserved to AVEVA Solutions Limited and its subsidiaries. The information contained in this document is commercially sensitive, and shall not be copied, reproduced, stored in a retrieval system, or transmitted without the prior written permission of AVEVA Solutions Limited. Where such permission is granted, it expressly requires that this Disclaimer and Copyright notice is prominently displayed at the beginning of every copy that is made. The manual and associated documentation may not be adapted, reproduced, or copied, in any material or electronic form, without the prior written permission of AVEVA Solutions Limited. The user may also not reverse engineer, decompile, copy, or adapt the associated software. Neither the whole, nor part of the product described in this publication may be incorporated into any third-party software, product, machine, or system without the prior written permission of AVEVA Solutions Limited, save as permitted by law. Any such unauthorised action is strictly prohibited, and may give rise to civil liabilities and criminal prosecution. The AVEVA products described in this guide are to be installed and operated strictly in accordance with the terms and conditions of the respective licence agreements, and in accordance with the relevant User Documentation. Unauthorised or unlicensed use of the product is strictly prohibited. Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved. The AVEVA Everything3D™ user interface is based on the Microsoft® Office Fluent™ user interface.
Trademarks AVEVA™, AVEVA Everything3D™, and AVEVA E3D™ are registered trademarks of AVEVA Group plc or its subsidiaries. AVEVA product names are trademarks or registered trademarks of AVEVA Solutions Limited or its subsidiaries. Unauthorised use of trademarks belonging to AVEVA Group plc or its subsidiaries is strictly forbidden. Fluent™ is a trademark of Microsoft Corporation and the Fluent user interface is licensed from Microsoft Corporation. The Microsoft Office User Interface is subject to protection under U.S. and international intellectual property laws and is used by AVEVA Solutions Limited under license from Microsoft. AVEVA Solutions Ltd, High Cross, Madingley Road, Cambridge, CB3 0HB, United Kingdom.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
4
www.aveva.com
CONTENTS 1
Introduction ............................................................................................................................7 1.1 1.2 1.3 1.4 1.5 1.6
2 3
Aim ..................................................................................................................................................... 7 Objectives.......................................................................................................................................... 7 Prerequisites ..................................................................................................................................... 7 Course Structure............................................................................................................................... 7 Using this guide ................................................................................................................................ 7 Training Setup................................................................................................................................... 8
HVAC Features .....................................................................................................................11 Overview of AVEVA E3D HVAC Designer...........................................................................13 3.1 HVAC Administrative Elements..................................................................................................... 13 3.1.1 HVAC Hierarchy ........................................................................................................................ 13
4
Creation and Routing of HVAC Components .....................................................................15 4.1 HVAC Components Representation in the Catalogue ................................................................ 15 4.1.1 HVAC Physical Shape ............................................................................................................... 15 4.1.2 HVAC Variables......................................................................................................................... 15 4.2 Setting HVAC Defaults ................................................................................................................... 16 4.2.1 Setting a Default Detailing Specification ................................................................................... 16 4.3 Choosing the HVAC Form Format ................................................................................................ 16 4.3.1 Categories ................................................................................................................................. 17 4.3.2 Available Types ......................................................................................................................... 18 4.3.3 Edit HVAC Attributes ................................................................................................................. 19 4.3.4 Customising HVAC Forms......................................................................................................... 22 4.4 Creating a HVAC System Element – A Worked Example ........................................................... 23 4.5 HVAC Branch Elements ................................................................................................................. 24 4.6 Creating a HVAC Branch – A Worked Example ........................................................................... 25
Exercise 1 – Create HVAC Main Branch Components .............................................................31 5
Modifying HVAC Branch ......................................................................................................33 5.1 5.2
Create Inline Plant Equipment – A Worked Example .................................................................. 33 Adding a Circular Section Silencer – A Worked Example .......................................................... 33
Exercise 2– Create HVAC Main Branch Components ..............................................................36 6
Tile & Grid Utility ..................................................................................................................37 6.1 6.2 6.3 6.4 6.5 6.6
Grid Setting Out Point (SOP) ......................................................................................................... 37 Layout Grid from SOP .................................................................................................................... 38 Apply Tiles in Grid .......................................................................................................................... 38 The Grid/Tile Utility – A Worked Example .................................................................................... 39 Creating Side Branch – A Worked Example ................................................................................ 43 Creating Secondary Side Branch – A Worked Example ............................................................. 46
Exercise 3a – Create HVAC Side Branch – SUPPLY_LEVEL02-001/02B ................................51 Exercise 3b – Create SOP using Tile and Grid Utility ..............................................................52 Exercise 3c – Create HVAC Side Branch – SUPPLY_LEVEL02-001/03 ...................................53 Exercise 3d – Create HVAC Network – SUPPLY_LEVEL02-001/01 .........................................54 Exercise 3e – Create HVAC Network – B01_LEVEL02_AC-RETURN ......................................55 7
HVAC Splitting......................................................................................................................57 7.1 The Split HVAC Form...................................................................................................................... 58 7.1.1 Branches to Split........................................................................................................................ 58 7.1.2 Split Markers.............................................................................................................................. 59 7.1.3 Flip Head Tube .......................................................................................................................... 61 7.2 Split HVAC – A Worked Example .................................................................................................. 62 7.3 Merge HVAC Branches – A Worked Example .............................................................................. 65
Exercise 4 – Split & Merge HVAC Branches .............................................................................67 © Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
5
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
8
Completing the Design ........................................................................................................69 8.1
Filling Ductwork Gaps – A Worked Example ............................................................................... 69
Exercise 5 – Completing the Design – Filling Ductwork Gaps ................................................72 8.2
Adding Stiffening Flanges – A Worked Example ........................................................................ 73
Exercise 6 - Completing the Design – Adding Stiffening Flanges ..........................................74 8.3 Automatic Item Numbering and Naming – A Worked Example ................................................. 74 8.4 Finishing Off Design Details.......................................................................................................... 75 8.4.1 Modifying Joint Types – A Worked Example............................................................................. 75
Exercise 7 - Completing the Design – Modifying Joint Types .................................................78 8.4.2
9
Inserting an Access Panel – A Worked Example ...................................................................... 78
Hole Management ................................................................................................................81 9.1 Introduction to Hole Management................................................................................................. 81 9.1.1 Hole Element Storage ............................................................................................................... 81 9.1.2 Request and Approval Workflow ............................................................................................... 82 9.1.3 Non-penetration Managed Holes............................................................................................... 84 9.1.4 Use of the Hole Management Application ................................................................................. 85 9.2 Penetration Holes – A Worked Example....................................................................................... 85 9.2.1 Creating an HVAC Penetration.................................................................................................. 86 9.2.2 Managing Holes – Requesting a Hole ....................................................................................... 88 9.3 Approving Holes ............................................................................................................................. 92 9.4 Rejecting a Hole .............................................................................................................................. 94 9.4.1 Rejecting on Initial Review ........................................................................................................ 94 9.4.2 Rejecting after Approval ............................................................................................................ 94 9.5 Making a Hole Redundant .............................................................................................................. 96
Exercise 8 – Create HVAC Penetrations ...................................................................................97 10
Checking and Outputting Design Data ............................................................................99
10.1 Querying Data Settings .............................................................................................................. 99 10.1.1 Item Details.............................................................................................................................. 100 10.2 Checking for Design Data Inconsistencies ............................................................................ 100 10.3 Data Check Functions .............................................................................................................. 101 10.4 Mass Properties......................................................................................................................... 103
11
HVAC Spooling ...............................................................................................................105
11.1 11.2 11.3 11.5
12
Generating HVAC Spools using HVAC Spool Manager – A Worked Example ................... 105 HVAC Spool Verification – A Worked Example...................................................................... 106 Modifying an HVAC Spool – A Worked Example ................................................................... 107 HVAC Sketches ......................................................................................................................... 109
HVAC Equipment Nozzles ..............................................................................................111
12.1
Creating HVAC Nozzles on Equipment Elements – A Worked Example ............................. 111
Exercise 9 – Creating HVAC Equipment Nozzles ...................................................................114 Appendix A – HVAC Branch Components for SUPPLY_LEVEL02-001/01 ............................116 Appendix B – Detailed Drawing for HVAC Main Branch B01_LEVEL02_AC-RETURN.........118 Appendix C – Detailed Drawing for HVAC Main Branch B01_LEVEL02_AC-SUPPLY .........120 Appendix D - Alternative Positioning Forms ..........................................................................121 Move Form ............................................................................................................................................. 121 Distance Tab .......................................................................................................................................... 121 Drag Move Form .................................................................................................................................... 127
Appendix E – Three-way Component......................................................................................129
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
6
www.aveva.com
CHAPTER 1 1
Introduction
Heating, Ventilation and Air Conditioning (HVAC) Designer is supplied as a module within the AVEVA Everything3D™ (AVEVA E3D™) Model module. The HVAC application allows the user to design and detail complex ducting networks within a full 3D environment, with the support of tools to produce a clash free design.
1.1
Aim
In completing the HVAC Modelling course, participants will learn the basic functions required to design, create and modify HVAC elements, and HVAC reporting.
1.2
Objectives
Through the completion of the training, the Trainee will have sufficient knowledge to complete the following tasks:
1.3
To have a clear understanding of the basic features of AVEVA E3D™ HVAC modelling.
To create and manipulate HVAC administrative elements.
To create a sequence of HVAC components.
To modify existing HVAC components.
To understand how to use the Grid/Tiling Utility.
To be able to make Data Consistency checks.
To discover how to Split HVAC elements and to generate HVAC spools.
To be able create HVAC sketches.
Prerequisites
Trainees should have attended the AVEVA E3D Foundations course and be familiar with Microsoft Windows.
1.4
Course Structure
Training will consist of oral and visual presentations, demonstrations and set exercises. Each workstation will have a training project, populated with model objects. This will be used by the trainees to practice their methods, and complete the set exercises.
1.5
Using this guide
Certain text styles are used to indicate special situations throughout this document. Menu pull downs and button click actions are indicated by bold dark turquoise text. Information the user has to enter will be in bold red text.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
7
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Where additional information is presented, or reference is made to other documentation the following annotation will be used:
Additional information
Refer to other documentation
System prompts will be bold, italicised, and presented in inverted commas i.e. 'Choose function'. Example files or inputs will be in the courier new font.
1.6
Training Setup
Login to AVEVA E3D Model module using the details provided by the Trainer, for example:
Project:
Training
Username:
A.HVACMAN
Password:
A
MDB:
A-HVAC
Click the Model button to load and display the default AVEVA E3D Model screen layout. Select Setup from the Training group located on the Tools tab to display the Training Setup form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
8
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Select the HVAC tab. Check the Setup Training Course checkbox and click the Apply button. Click the Close button.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
9
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
This page is intentionally left blank.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
10
www.aveva.com
CHAPTER 2 2
HVAC Features
AVEVA E3D HVAC has been designed by HVAC Engineers for HVAC Engineers. The HVAC application offers the following key benefits. The HVAC Designer application lets the user build up and detail complex ducting networks by selecting components from standard catalogues. By using standard default settings, a conceptual layout can be created and analysed rapidly, leaving the design details to a later post-approval stage. The application provides a facility to create rectangular, circular and oval cross-sectional items. Individual design components can be selected from over 100 parametric catalogue items covering all likely requirements. A range of auxiliary items such as stiffening frames, access panels, splitters plates etc., have been included and are accurately detailed in the design model. The catalogue also includes a range of inline plant items such as centrifugal and axial fans, air handling units, silencers, dampers etc. These items can be inserted into the design model in a single operation. User-definable detailing specifications, such as those for construction materials, ductwork gauge, flange dimensions etc., define precise manufacturing requirements. User-definable default settings ensure compliance with company standards and maintain a high level of design consistency throughout the project. Accurate geometric representation of all design items ensure reliable clash checking during the design process, leading to good space management and the early elimination of positional errors. Explicitly positioned design components are interconnected automatically with implied ductwork as the design of the ductwork sequence is built up. An auto filling facility is provided which can then calculate the optimum use of standard ducting straights to complete the material take-off for the entire network. Several design aids are incorporated, including a facility for creating horizontal grids which can be used to position ceiling tiles. This can greatly aid the layout of building services in an architectural environment. HVAC elements may be named in accordance with a predefined set of rules, so that their positions in the database hierarchy are always obvious without the user having to enter specific texts during the design process. The applications user interface can be tailored readily to suit the level of experience of any individual user. In particular, graphical illustrations of all catalogue items can be displayed if required to simplify component selection and dimensioning. The user can carry out multi-disciplinary clash checks at any stage of the design, thus avoiding spatial conflicts within the overall model which could be expensive to rectify at the construction stage. This is particularly important where different features of the design model are under the control of different designers. At any stage of the design process, the user can create reports listing specified data from the current database. The user can specify a standard report template, so lists of commonly required information can be derived very quickly. Alternatively, one-off report formats can be designed to suit special needs. The resultant output, can include data from any design discipline, sorted to suit project requirements, can be either displayed on the screen or sent to a file for storage and/or printing.
For further information, refer to TM-1869 AVEVA Everything3D™ HVAC Modelling Administration
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
11
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
This page is intentionally left blank.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
12
www.aveva.com
CHAPTER 3 3
Overview of AVEVA E3D HVAC Designer
This chapter aims to introduce the HVAC application in regards to access, the user interface and the HVAC viewing and manipulations controls. Although this guide is about the design of HVAC ducting networks, in practice ductwork will be routed with reference to predefined design items such as a frameworks, floors and ceilings. As such, it is important to understand how items are defined in AVEVA E3D as well as learning how to route sequences of HVAC components and ducting within them.
3.1
HVAC Administrative Elements
This section explains the Administrative context in which the HVAC elements are created.
Refer to TM-1869 AVEVA Everything3D™ HVAC Modelling Administration for further information on the creation and management of HVAC Administrative elements.
3.1.1
HVAC Hierarchy
All Design data in AVEVA E3D is stored in the form of a hierarchy. An AVEVA E3D Design database has: World (this can be represented by the symbolic name /*) Two principal administrative sublevels, Site and Zone. The names used to identify database levels below Zone depend on the specific engineering discipline for which the data is used. For HVAC design data the lower administrative levels (and their AVEVA E3D abbreviations) are: HVAC (HVAC) BRANCH (BRAN) SPOOLS (HSLIST) Each HVAC element can represent any portion of the overall ducting network. Each Branch (BRAN) within an HVAC element represents a single sequence of components running between two, and only two, points: Branch Head Branch Tail The Spools (HLIST) contains a collection of HVAC spool elements. The data which defines the physical design of the individual HVAC components is held below Branch level. The overall format is as follows:
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
13
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
HVAC Specific Elements
Common to All Disciplines
WORLD /*
SITE
ZONE
HVAC
Branch (BRAN)
Spools (HLIST)
HVAC Component
HVAC Spool
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
14
www.aveva.com
CHAPTER 4 4
Creation and Routing of HVAC Components
4.1
HVAC Components Representation in the Catalogue
Each HVAC component is represented in the project catalogue by the following types of data: Physical shape Parameters
4.1.1
HVAC Physical Shape
The physical shape of a component is defined by a set of geometric primitives, so that a component can be manipulated and linked to adjacent HVAC items. All principle points needed to define the component position orientation and connectivity are identified by uniquely numbered tags. These tags, which have both position and direction, are called P-points: Each P-point is identified by a number of the format P0, P1, P2 etc. P0 always represents the components origin position. The principle inlet and outlet points are also identified as P-Arrive (PA) and P-Leave (PL). P1 is the same as P-Arrive, and P2 is the same as P-Leave.
4.1.2
HVAC Variables
The setting of all variables needed to distinguish a component from others with the same geometry and Ppoint sets are defined by parameters. The values of these are defined to suit the specific design requirements. For example, a rectangular three way component (or branch connector) might be represented in the project catalogue as follows:
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
15
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The two curved duct sections from the component geometry set The four P-points from its point set P-point, P3, enables the user to control the direction of the branch connection arm when it is incorporated into the design The dimensions of the component and other constructional details are represented in the catalogue by parameters whose values are set to suit the design requirements.
4.2
Setting HVAC Defaults
The following defaults will need to be set for the users to complete the training exercises. A Default Detailing Specification The format of the HVAC form Customised HVAC forms
4.2.1
Setting a Default Detailing Specification
The constructional detail of components that the user selects from the HVAC catalogue, such as joint types and maximum straight lengths, are determined by the current default specification.
To set the default specification, select TUTORIAL from the Spec drop down menu within the Settings group on the HVAC tab. This specification gives access to a range of catalogue components that are suitable for use with this training course.
Note that when starting a new session, the specification will need to be set each time.
4.3
Choosing the HVAC Form Format
All the principle functions for creating, positioning, orientating and connecting HVAC elements are available from within a single form, the Heating, Ventilation, Air Conditioning (HVAC) form. The HVAC form has two display formats: The brief form, the default, uses drop-down lists to show the elements available for selection by the user when a design is being created. The full form, which uses scrollable lists to show the elements available for selection and also offers more complex positioning options. It is preferable to use the full form whilst learning about the HVAC Designer application. This guide uses examples of the full form. The HVAC form can be displayed by clicking the HVAC button from the Create group located on the HVAC tab. The HVAC form is displayed in Brief format. © Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
16
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 To use the full form, move the mouse over the form and press the right mouse button and select Use Full Form from the right click menu.
Brief HVAC Form
4.3.1
Full HVAC Form
Categories
HVAC tasks are initiated by first selecting an entry from the Categories drop-down list. These categories are standard types of HVAC provided by the application with the exception of User Defined Fittings or Assemblies.
A HVAC assembly is a collection of HVAC components that can be copied and placed into any part of the HVAC network.
Depending on the entry selected in the Categories drop-down list the Available Types drop-down list will present the user with a different set of options.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
17
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
4.3.2
Available Types
After selecting a Category of HVAC the user can choose a specific type of HVAC element from the Available Types list. When a selection is made from the Available Types drop-down list, a separate window will be displayed allowing the user to input specific criteria based on what type of HVAC component is being created. For example the user could be prompted to enter dimensions for a straight piece of HVAC for selecting Rectangular from the Category list followed by Straight from the Available Types list.
These are described in more detail in the following sections of this guide.
Alternatively, selecting Options… in the Available Types list menu displays a form containing all different types of available ductwork for the selected Category as shown below. Selecting any of these options will display the relevant window allowing user to input specific criteria as mentioned above.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
18
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
The user will not be able to select certain Available Types if the correct database hierarchy has not been configured beforehand. For example certain HVAC elements must reside below other elements in the database hierarchy. If a particular HVAC element cannot be created at the current position in the database hierarchy the user will receive an error message summarising the problem.
4.3.3
Edit HVAC Attributes
The lower part of the HVAC form contains tools allowing the user to modify the Orientation, Position and Connection type of HVAC components that already exists in the Model Explorer. These are discussed in detail as below.
4.3.3.1 Orientation The Orientation section of the form allows users to modify: Leave Direction- Sets Leave direction of the HVAC component. Leave ‘A’ Axis – Sets the rotation of the HVAC component relative to the Leave Direction. The user must first select the element to modify either from the Model Explorer or from the 3d view. Clicking the CE button will display the current orientation of the selected component.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
19
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
4.3.3.2 Position The Position section of the form allows users to position/reposition components using the selected option: The Position At method pull-down offers the following options:
Cursor – allows users to use the Cursor to pick the new position for the selected component. The user must set the view to a Plan view. Using this method the user is prompted to pick co-ordinates for East, North and Up. The East and North co-ordinates are picked first and together with one click. After clicking Cursor, the user is prompted to ‘enter a 3d position’. The user must click a position in the selected Plan view. The view will then change automatically, allowing the user to pick an Up coordinate to be used for the elevation of the selected component. ID- P-Point - allows users to use the ID P-Point to pick the new position for the selected component. The user is prompted to ‘identify design ppoint’ to re-position the origin of the component at a chosen p-point on another HVAC element in the 3D graphical view. ID Element – allows users to use the ID Element to pick the new position for the selected component. The user is prompted to ‘identify element’ to position the origin of the CE at the location of the origin of a selected element in the 3D graphical view. The user must pick a different HVAC element. Next – allows users to re-position the origin of the selected component in such a way that the P-leave is positioned at the P-arrive of the next HVAC component in the branch. Previous – allows users to re-position the origin of the selected component in such a way that the Parrive is positioned at the P-leave of the previous HVAC component in the branch.
The Through method pull-down allows users to re-position the selected component along the leave direction of the previous component using the following options: Cursor - allows users to Cursor pick the new position for the selected component by prompting to enter a 3-d position. The user must click a position in the 3D graphical view to re- position the along its arrive-leave axis to align to the picked position.
ID- P-Point - allows users to identify a design p-point. The user must click a p-point on another HVAC element in the 3D graphical view to re-position the component along the leave direction of the previous component to align to the selected p-point. ID Element – allows users to reposition the selected component along the leave direction of the previous component in alignment with another selected HVAC element from the 3d view. Next – allows users to re-position the origin of the selected component, along the leave direction of the previous component, to the P-arrive of the next piece of HVAC in the branch. The user can also move the selected HVAC component to a new position by inputting values into the Move by or Distance fields.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
20
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Inputting a value into the Move by field moves the selected component relative to its current position by given distance and direction. Inputting value into the Distance field moves the selected component along its P-leave axis away from the previous component, leaving the specified distance.
4.3.3.3 Plane Positioning The Plane Positioning section of the HVAC form allows users to position elements by using a reference plane (construction plane). The plane is defined in terms of its position (a point through which it passes) and its direction (the direction of a line normal to the plane). The Through method allows users to specify the method of identification of a point through which the plane is constructed and positioned.
4.3.3.4 Connect The Connect section of the form allows users to connect the HVAC branch Head/Tail or its components by selecting the options as discussed below. A HVAC Branch Component can be connected using the following options: To Previous – allows users to connect components which are axially asymmetrical i.e. p-leave is always in the opposite direction of p-arrive. Leave East/West/North/South/Up/Down – allows users to connect a two way piece which forces a change of direction i.e. bends, elbows with leave direction set to the selected option. P3 is East/West/North/South/Up/Down - allows users to connect HVAC components with side connections i.e. Threeways, Branch Connectors and Asymmetrical two-way components such as Offsets, Eccentric Tapers with P3 direction set the selected option. Next – allows users to connect the selected component to the next HVAC component in the branch. Branch Tail – allows users to connect and position the p-leave of selected component to the branch tail position.
A HVAC Branch (Head/Tail) can be connected using the following options:
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
21
Head/Tail of ID Branch – selecting this option, the user is prompted to ‘Identify Branch’ from 3D view. Once picked, the Head/Tail of the branch is positioned and connected to the Head/Tail of the picked branch.
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 ID Branch Connector – allows the user to connect the Head/Tail of the branch to a branch connector component from another HVAC branch. Upon selection, the user is prompted to ‘Identify Branch Connector’ to connect to. ID Threeway Piece – allows users to connect the Head/Tail of the branch to a Threeway/Tee component from another HVAC branch. Upon selection, the user is prompted to ‘Identify Threeway or Tee Item’ to connect to. ID Centrifugal Fan – allows users to connect the Head/Tail of the branch to a Centrifugal Fan. Upon selection, the user is prompted to ‘Identify Centrifugal Fan’ to connect to.
The p-arrive and p-leave points for a centrifugal fan are both on the rectangular flange face and the P3 is on the circular flange face, regardless of the flow direction through the fan. ID Air Handling Unit – allows users to connect the Head/Tail of the branch to an Air Handling Unit. Upon selection, the user is prompted to ‘Identify Air Handling Unit’ to connect to. ID Equipment Nozzle- – allows users to connect the Head/Tail of the branch to an equipment/subequipment Nozzle. Upon selection, the user is prompted to ‘Identify NOZZ’ to connect to. ID Ceiling Fitting – allows users to connect the Head/Tail of the branch to a HVAC Ceiling Fitting. Upon selection, the user is prompted to ‘Identify HVACFI’ to connect to. First/Last Member– allows users to connect and position the Head/Tail of the branch to a p-arrive of First Member or p-leave of the Last Member in the HVAC branch category. Explicit… – selecting this displays the Head/Tail Position form which allows users to enter explicit position coordinates for the selected HVAC branch. Clicking the Pick Position link label prompts the Positioning Control toolbar allowing user to graphically pick position from 3d view.
4.3.3.5 Copying HVAC Elements An existing HVAC component can be copied using the Copy ID button on the HVAC form. Clicking the Copy ID button prompts the user to ‘Identify Element’ to copy from 3d view. Depending upon the type of component selected, the appropriate form is displayed to facilitate the creation of new component.
4.3.4
Customising HVAC Forms
The appearance and behaviour of the forms for creating and modifying HVAC components can be customised to suit their preferences or the type of design work being carried out. Clicking the right-click mouse button on the HVAC form and selecting Style Options… displays the HVAC Form Style form as shown below.
Show Local Views - displays a small 3D graphical view showing the current component in its design context on the Create form. Local Views Shade - displays local views in colour shaded as opposed to wire line representation. © Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
22
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Use UK on Create Forms - provides component Create/Modify forms with Apply/Dismiss buttons instead of OK/Cancel buttons, allowing them to remain available for repeated use until dismissed explicitly. Show Pixmaps - automatically displays diagrams showing components geometries to help the user select items from the catalogue for the selected Category. Show Forms This displays the Create/Modify form automatically when the user adds a new component to the design so that default dimensions and/or orientation can be adjusted as required.
4.4
Creating a HVAC System Element – A Worked Example
Add ZONE BUILDING_B01 located under SITE-STRUCTURAL-AREA02 to the 3D View and change view to ISO1. Remove the Ladders, Handrails, roof and upper outer walls from the Drawlist as shown below.
A HVAC main branch is a starting point or branch head to which all other HVAC components can be added. Navigate to ZONE-HVAC-AREA02-B01 in Model Explorer. From the HVAC form, select HVAC/Branches from the Categories list and then select HVAC System Element from the Available Types list to display the Create HVAC form.
Enter B01_LEVEL02_AC-SUPPLY in the HVAC Name field. Click the OK button.
It is possible to assign the newly created HVAC to a preconfigured Primary System in AVEVA E3D. This allows users to create reports, drawings etc. based on the system element.
The HVAC element is created and can be seen in the Model Explorer.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
23
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
4.5
HVAC Branch Elements
There are two types of HVAC branch element. Main branch. Side branch. These differ only in the way they are added to the design: A main branch requires the user to position and orientate the branch head explicitly. A side branch takes its head position and orientation from a branch connection point P3 on an existing three way component. The first HVAC branch element will be a main branch element, the branch head. From the HVAC form, select HVAC/Branches from the Categories list and then select Main Branch Element from the Available Types list to display the HVAC Main Branch form. The HVAC Main Branch form is a dual purpose window, which allows the user to either Create a new HVAC Main Branch element (by default) or Modify an existing HVAC Main Branch element. Branch Name - allows users to input a unique name for the main branch. Specification – allows users to select a HVAC specification for the main branch from the drop-down list. Branch Head Shape – allows users to specify the crosssectional shape of the HVAC that will be connected to the branch head. This can be Rect(Rectangle), Circ(Circle) or Oval. Head Direction – specifies the direction that the HVAC will take from the Branch Head. Duct width AA – allows users to enter the Branch head width. AA stands for Arrive A dimension. Transpose width/depth – clicking this button exchanges the Duct width AA dimensions with Duct depth AB dimensions. Duct depth AB - allows users to enter the Branch head depth. AB stands for Arrive B dimension. Insulation Spec – allows users to select an Insulation specification for the HVAC branch. Insulation Thickness – allows users to select a thickness for the selected Insulation Spec. This should be set to 0 if no Insulation Spec is selected. Head Start – allows users to specify how the HVAC main branch head is positioned and connected. Depending upon the selected option from the drop down list, the user is prompted to complete an action in order to continue. This is discussed in further detail throughout the training course. Defaults – clicking this button resets all dimensions on the form to the system default values. Picture – clicking this button displays a detailed drawing of the HVAC Main Branch as shown below. The labels on the drawing depict a pictorial representation of various inputs fields discussed above.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
24
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
OK/Cancel – clicking the OK button creates a new HVAC Main branch element and clicking the cancel button discards the changes and closes the HVAC Main branch form.
If a Default Specification has already been selected, the specification field will automatically be loaded with the Default Specification set to it.
To use different specifications within a ductwork run, a new branch must be created at each point a different specification is used.
4.6
Creating a HVAC Branch – A Worked Example
Ensure the newly created HVAC element is the Current Element. From the HVAC form, select HVAC/Branches from the Categories list and then select Main Branch Element from the Available Types list to display the HVAC Main Branch form.
Enter SUPPLY_LEVEL02-001 in the Branch Name field. Set the Specification to TUTORIAL, Branch Head Shape to Circ, Head Direction to N and Duct Width AA to 450mm. From the Head Start drop-down list select Explicit… to display the Head Position form. Set the following co-ordinates for the Branch Head:
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
25
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 West - 301504.59mm North - 325022.25mm Up – 109200mm Click the OK button. Click the OK button on the HVAC Main Branch form. The first component required is a Circular 7 Segment Bend which will be placed at the Branch head. From the HVAC form, select Circular from the Categories list and then select Options… from the Available Types list to display the HVAC Circular Ductwork form.
Select 7 Segment Bend from the HVAC Circular Ductwork form to display the Create Circular 7 Segment Bend form.
Set the Inside Radius to 225mm and Leave Direction to D. Click the OK button to create the component. The newly created bend should now be displayed in the 3D view and Model Explorer, connected to the Head of the main branch.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
26
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The next component to be created is a Circular Radiused Bend. From the HVAC form, select Circular from the Categories list and then select Radiused Bend from the Available Types list to display the Radiused Bend form. Set the Leave Direction to E. Click the OK button to create the component.
On the HVAC form, enter 1150mm in the Distance textbox and click the Distance button to reposition the bend.
The next component to be created is a Round to Square transformation. From the HVAC form, select Transformations from the Categories list and then select Square to Round from the Available Types list to display the Square to Round form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
27
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Set the Duct width AA to 250mm, Duct width AB to 500mm, Flip Circ/Rect to Yes and Length to 400mm. Click the OK button to create the component.
The next component to be created is a 90 degree Square Bend. From the HVAC form, select Rectangular from the Categories list and then select Square Bend from the Available Types list to display the Square Bend form.
Set the Duct width AA to 500m and the Duct width AB to 250mm, by using the Transpose Width/Depth button. Set the Duct width LA to 500mm and Leave Direction to S. Click the OK button to create the component. Changing to Wireline view will show the created elbow and turning vane elements.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
28
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
The Model Explorer shows the two new elements. BEND 3 represents the bend ducting. SPLR 1 represents the set of air deflectors within the bend (created because a square bend requires turning vanes).
When creating an element after the bend, user must ensure that the deflectors are the current element. The two newly created elements will now be repositioned individually. Navigate to BEND 3 in the hierarchy. On the HVAC form, enter 300mm in the Distance textbox and click the Distance button to reposition the bend. Note that the Splitter SPLR1 has not moved.
Now navigate to SPLR 1 in the hierarchy and from the HVAC form, Select Connect HVAC Branch Component to Previous. The splitter has been moved to the correct position.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
29
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The next component to be created is a Rectangular Radiused Offset which allows designers to offset a HVAC branch to accommodate any design requirements or sometimes to avoid clashes with existing plant items. From the HVAC form, select Rectangular from the Categories list and then select Radiused Offset from the Available Types list to display the Rectangular Radiused Offset form. Using the Transpose Width/Depth button Set the Duct width AA to 250mm, and the Duct width AB to 500mm. Set the Duct width LA to 250mm, A offset to 200mm, Arrive Back Rad to 350mm, Leave Back Rad to 350mm and Offset Direction to D. Click the OK button to create the component.
The HVAC network should now look as shown below.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
30
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 1 – Create HVAC Main Branch Components 1
Following on from the worked example, complete the HVAC main branch with all appropriate components using the HVAC form. A list of all components with their respective details is as shown below.
Component
Attributes
Rectangular > Square Bend
Duct Width AA – 500mm Duct Width AB – 250mm Duct Width LA – 500mm Leave Direction – W Position:- Move south by 4000mm The Air Deflectors must also be repositioned.
Rectangular > Square Threeway (Standard Configuration)
Change Direction – N
Rectangular > Radiused Bend
Leave Direction – W
Position:- Move West by 4750mm
Position – Move North by 3600mm Rectangular > Radiused Bend
Duct Width AA – 250mm Duct Width AB – 500mm Inside Radius – 125mm Leave Direction – D Position – Move West by 4100mm
Rectangular > Mesh End
Position – No Change.
From the HVAC form Select Connect HVAC Branch Tail to Last Member to complete the HVAC main branch route. The HVAC network should look as shown below.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
31
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
32
www.aveva.com
CHAPTER 5 5
Modifying HVAC Branch
It is usual for the user to build up the HVAC design by adding components sequentially, starting at the branch head, and positioning and orientating each component as they proceed. The user can insert a component into an existing sequence by navigating to the item immediately before the required location and then creating the new component. This allows users to insert new Inline Plant Equipment or Branch connecters along an existing branch.
5.1
Create Inline Plant Equipment – A Worked Example
The Inline Plant Equipment to be created is a Fire Damper which will be placed at the entry point of HVAC into the building. Add FRMW /B01_LEVEL_03_FLOORS, located under STRU /BUILDING_01_LEVEL_03 under ZONE /BUILDING_B01 in the Model Explorer to 3D view. This will add the roof to the 3D view, which will be used to position the Fire Damper. Now, navigate to the first bend in the existing HVAC which is located just above the roof of the building. From the HVAC form, select Inline Plant Equipment from the Categories list and then select CIRCULARFire Damper from the Available Types list to display the Circular Fire Damper form. Set the FD Name(Ref) to FD1 and Curtain Direction to W. Click the OK button to create the component. On the HVAC form, select Position > Through ID Element from the option list. Now pick the roof of the building from the 3D view to reposition the Fire Damper
.
5.2
Adding a Circular Section Silencer – A Worked Example
To include a circular section silencer in the rectangular, a transformation piece either side of the silencer is required. Remove the building roof from the 3D view. Navigate to splitter SPLR 2 in the Model Explorer. From the HVAC form, select Transformations from the Categories list and then select Square to Round from the Available Types list to display the Square to Round form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
33
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Set the Duct Diameter to 450mm. Click the OK button to create the component. On the HVAC form, move the newly created component by 425mm.
From the HVAC form, select Inline Plant Equipment from the Categories list and then select Circular Silencer from the Available Types list to display the Circular Silencer form. Set the Name to SIL1. Leave all other values as the default values. Click the OK button to create the component.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
34
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 A second transformation piece will now be added to revert back to the rectangular ducting. However, instead of specifying this from first principles, a copy will be created of the first transformation piece and reversed to achieve the desired round to square result. Ensure the silencer SIL1 is the current element. From the HVAC form, select the Copy ID button. The user is then prompted to ‘Identify Element’. Select the previously created square to round transformation from the 3D view. The Square to Round Transformation form will now be displayed. Set the Flip Circ / Rectangle option to Yes. Click the Apply button to create the component.
The HVAC system should look as shown below.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
35
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 2– Create HVAC Main Branch Components 1
Fire Dampers are required at each point the HVAC main branch penetrates through the building walls. Using the previous worked example, navigate to the appropriate component in the hierarchy and create suitable fire dampers for the given HVAC shape.
The complete result should look as follows:
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
36
www.aveva.com
CHAPTER 6 6
Tile & Grid Utility
In the previous chapter a sequence of components was created to form the main branch of the HVAC ductwork. This chapter will demonstrate how to extend the model, by adding side branches, and show users how to position components using a working grid. The Tiles/Grid utility is used to create a reference grid to aid in the construction of the design, a reference grid based on a horizontal layout is used as an aid to position inlet/outlet HVAC grilles which are represented as ceiling tiles. There are three stages to tiling: 1. Specify a setting out point (SOP) to represent the datum from which grid line positions are to be calculated. 2. Create grid lines at specified intervals, referenced from the SOP in a horizontal plane. 3. Add tiles at specified positions in the plane of the grid.
6.1
Grid Setting Out Point (SOP)
The SOP and Datum are the points from which all reference grid lines are calculated. The HVAC application incorporates design aids which help the user to position ceiling tiles representing inlet/outlet grilles etc. based on a horizontal grid layout.
The setting out point can only be created using the 2D cursor in the orthogonal view (plan view), change the view to the plan view, from the right click menu click Plan > North, South, East or West.
The HVAC Grid Setting Out Point form can be displayed by selecting Setting Out Point from the Tiles/Grid Layout drop down menu within the Tools group on the HVAC tab.
The S.O.P Name field allows users to input the name of the setting out point, and the S O.P Height field allows users to input the elevation of the datum point.
On clicking the OK button, the user is prompted to ‘Use the 2D cursor to position a datum’ in the 3D graphical view. Once positioned, the datum or setting out point is created and can be seen in the 3D graphical view and in the Model Explorer as a DISH element.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
37
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
6.2
Layout Grid from SOP Once the datum has been created, the layout of the grid must be defined through the current S.O.P datum, with the grid lines spaced out from the S.O.P in both directions. The Grid from S.O.P form can be displayed by selecting Grid from S.O.P from the Tiles/Grid Layout drop down menu within the Tools group on the HVAC tab
The X Spacings field allows users to input the width dimension of the grid spacing separation whereas the Y Spacings field allows users to input the length dimension of the grid spacing separation.
On clicking the OK button, the user is prompted to Position the lower left grid extent in the 3D graphical view. Once picked, the user is prompted to then Position the upper right grid extent in the 3D graphical view. Once complete, the grid with the specified spacings will be displayed in 3D view.
6.3
If the SOP is not the current element a prompt will be displayed Identify the Grid S.O.P.
Apply Tiles in Grid
Once the grid layout has been created, the dimensions of the tiles to be placed in the layout grid must be defined using the HVAC Tiles form. The HVAC Tiles form can be displayed by selecting Apply Tiles in Grid from the Tiles/Grid Layout drop down menu within the Tools group on the HVAC tab The X of Tile and Y of Tile field allows users to input the dimension of the tile in their respective orientation.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
38
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
6.4
The Grid/Tile Utility – A Worked Example
A new S.O.P and subsequently a grid will be created in the room marked in red below using the Grid/Tile utility. This will be used later in the training to aid in creating and positioning side branches and their components. In the 3D view, remove ZONE BUILDING_B01, add STRU BUILDING_01_LEVEL_02, and remove FRMW B01_LEVEL_02_CEILINGS. The view should look as shown below.
Navigate to the ZONE-HVAC-AREA02-B01 in the Model Explorer. Select Setting Out Point from the Tiles/Grid Layout drop down menu within the Tools group on the HVAC tab to display the HVAC Grid Setting Out Point form. Set the S.O.P. Name to SOP1 and the S.O.P. Height to 106595mm. Now set the view direction of the 3D view in a Plan view by right clicking in the 3D view and selecting Plan > North.
Click the OK button. A prompt is displayed stating ‘Use the 2D cursor to Position a Datum’. Rather than trying to pick this point precisely, a random point in the ceiling plane will initially be selected. This point will then be moved to the exact position required for the S.O.P. Pick a point in the 3D view. The S.O.P should now be positioned and displayed in the 3D view.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
39
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 To move this point to a precise location select Position Explicitly button from the Common group located on both the Home and HVAC tab to display the Explicit Position form.
Set the position co-ordinates to: West 310250mm North 320400mm Up 106595mm. Click the Apply button and then click the Cancel button. The S.O.P is displayed in the 3D graphical view as a small sphere, and is represented by a DISH element in the Model hierarchy.
Next a grid will be defined in the plane of the ceiling (a horizontal reference grid) through the S.O.P datum, with the grid lines spaced out from the S.O.P in both directions. In the Model Explorer under SITE-STRUCTURAL-AREA02 remove FRMW B01_LEVEL_02_BEAMS. Navigate back to the previously created SOP in the Model Explorer. Select Grid from S.O.P from the Tiles/Grid Layout drop down menu within the Tools group on the HVAC tab to display the HVAC Grid form.
Set both fields on the form to 600mm. Click the OK button. Ensure the 3D view still in a Plan > North view direction.
A prompt is displayed as ‘Identify Grid S.O.P.’, select the Setting Out Point SOP1 from within the 3D view. A second prompt is displayed stating ‘Position the lower left grid extent’. Pick the intersection of the West wall and the curved South wall. A third prompt is displayed stating ‘Position the Upper Right Grid Extent’. Pick the intersection of the walls in the diagonally opposite corner as shown in the detail below.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
40
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
If the SOP is not the current element a prompt will be displayed Identify the Grid S.O.P after clicking the OK button on the HVAC Grid form. Identify the SOP in the graphical view before continuing.
The positioning control toolbar is not active during the Grid Extent selection process. As such the user must make a visual approximation of the intersection point. As the tile grid is set out from the centre of the room the accuracy of the grid is maintained.
The grid should now be created and displayed in the 3D view and should look as shown below.
To complete this worked example, two gird tiles will be created in the ceiling grid where the HVAC grilles are to be installed. © Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
41
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Select Apply Tiles in Grid from the Tiles/Grid Layout drop down menu within the Tools group on the HVAC tab to display the HVAC Tiles form.
Set both fields on the form to 600mm. Click the OK button.
A prompt is displayed ‘Position the tile centre point (2D cursor)’. Pick the grid squares shown in the diagram below (the picked points snap to the nearest half tile) then press the Esc key on the key board to complete the process.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
42
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
6.5
Creating Side Branch – A Worked Example
A side branch which runs from a start point on the main branch and passes through the tile positions will be created. Two further side branches will be added, each running from a point on the first side branch to the tile positions. First a suitable branch connector must be inserted into the main branch so there is a point to which the side branch can be connected. Navigate to the Threeway component in the Model Explorer. From the HVAC form, select Branch Connectors from the Categories list and then select Flat Oval ‘A’ Boot from the Available Types list to display the Oval ‘A’ Boot Brco form. Set the Boot Depth to 100mm, MAIN width LA to 500mm and Boot Direction to W. Click the OK button to create the component. On the HVAC form, position the newly created component through the S.O.P created previously, using Position > Through > ID Element.
From the HVAC form, select HVAC / Branches from the Categories list and then select Side Branch (off main) from the Available Types list to display the HVAC Side Branch form.
Set the Branch Name to SUPPLY_LEVEL02-001/02. Click the OK button. A prompt is displayed ‘Identify Branch Connector’. Pick the newly created branch connector from 3D view. This will automatically set the position and connection reference for the new branch. New components can now be created in a normal manner on this branch.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
43
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The first component to be created in the side branch is a Flat Oval straight. Ensure the newly created Branch is the current element. From the HVAC form, select FlatOval from the Categories list and then select Straight from the Available Types list to display the Oval Straight form.
Set the Length to 1000mm and Width Direction to S. Click the OK button.
A circular boot connector now needs to be created which will allow a duct to be routed to the tile position to the North of the branch. From the HVAC form, select Branch Connectors from the Categories list and then select Circular Boot from the Available Types list to display the Boot Brconnector form. Set Boot Direction to N. Click the OK button. Position the Boot Through ID Element. A prompt is displayed ‘Identify element’, Pick the tile position to the North of the branch and the Boot will be positioned perpendicular to it.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
44
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 A Flat Oval taper can now be placed after the Circular Boot. On the HVAC form select FlatOval from the Categories list and then select Taper from the Available Types list to display the FlatOval Taper form. Set the Duct Width LA to 300mm, the Length to 400mm and the A Offset Direction to W Click the OK button.
Next position the second Circular Boot which will connect to the tile positioned at the South of the branch. From the HVAC form, select Branch Connectors from the Categories list and then select Circular Boot from the Available Types list to display the Boot Brconnector form. Set Boot Direction to S. Click the OK button. Position the Boot Through ID Element A prompt is displayed ‘Identify element’, Pick the tile positioned to the South of the branch and the Boot will be positioned perpendicular to it.
A Cap End is required at the end of the branch. From the HVAC form, select FlatOval from the Categories list and then select Cap End from the Available Types list to display the FlatOval Cap End form
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
45
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Click the OK button.
To complete the branch, select the first element in the branch (1000 FlatOval straight) From the HVAC form, click the Modify CE button to display the FlatOval Straight form. Click the Fit button then click the Apply button to apply the changes. Click the Cancel button to close the form.
Finally, within the Connect Section of the HVAC form set HVAC Branch Tail to Last Member.
6.6
Creating Secondary Side Branch – A Worked Example
As mentioned in the previous worked example, a secondary side branch will now be created from the first circular boot connector. From the HVAC form, select HVAC / Branches from the Categories list and then select Side Branch (off main) from the Available Types list to display the HVAC Side Branch form. Set the Branch Name to SUPPLY_LEVEL02-001/02A. Set the Connect Head to option to Branch Connector, and click the OK button. The user is prompted to ‘Identify Branch Connector’. Pick the first of the newly created branch connectors from the 3D view. The new branch element has now been created. Ensure the newly created branch created is the current element. From the HVAC form, select Circular from the Categories list and then select Straight from the Available Types list to display the Circular Straight form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
46
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Set the Length to 925mm. To check the types of leave joint available, click the Choose button next to the Leave Joint field.
From the resulting Choose Joint form, select Male Socket & Spigot Joint. Click the OK button. Click the OK button on the Circular Straight form.
A Circular Damper will now be created 100mm from the leave of the newly created straight. Ensure the STRT is the current element. From the HVAC form, select Circular from the Categories list and then select Internal Damper from the Available Types list to display the Internal Damper form. Leave all values as the default values, and click the OK button.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
47
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Ensure the damper is the current element. From the HVAC form, select Circular from the Categories list and then select Flexible Bend from the Available Types list to display the Circular Flexible Bend form. Set the Leave Direction to D. Click the OK button.
From the HVAC form, select Transformations from the Categories list and then select Spigot Box from the Available Types list to display the Spigot Box form.
Set the following values: Duct Width LA: 300mm Duct Depth LB: 300mm Rect Box Height: 30mm Circ Extension: 50mm Male Collar: 30mm Click the OK button.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
48
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 From the HVAC form, select Inline Plant Equipment from the Categories list and then select Rectangular Grille in Line from the Available Types list to display the In line Grille form. Set the following values: Unit Name: GRIL1 End Width: 400mm End Depth: 400mm Grille Length: 50mm ‘A’ Extension: 0mm Width Direction: S. Click the OK button.
The newly created grille will now be positioned through the tile.
Using the HVAC form, set the Position > Through to ID Element and select the Tile from the 3D view.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
49
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
At this stage the PL (P-Leave) of the spigot box and the PA (P-Arrive) of the grille have become misaligned, as such a broken line is displayed between them rather than a length of implied ducting.
Highlight the spigot box in the 3D View and using the HVAC form select Position > Through Next which is the grille in this case.
Next, the flexible bend will be modified so that it fits correctly between the internal damper (at its P-Arrive) and the spigot box (at its P-Leave). Select the Flexible Bend in the 3D View and from the HVAC form click Modify CE to display the Circular Flexible Bend form.
Click the Fit button, the Leave Extension will be recalculated and adjusted on the form. Click the Apply button and then click the Cancel button.
Finally, from the HVAC form select Connect > HVAC Branch Tail to Last Member to complete the HVAC side branch route.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
50
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 3a – Create HVAC Side Branch – SUPPLY_LEVEL02-001/02B 1
Using the previous worked example as a reference, create a new secondary side branch which is connected to the remaining boot connector on the side branch and will outlet at the remaining tile.
Name the branch - SUPPLY_LEVEL02-001/02B
Copy ID functionality may be used to copy components to the new branch. 2. Navigate to STRU /SOP1/owner in the hierarchy. As this SOP and the subsequent grid are no longer required, delete the element from the hierarchy (STRU SOP1/owner). 3. Create a Flat Oval Fire Damper /FD5 at a position where the HVAC side branch penetrates through the wall.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
51
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 3b – Create SOP using Tile and Grid Utility 1. Create and insert a new Branch Connector in the main branch 850mm from the previously created BRCO. The component should be an exact copy of the original BRCO and must have the Boot Direction set to E. 2. Create a new Grid setting Out Point named /SOP2 and setting out point height set to 106595mm. Create the Setting Out Point beneath a new STRU, owned by /ZONE-HVAC-AREA02-B01. Position the newly created SOP roughly parallel to the newly created BRCO and then set the explicit position to West 303000mm North 321247.25mm Up 106595mm 3. Now create a 600mm x 600mm grid based on the SOP. The lower left grid extent and upper right rid extent for the grid are as shown below.
4. Create two 600mm x 600mm tiles in the newly created grid using the Tile/Grid utility as shown below.
The Tiles will be identified as BOX1 & BOX2 within the Model Explorer Hierarchy and can be renamed to TILE if required.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
52
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 3c – Create HVAC Side Branch – SUPPLY_LEVEL02-001/03 1. Using the previous worked examples in the chapter, create a new side branch named SUPPLY_LEVEL02-001/03 which is connected to the BRCO created in the previous exercise. The branch will contain a straight, two BRCOs (100mm diameter boot branches) which must be positioned through the tiles and cap at the end of the branch. Refer to the Appendix C for detailed drawings.
2. Create two secondary side branches which will be identical in dimensions and will be connected from the BRCOs created on the side branch /SUPPLY_LEVEL02-001/03. The flexible bend, damper, plenum and grill are to be the same as created in the previous Worked Example.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
53
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 3d – Create HVAC Network – SUPPLY_LEVEL02-001/01 1. Navigate to ZONE-CWAY-AREA02-B01 under SITE-CABLE-AREA02 and add /CWAY-POWERBUILDING-B01_B1 to 3D view. 2. Create a new HVAC side branch, beneath HVAC B01_LEVEL02_AC-SUPPLY, with its head connected to the open end of the three way item on branch SUPPLY_LEVEL02-001. Name the new branch SUPPLY_LEVEL02-001/01. The branch is to be created in such a way that it avoids the cableways in Building B01 as shown below. 3. Refer to the Appendix A for HVAC component sketches showing suggested dimensions for the Bend and Offset components. 4. Complete the Branch with a Rectangular Mesh End. Set the height of the Mesh End to be the same as the grills created in the previous exercise.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
54
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 3e – Create HVAC Network – B01_LEVEL02_AC-RETURN 1. Create a new HVAC main branch B01_LEVEL02_AC-RETURN and subsequent side branches as shown below. Refer to the Appendix B for detailed drawings. Duct diameter – 450mm All bends to be 7 Segment Bends unless stated otherwise
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
55
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
56
www.aveva.com
CHAPTER 7 7
HVAC Splitting
HVAC systems are created as a series of branches and components throughout the route. Once the HVAC route is well defined and stable, the HVAC Splitting utility can be used to split the HVAC system. These splits may occur at logical breaks based on topographical features or at specific points along the HVAC route. The suggested workflow for HVAC is to define the whole route using the principle elements only (i.e. bends, dampers reducers etc.), leaving the spaces between these fittings as ‘implied’ duct. The splitting can then be applied while the implied duct is still present:
Auto-filling gaps can be done after splitting
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
57
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
7.1
The Split HVAC Form
To display the Split HVAC form, click the Split button from the Tools group located on the HVAC tab The Split HVAC form consists of three sections: Branches to Split Details Split Branches and Move elements into
7.1.1
Branches to Split This section of the form allows the user to define a list of HVAC branches to be split. It consists of a list pane with a pop-up menu of options, an options list, and an Add button. The options list has the following options that can be selected in conjunction with the Add button:
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
CE – Adds to the list the HVAC branch element if the CE is an HVAC branch, or adds the owning branch if the CE is an HVAC branch member, or adds all the HVAC branches if the CE is an HVAC main element.
Collection – Adds all the HVAC branches from the active list.
Graphical Pick – Prompts the user to pick an HVAC element using graphical pick and adds the owner branch to the list.
Window Selection – Allows the user to add HVAC branches from the elements selected using Window selection in graphical window. Only HVAC branches in the selection are added to the list. The window selection needs to be performed prior to clicking the Add button
58
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
7.1.2
Split Markers
This section allows the user to define and modify a plane at which to split the branches, and create and position split markers. Plane definition The Plane Size text box is used to set/modify the visible size of the plane. The Fill toggle is used to set/modify the plane filling.
Define Plane using The drop-down list has the following options in which a plane can be created: DB Planar Element – AVEVA E3D Database element which can be translated into a plane, e.g., panel. Element – AVEVA E3D Database element. Ppoints – Standard ppoint. Pline – Standard pline. Reference Grid – Grid Section. Explicitly… - Allows the user to create a plane explicitly using the Define Plane form. Modify Plane The drop-down list has the following two options to modify a defined plane: Definition… – The system prompts the user to pick the plane to be modified. When a plane is picked the system displays the Modify Plane form for the user to the plane definition. Position – Prompts the user to pick the plane to be modified, and the new position of the plane. Insert uses two radio button options for insertion: Marker – to insert a marker at the split. Assembly – to insert an HVAC assembly at the split. The selection of the radio button will change the layout of the form to suit.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
59
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 With the Marker radio button selected the Create Marker link label becomes available. This creates split markers at the intersection points between the defined plane and the implied tubes of the HVAC branch elements present in the Branches to Split list.
If required the Marker can now be selected and the Reposition Marker pull down can be used. The list has the following three options: Explicitly At…
Relatively By…
Each option displays a standard Position form to reposition the created split markers. With the Assembly radio button selected the Select Assembly link label becomes available. Clicking this link label will display the Select HVAC Assembly form.
The user can select the desired assembly to be inserted at the split from the hierarchy and then click Select as the Splitting Assembly button. This populates the Split HVAC form with the name of selected assembly.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
60
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
This section allows the user to specify the hierarchy into which the split elements will be placed. It consists of the following radio button options: Current HVAC – Creates new branch for each split marker under the HVAC system where the branch to be split is located. New HVAC – Creates a new HVAC system and a branch under it for each split marker. Existing HVAC – Creates a new branch under the HVAC system specified in the adjacent text. The existing HVAC system can be specified by typing the name in the text box, or by navigating to the HVAC system and typing CE (case insensitive) in the text box. Click the Apply button to action the splitting.
7.1.3
Flip Head Tube
Occasionally the splitting process may require some remedial action. The orientation of the implied tube between the split position and the subsequent fitting is sometimes incorrect. This can be corrected by clicking the Flip Head Tube link label from the Split HVAC form. The user is then prompted to ‘Pick branch tubes to flip’ select the elements that require action and press the Escape key. This will orientate the implied tube correctly.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
61
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
7.2
Split HVAC – A Worked Example
In this worked example, HVAC branch /RETURN_LEVEL02-001, created in Exercise 3e, will be split using the HVAC Split form just after the threeway piece as shown below.
Select Split from the Tools group located on the HVAC tab to display the Split HVAC form. Select the Branch RETURN_LEVEL02-001 from the 3D view or from the Model Explorer. Ensure the pick option is set to CE and click the Add button. The branch is added to the Branches to Split list.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
62
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Set the Plane Size to 1500mm. Toggle the Fill to On. The Plane will first be positioned at the arrive p-point of the square bend and then moved along the north direction until it is in line with the side branch. Select the Define Plane using to Element.
The user is prompted to ‘Pick an Element to convert into a plane’. Select the TEE piece from the ductwork as shown.
Once selected, the plane will be automatically positioned and orientated as shown.
To reposition the Plane, select Modify Plane Definition… from the Split HVAC form to display the Modify Plane form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
63
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Set the West position co-ordinate to 305780mm, 1000mm west from its original position. The plane will now move to the updated position. Click the OK button.
Click the Create Marker link label. An attachment is created in the HVAC branch at this point and can also be seen in the model hierarchy.
.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
64
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Ensure the Current HVAC radio button is selected and then click the Apply button on the Split HVAC form. The HVAC has now been split at the marker position and the downstream components have been moved to a new branch called RETURN_LEVEL02-001/Split(1) as shown below.
7.3
Merge HVAC Branches – A Worked Example
HVAC branches that have been split can be merged into one using the Merge Branches utility. In this worked example, the HVAC branch split in the previous example will be merged back into one. Select Merge from the Tools group on the HVAC tab. A prompt is displayed ‘First pick a connected branch to merge’. Select the branch RETURN_LEVEL02-001/Split(1) from within the 3D view.
A second prompt is displayed ‘Secondly pick the branch to merge to’. Select the branch RETURN_LEVEL02-001 from within the 3D view.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
65
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
An alert message is displayed to confirm the action. Click Yes.
The first picked branch will now become part of the second picked branch. The first branch picked will be removed from the Model Explorer; the component(s) from this branch are now part of the second picked branch.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
66
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 4 – Split & Merge HVAC Branches 1.
Using the worked example, split the HVAC branch at a midway point between the last two bends in the branch RETURN_LEVEL02-001 as shown below. The elements in the branch are to be moved to the current HVAC.
2
Using the Merge Branches utility, merge the branches split in this exercise back into one.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
67
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
68
www.aveva.com
CHAPTER 8 8
Completing the Design
In this chapter some facilities for enhancing the basic HVAC design model are examined. The main features described are: Replacement of implied ducting by catalogue straights. Addition of stiffening flanges to ductwork items. Item numbering of HVAC components. This will be demonstrated using the duct work that was created in the previous worked examples, SUPPLY_LEVEL02-001.
8.1
Filling Ductwork Gaps – A Worked Example
During the creation of the main branch, components were specified with specific functions, such as bends, side connection points, silencers and dampers. Most of the gaps between these components were left undefined and were filled by implied ducting to complete the representation shown in the 3D view. To enable the design to be prefabricated, it is necessary to specify the fixed lengths of ductwork (ductwork straights) required between these components. This will also enable a full material take-off to be generated. The HVAC application is able to calculate the optimum combination of standard and non-standard straights needed to fill each gap and then create the corresponding components in the design database automatically. Clear the 3D view. Navigate to the main branch SUPPLY_LEVEL02-001 and add it to the 3D view. To confirm the presence of gaps in the branch, Select Show Gaps from the Autofill dropdown menu in the Tools group located on the HVAC tab to display the Highlight Implied Ductwork (HVAC) form and click the Apply button.
For each gap in the named branch, the scrollable list area of the form shows the: Location (the preceding component) Length Calculated combination of straights to fill the gap. All corresponding lengths of implied ducting are highlighted simultaneously in the graphical view.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
69
The CE button on the form allows multiple branches to be checked.
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
If the user is presented with warning stating ‘This Gap will not be filled’, then the arrangement will need to be modified to allow for this. Click the Cancel button to close the Highlight Implied Ductwork (HVAC) form. Select Fill Gaps from the Autofill dropdown menu in the Tools group located on the HVAC tab to display the Autofill with Straights (HVAC) form. Click the Apply button on the form. A list of identified gaps is displayed and the specified straight lengths are created automatically to replace the implied ducting. The Model Explorer shows the new elements.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
70
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
71
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 5 – Completing the Design – Filling Ductwork Gaps 1.
Using the worked example, show and subsequently fill all gaps with straights for all HVAC branches created during this training.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
72
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
8.2
Adding Stiffening Flanges – A Worked Example
AVEVA E3D provides a utility for calculating the optimum number and positions of stiffening flanges needed to support ductwork items. The configuration of the flanges is tailored to suit the component geometry in each case. The user can then create and position such flanges automatically.
In the branch membership hierarchy, they are treated as sub-components of the straight.
Navigate to the straight shown below (STRT3) from the Circular main branch RETURN_LEVEL02-001 and make it the current element.
From the HVAC form, select Circular from the Categories list and then select Stiffening from the Available Types list to display the Stiffening form. Based on the selected specification and the dimensions of the selected component, the number of required stiffeners are automatically calculated and displayed as shown. To create the stiffening flange, click the OK the Spec Requirement button. The flanges are created and positioned automatically.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
73
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 6 - Completing the Design – Adding Stiffening Flanges 1.
8.3
Using the worked example, check and add stiffening flanges to all HVAC branches created during this training.
Automatic Item Numbering and Naming – A Worked Example
The item numbering facility automatically allocates sequential item numbers to all HVAC components and gives each item a name of the format: < number> where /PREFIX is a user definable string and number is the sequential number. Sub-components, air deflectors, stiffening flanges, etc. are numbered as decimalised subsets of their owning components. Inline equipment items, silencers, fire dampers, etc. which are usually named, remain unchanged. To auto number all HVAC items in the current design model, navigate to the owning HVAC Branch, SUPPLY_LEVEL02-001/02. Care should be taken if the selected owning element is the system element as opposed to the branch element because the branch order below may not be in sequence. This is important if the itemisation is to be consistent with the branch numbering, i.e., B1, B2, B3 etc.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
74
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Select Itemise from the Tools group located in the HVAC tab to display the HVAC Itemising form. Set the Naming Prefix to SUPP_LEVEL02001/02/ITEM, leave the Start Number set to 1, and click the Apply button.
The HVAC Command Output form is displayed, listing all HVAC items and their allocated numbers. Comparing the entries in this itemising list with those in the Model Explorer, it can be seen that each item (with the exception of any inline equipment components) has been named in the Model Explorer using the specified prefix /SUPP_LEVEL02-001/02/ITEM suffixed by the item number. i.e., the straights in the main branch, and their stiffening flange subcomponents, appear as follows:
8.4
Finishing Off Design Details
The design details for the ductwork straights can now be completed. This will entail: Modifying joint types to suit the final design. Inserting an access panel into the side of a length of ducting.
8.4.1
Modifying Joint Types – A Worked Example
When the lengths of implied ducting leading to the four fire dampers were replaced with straight components, the connecting joints will have been assumed to remain as default flanged joints. In fact, the fire dampers require raw edge joints, such that the ducting simply fits over the damper inlet and outlet. The inlet joint for the damper is the leave joint for the straight that precedes it. To modify this joint, navigate to the preceding straight element STRT 4 of BRAN SUPPLY_LEVEL02-001. From the HVAC form, click the Modify CE button to display the Modify Rectangular Straight form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
75
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Click the Leave Joint Choose button to display the Choose Joint (HVAC) form.
Select Raw Edge Joint, slip over 40mm (RE40) from the Choose Joint list and click the OK button. Click the Apply button and then click the Cancel button on the Rectangular Straight form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
76
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
To modify the outlet joint between the damper and the following straight (the arrive joint of the straight), navigate to the straight. From the HVAC form, click the Modify CE button to display the Modify Rectangular Straight form. Click the Arrive Joint Prev button. The Arrive Joint field is set to RE40 by automatic reference to the previous component, namely the fire damper. Click the Apply button and then click the Cancel button.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
77
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 7 - Completing the Design – Modifying Joint Types 1.
Using the worked example, modify the joint types for the remaining Fire Dampers for BRAN SUPPLY_LEVEL02-001. All joint types to be updated to Raw Edge Joint slip over 40mm (RE40) joint.
8.4.2
Inserting an Access Panel – A Worked Example
The final component of the HVAC ducting network is an access panel in the straight before the final Fire Damper (FD4) of the main branch SUPPLY_LEVEL02-001. An access panel will be inserted; whose catalogue definition includes a predefined working volume, into the side of the aforementioned straight. Navigate to the appropriate straight. From the HVAC form, select Rectangular from the Categories list and then select Access Panel from the Available Types list to display the Access Panel form. Set the Select Size option to 300x200 and Dist from Leave to 200mm. Click the OK button.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
78
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
The amount of detail shown in the 3D for different components is controlled by the current graphical representation settings. These can be checked by selecting Graphics from the Settings group on the 3D View tab to display the Graphics Settings form. On the Representation tab select 50% from the Obstruction Visibility / Translucency dropdown menu. Note:- The obstruction volumes on all displayed components are now shown as a 50% translucency..
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
79
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
This page is intentionally left blank.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
80
www.aveva.com
CHAPTER 9 9
Hole Management
On a typical AVEVA E3D project it is necessary for designers to create holes in panel elements, i.e. deck plates, grating, walls, floors, etc. Due to the implications on design integrity and cost, the hole creation process needs to be controlled and managed.
9.1
Introduction to Hole Management
AVEVA E3D controls and manages holes using the Hole Management application which facilitates: Communication of hole data between disciplines including Request and Approval processes. Ensuring holes are only created by users with appropriate write access permissions. Performing validation checks on managed holes and providing feedback to users on the hole status. Generation of reports for managed holes. Generally in AVEVA E3D projects discipline Designers do not have write access to items created by other disciplines, i.e. a Piping Designer does not have write access to Structural elements and Structural Designers do not have write access to Piping elements, etc. With Hole Management penetration holes are specified and requested by the penetrating discipline, normally piping, HVAC or equipment designers, and approved by the penetrated discipline, normally structural Designers. For cases where a penetration is required, say, for a steel section through a deck/floor plate, the hole would be specified, requested and approved by the structural discipline. The specification of a penetration hole by the relevant discipline in the appropriate Design application creates a ‘virtual hole’ in the panel element, consisting of a FRMW and two FIXING elements. Each fixing element has a Specification Reference (Spref) attribute that points to the hole definition in the catalogue. An Association (ASSOC) element that references all of the hole elements is also created. Once the ‘virtual hole’ has been created the penetrating discipline enters the Hole Management application and requests the hole. The owner of the panel, normally the Structural discipline, then reviews and approves (or rejects) the hole request using the mechanism provided by the Hole Management application. The act of approving the request creates the ‘actual’ hole as a PFIT owned by the PANE element. The Hole Management application checks and validates the hole using the association restrictions and stores data on the hole history and status. Only valid holes may be approved. For a structural penetration the Structural Designer may be both the requester and approver, although specific company procedures, controlled by DAC, may be required if the Originator and Reviewer need to be different.
9.1.1
Hole Element Storage
The ‘virtual hole’ FIXING elements are stored in a FRMW owned by a STRU whose Purpose attribute is set to HOLE, for example:
The STRU element is normally pre-defined by the System Administrator in specific Design database. If a suitable STRU does not exist, the following error message is displayed:
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
81
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The Hole Management associations are stored in an Association Group (ASSOGP) element owned by an Association World (ASSOWL) element. The ASSOGP must also have its Purpose attribute set to HOLE. The ASSOWL and ASSOGP elements are normally pre-defined by the System Administrator. An association is created for each hole and named on a simple sequential numbering system. Each association has several members of different element types that not within the scope of this training guide. The Model Explorer may look like this:
If no ASSOGP element with the Purpose set to HOLE can be found, the Hole Management application will create an ASSOGP in the first writeable ASSOWL element and set the Purpose attribute. If no writeable ASSOWL element can be found the following error message is displayed.
9.1.2
Request and Approval Workflow
Once the penetration hole has been specified and the ‘virtual’ hole created, the Hole Management application provides a series of tasks for the Originator (Penetrating discipline) and Reviewer (Structural discipline). These tasks are: Originator Tasks
Reviewer Tasks
Request Redundant Cancel Request Delete Entry
Approve Reject Agree Redundant
There are three main workflow scenarios for the request/approval cycle that are detailed in the following sections.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
82
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
9.1.2.1 Hole Creation/Modification Workflow
In this workflow the Originator creates the ‘virtual’ hole and then either requests it or deletes the entry. Once requested, the Originator may cancel the request and delete the entry prior to it being reviewed. If requested and not cancelled or deleted, the Reviewer checks the hole details and, if OK, approves the hole, thereby creating the ‘actual’ hole. If the Reviewer rejects the hole then the Originator can either modify the ‘virtual’ hole and re-request the hole or cancel the request and delete the entry.
9.1.2.2 Redundant Hole Workflow
In this workflow the ‘actual’ hole has been created. The Originator decides that the hole is now redundant and sets its status to Redundant. Before the Originator can delete the entry the Reviewer must agree that the hole is redundant.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
83
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
9.1.2.3 Rejected Hole Workflow
In this workflow the ‘actual’ hole has been created. The Reviewer, possibly due to changed conditions, decides to reject the hole. The Originator has the option to: Modify the hole and re-request it, whereby it will go through the normal review and approval cycle. Cancel the request, in which case the ‘virtual’ hole details remain Delete the entry, in which case the entire hole is deleted and the ‘virtual’ hole and association deleted. The ‘actual’ hole is deleted and the panel restored to its original state.
9.1.3
Non-penetration Managed Holes
In addition to penetration holes, the Hole Management application enables creation of non-penetration holes in structural panels. These holes fall into two general categories: Holes that are required, say, to access to a piece of equipment, a valve or other design item. Holes that are created by a panel fitting, e.g. a hatch, door, window, etc. For non-penetration managed holes that are not created by a fitting, with the exception of a User Defined hole type, the ‘virtual’ hole is created as a single FIXING in a new FRMW, as described for penetration holes. This fixing has a Specification Reference (Spref) attribute that points to the hole definition in the catalogue. An Association (ASSOC) element that references all of the hole elements is also created. Approving the hole creates an SFIT owned by the PANE. User Defined hole shapes are created using a template and negative extrusion in a similar way as described below for Fitting holes. For non-penetration holes that are created by a panel fitting, the ‘virtual’ hole is created as a single FIXING in a new FRMW. The fixing owns a Template (TMPL) element that owns a negative extrusion (NXTR) whose vertices describe the required hole shape. The fitting is created as a FIXING element owned by the PANE whose Spref attribute points into the catalogue to the selected fitting. An Association (ASSOC) element that references all of the hole elements is also created. Approving the hole creates an NXTR owned by the PANE that is a copy of the ‘virtual’ hole NXTR. Non-penetration managed holes, of either type, may be associated with any other element in Design. The holes have the same request/approval process as penetration holes, however, as they are created solely by the structural discipline the Structural Designer may be both the requester and approver. © Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
84
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
9.1.4
Use of the Hole Management Application
The Hole Management application, as with other applications that use associations, is passive, i.e. the user is not alerted if a hole association is broken or invalidated. The user must enter the Hole Management application and actively verify if the association is still valid. The use of the application will vary from company to company. In some it may be down to the individual Designers to request and approve holes, whilst in others it may be the discipline lead Designer or a designated user who performs the tasks.
9.2
Penetration Holes – A Worked Example
The creation and requesting of penetration hole is generally performed by discipline personnel, in this case the HVAC Department, and creation of the actual hole in normally carried out by the panels discipline, for example the Structural Department. For the purposes of this worked example, i.e. to show the complete workflow, the HVAC holes will be created and requested as well as approved.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
85
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
9.2.1
Creating an HVAC Penetration
Set up the view as shown.
Select Create Penetration HVAC dropdown menu on the Penetrate group on the HVAC tab to display the Create Penetration form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
86
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Click the Pick Penetrated Items button on the form and graphically select the roof of building B01 as shown above. The panel’s system name is displayed in the grid below the button. Click the Pick Penetrating Items button on the form and select the two penetrating HVAC as shown above. The HVAC name is displayed in the grid below the button.
Multiple penetrated items and multiple penetrating items may be selected. The same penetration hole is applied to all selected penetrating items.
Click the OK button. The Hole Management Definition form will now be displayed.
The Single or Merged Penetration area at the top of the form enables individual single holes or a merged hole to be specified for multiple penetrating items by selecting the appropriate radio button. Set the option to Merged. The Hole Shape selection area of the form contains Class options lists that enables the user to select the class of hole, i.e. Standard Types, Piping penetration piece tables and Pipe Duct. The Type options list changes depending on the Class selected. For this example Standard Types will be used. The Type options list has the following entries.
A description of the different types of hole shapes is outside the scope of this training guide. The Hole shape parameters area of the form displays different parameter textboxes for the different hole types. For a Rectangular Hole the Width, Height and Radius can be set. Set the Type to Rectangular Hole – Type HR. Set the Width to 600mm, Height to 1250mm and Radius to 25mm. The Penetrating item clearance area of the form contains the Clearance textbox that enables a clearance around the penetrating item to be specified. Set the Clearance to 0.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
87
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The ‘virtual’ hole clearance fixing is displayed at the specified clearance diameter. The Positioning area of the form enables an offset in the X and Y directions for the penetration hole to be specified by entering appropriate values in the X Offset and Y Offset textboxes. This enables the penetrating item to be eccentric to the penetration hole, which may be required in some circumstances. The Rotation gadget enables the hole shape be rotated to align the hole in a different direction. This is only relevant on non-circular hole shapes. The rotation value may be set by using the up or down arrow or by entering a value in the textbox. Clicking the OK button on the Hole Management – Definition form creates the FRMW and two ‘virtual’ hole FIXING elements, one for the clearance diameter and one for the penetration hole, in the STRU whose Purpose attribute is set to HOLE. The top level fixing is auto-numbered using the format HM-VH-nnnn, where nnnn is a four digit sequential number starting at 0001. The secondary level fixing is auto-numbered using the format HM-VH-nnnn-SUB-nn, where HMVH-nnnn is the name of the top level fixing and nn is a two digit sequential number starting at 01. The association is created in the ASSOGP whose Purpose attribute is set to HOLE and is automatically named using the format HMASSOC-nnnn, where nnnn is a four digit sequential number starting at 0001.
9.2.2
Managing Holes – Requesting a Hole
Now the holes have been defined a request must be made for the holes to be created in the appropriate panel. This is facilitated by the Hole Association Manager form. Select Hole Manager from the Holes dropdown menu on the Penetrate group on the HVAC tab to display the Hole Association Manager form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
88
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 This form is used to display the Hole Associations in the model and is controlled by the Hole Association Filters.
9.2.2.1 Using the Hole Association Filters The Hole Association Filter area of the form enables the user to limit the display of the hole associations in the Hole Associations grid below by using the various radio buttons and options lists. The three radio buttons have the following function: Current Element – applies the filters to the current element only. List of elements – applies the filters to the elements in the Elements to manage list at the bottom right of the form. If this option is selected the Elements to manage list and its associated link labels are enabled. The Add Current Element link label adds the current element to the list. The Reset link label clears the list and adds the current element to it.
The Refresh link label starts the filtered search for all managed holes that reference any item in the list.
Right clicking an item in the list displays a pop-up menu that enables the selected item to be removed from the list.
All Managed Holes – applies the filters to all the managed holes in the project. The four filter option lists have the following functions: Discipline – enables the user to select only holes belonging to a specific discipline.
Status – enables the user to select only holes with a specific approval status.
Claimed – enables the user to select holes with a specific Claim status.
Valid – enables the user to select only holes that have passed/failed the validation test.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
89
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Setting any Validity option other than Not Checked may significantly slow down the list generation. This is because all validation tests will be run for every hole that passed the previous three filter options.
The Invalid checkbox, if checked, will include all hole associations that have any bad references or invalid data. The checkbox is enabled if the List of elements or All Managed Holes radio buttons is selected. The Apply filter link label refreshes the Hole Associations list according to the element and filtering. In the Model Explorer, navigate to Site SITE_STRUCTURAL_AREA02 and expand the hierarchy to STRU level. Make STRU BUILDING_01_LEVEL_03 the CE. Open the Hole Association Manager form and set the Hole Association Filters to match the details provided below.
Select Discipline Status Claimed Valid
Current Element HVAC All All Not Checked
Once the settings are made click the Apply filter link label.
The newly created hole will be populated in the Hole Associations grid. Select the hole and then click the Manage Selected Holes link label in the lower left corner of the form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
90
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Under the Originator Tasks heading select the Request link label.
A confirmation message will be displayed. Click the Yes button. Expand the Hole validation results panel and check that all results are passed.
Expand the Hole History panel and note that the status has changed to REQUESTED.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
91
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
9.3
Approving Holes
The HVAC Designer would not normally be able to approve the requested holes. Hole approval is the responsibility of the discipline that owns the Panel or Floor. Select Setup from the Training group on the Tools tab to display the Training Setup form. Navigate to the Switch User tab. Enter the current user password (previously supplied by the trainer) then change to a structural user by entering the following information: New User Name: A.STEELMAN Password: A
Click the Switch User button, and then close the Training Setup form. Select Hole Manager from the Holes dropdown menu on the Penetrate group on the HVAC tab to display the Hole Association Manager form. Set the Hole Association Filters to match the details provided below. Select
Current Element
Discipline
HVAC
Status
All
Claimed
All
Valid
Passed
Once the settings are made click the Apply filter link label. Click the R.H. Mouse Button and select Add to 3D view from the pop up menu.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
92
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Select the First Hole and select Navigate To > Association from the pop-up sub-menu. Select the Manage Selected Holes link label from the lower left corner of the form.
Under the Reviewers Tasks list select the Approve link label.
A confirmation message will be displayed. Click the Yes button.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
93
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The Hole is now created.
Open the Hole History fold-up panel and note the new Status column entry.
Click the Return to Hole Associations link label at the bottom of the Hole Management form to return to the Hole Association Manager form.
9.4
Rejecting a Hole
The Reviewer may make reject a hole on initial review or after it has been approved. In either case the Originator has the option to modify the hole and re-request, cancel the request or delete the entry.
9.4.1
Rejecting on Initial Review
Highlight the new hole in the grid (HM-ASSOC-0001) and select the Manage Selected Hole link label. Enter Hole Must be Oval in the Hole comment textbox. Press the Return key and click the Save button.
Click the Reject link label under the Reviewer Tasks and click the Yes button on the confirmation message. The hole has been rejected by the Reviewer; however, the comment indicates that if the hole is Oval then it will be approved. Therefore, the Originator must decide if the Oval hole is definitely required or a rectangular hole will be OK.
9.4.2
Rejecting after Approval
Select the first penetration hole created (HM-ASSOC-0001) in the grid to make it the current association and click the Manage Selected Holes link label to display the Hole Management form. This hole has previously been approved so the only Reviewer task available is Reject. © Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
94
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Click the Reject link label under the Reviewer Tasks and then click the Yes button on the confirmation message. The hole status has now changed to Rejected. Note that none of the Originator or Approval Tasks will be active at this point. The Designer must switch user, back to the Originator of the request.
The Steelwork Designer would not normally be able to Request HVAC hole. Hole Requests are the responsibility of the discipline that owns the HVAC.
Select Setup from the Training group on the Tools tab to display the Training Setup form. Navigate to the Switch User tab. Enter the current user password then change to a HVAC user by entering the following information: New User Name: A.HVACMAN Password: A Click the Switch User button, and close the Training Setup form. Select Hole Manager from the Holes dropdown menu on the Penetrate group on the HVAC tab to display the Hole Association Manager form. Click the right mouse button and select Navigate To.
You will be taken to the specified hole within Model Explorer. With the hole highlighted within the Hole Management form right click and select Add to 3D view then Focus on Hole.
The Originator now has the option to modify the hole definition, as described above, Cancel Request or Delete Entry, which have the following affects: Cancelling the request removes the ‘actual’ hole and resets the Hole History Status to blank, i.e. it has been reset to its original status after the ‘virtual’ hole was created but before it was requested. The ‘virtual’ hole fixings and hole management associations are retained so that the hole may be © Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
95
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 modified and re-requested later. Deleting the entry deletes the ‘actual’ hole, the ‘virtual’ hole fixings and the hole management associations, restoring the panel to its original state before the penetration was created. All references to the ‘virtual’ hole are deleted. For this example the request will be cancelled and then the entry deleted. Click the Cancel Request link label under the Originator Tasks to display the cancel confirmation message. Click the Yes button to cancel the request.
Open the Hole History fold-up panel and note that the hole status is blank, i.e. Note also that the ‘virtual’ hole fixings are still present.
Click the Delete Entry link label under the Originator Tasks to display the remove confirmation message. Click the Yes button to remove the selected hole.
9.5
All references to the hole have been deleted from the Hole Management form and the ‘virtual’ hole fixings have also been deleted, restoring the panel to its original state before the penetration was created.
Making a Hole Redundant
Once the hole has been approved, it can be made redundant by the originator if required. This can be done by clicking the Redundant link label under the Originator Tasks. A confirmation message is displayed to the user confirming the action. Before the Originator can delete the entry the Reviewer (A.STEELMAN) has to agree it is redundant. This can be done by clicking the Agree Redundant link label under the Reviewer Tasks on the Hole Association Manager form. A confirmation message is displayed to the user confirming the action. Once completed, the hole status is set to Withdrawn. At this point, the only available task to the originator is to Delete Entry. Clicking this link label deletes the hole entry and restores the panel at the penetration.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
96
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Exercise 8 – Create HVAC Penetrations 1.
Using the worked examples as a reference, create 2 new single penetrations for HVAC BRAN /SUPPLY_LEVEL02-001 and BRAN /RETURN_LEVEL02-001 through the roof of /BUILDING_B01. 2. Set the type of Hole type to TYPE HR and size to 500mmx500mm.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
97
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
98
www.aveva.com
CHAPTER 10 10
Checking and Outputting Design Data
This chapter describes the following: Methods of checking for errors and inconsistencies in the HVAC layout. How to output a design data report derived from the HVAC model. How to generate an isometric plot.
10.1
Most of these facilities are available from all Design applications. It is possible to readily check and output data from any combination of design disciplines.
Querying Data Settings
Specific data settings can be queried by the user as the design model is created. This allows the designer to check the detailed design at any stage in the modelling process. Clear the 3D view, and then add BRAN /SUPPLY_LEVEL02-001/02. Select the first branch connector as shown.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
99
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
10.1.1
Item Details
Select HVAC from the Query group on the HVAC tab to display the HVAC Component form The form displays all the relevant data with regard to the CE highlighted The Brief Description section displays a summary showing the components type, key dimensions and joint specifications. The Component Details section displays its specification. Item number, the coordinates of the origin, the PA (P-Arrive) the PL (P-Leave), the P3 and the objects orientation. The Taper Side Angles The Branch Details section displays the coordinated for the head / tail positions, the detail specification and the insulation depth. The Gap to next HVAC component displays the gap size and the direction of the PL(P-Leave) and the A&B planes.
10.2
Checking for Design Data Inconsistencies
The data consistency checking utility, available within Design’s Piping, HVAC and Structural applications, reports the following types of occurrence (and other similar errors) in the design: Branch head or tail reference not set. Branch Head or tail reference type not valid. Adjoining components have incorrectly ordered PA and PL points, i.e., one component may have been flipped while its neighbour was not. Distance between a component and a connected neighbour, or between a component and the branch head or tail, is not valid. Neighbouring connected components, or a component and the branch head or tail, have their PA/PL misaligned. Arrive or leave joint has wrong connection type. To check the design for data consistency errors, select Data Consistency from the Check group on the Tools tab to display the Data Consistency Check form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
100
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
The Check list allows the user to specify how much of the design model is to be checked in a single operation. To check each branch separately, select Branch from the list. Clicking the HVAC… button under the Parameters section of the form displays the HVAC Consistency Check Options form.
Uncheck the Check attachment points option. Click the OK button. Navigate to the BRAN SUPPLY_LEVEL02-001 and click the Check button. The resulting diagnosis is displayed in the scrollable text area of the Data Consistency Check form.
10.3
Data Check Functions
Further checking can be carried out using the Data Checker facilities, select Checker from the Check group on the Tools tab to display the Checker form. The form contains four pull-down menus: Control allows the user to Save an existing check, Load a previously failed check. Reload Checks enables the user to add newly created checks to the form. This task would normally be done by an administrator. Add allows the user to include the elements to be checked using CE, CE Members, Pick, Failed List and List. This will in turn populate the Check Items section of the form. Remove uses All, Selected, CE, CE Members, Pick and List to remove items already placed in the Check Items section of the form. Highlight allows the user to determine how the representation of the results will be shown to the user.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
101
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The form includes a customised class of checks specific to the HVAC functions. AVEVA provide a small set of HVAC checks to introduce users to this powerful utility. The functionality of the Data Checker can be extended or modified using the AVEVA PML2 facilities. The available checks are defined in a file named ‘comchecks.pmldat’ stored in the company or project defaults directory. The user can organise the checks by class and groups. An example file is shown; the class and group settings can be clearly seen. The example file produces form values as shown.
The Classes section of the form enables the user to indicate the type of design element that will be checked. This will filter the selections available under the Groups pull-down.
The Groups section determines the level at which the check will be performed. As already stated the content of the pull-down is influenced by the Class that has already been set.
Selecting the Groups will in turn populate the Checks list of the form allowing the user to select the Check to be carried out. Once the Check has been selected from the list the Check button becomes active. Click the Check button to perform the check.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
102
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
The results of the check will be displayed in the Checker Results form and highlighted graphically for cross referencing with the form. The Checker Results form is split into two sections: Passed will list all the elements that successfully passed the checker. Failed will list the elements that failed individually and describe the reason for the failure. The representation of the graphical view and the Checker Result form is controlled via the Highlight pulldown on the Checker form.
10.4
Mass Properties
These values may be calculated for HVAC elements by navigating to the Model Query group within the Tools tab. The three main types of Mass Property are: Weight C of G (Centre of Gravity) Area Volume
The options and settings available in the Mass Properties forms is covered in detail in the AVEVA E3D Design Utilities Training Guide (TM-1003)
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
103
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
104
www.aveva.com
CHAPTER 11 11
HVAC Spooling
The HVAC Spooling utility allows the user to split the HVAC design into logical sections (spools) to facilitate component fabrication. Hence an HVAC Spool is a collection of HVAC elements to be manufactured as a single entity. The HVAC element contains a HSLIST, which contains HSPOOL elements. These elements are managed by the application and cannot be deleted outside of the HVAC spool application. The size and connections of HVAC components are controlled by its design parameters. The spool split point is also a design parameter and to set it use the following syntax at BRAN members.
11.1
DESP N37 TRUE
The component is the last in the current spool
DESP N37 FALSE
The component is a member of the current spool
The administrator can query the design parameter value with the use of a property created for that purpose using the query syntax Q PROP SPLI.
Generating HVAC Spools using HVAC Spool Manager – A Worked Example
The following demonstrates how the HVAC Spool Manager enables the user to generate HVAC spools automatically. Clear the 3D view and add HVAC /B01_LEVEL02_AC-RETURN to 3D view. Click the Spooling button located in the Tools group on the HVAC tab to display the HVAC Spool Manager form. The Set HVAC button allows users to set the CE as the HVAC element to be spooled. The form also allows users to set Naming options for the HVAC spool. There are two available options: Auto Name – allows users to use the predefined auto naming rules. When checked, the HVAC Spool List Name and Spool Prefix text boxes are greyed out. User Defined Name – allows users to explicitly define HVAC Spool List Name and a Spool Prefix. HVAC Spool List Name is populated by default with the name of the current HVAC suffixed with “-Spools”. This is a suggested name which can be overwritten.
The Generate Spools link label creates the spools and populates the HVAC Spool Manager form with a Spool list. The spools are also visible in the Model Explorer. Click the Auto Name radio button, and click the Generate Spools link label. The spools have now been generated and displayed in the HVAC Spools list on the HVAC Spool Manager form. A HSLIST element is also created at the same hierarchical level as the HVAC with HSPOOLs as its members.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
105
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
Selecting a spool in the list highlights that particular spool in the 3D view as shown below.
The Delete Spools link label will remove all the generated Spools and return the user to the HVAC Spool Manager form. The Regenerate link label regenerates the Spool list allowing for any modifications applied by the user.
11.2
Delete Spools does alter the configuration of the spools see 7.3 Modifying a HVAC Spool
HVAC Spool Verification – A Worked Example The Verify HVAC and Verify HVAC Spool link labels verify the contents of the list or the selected spool from the list and display the results in the HVAC Spools list.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
106
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
The verification results are listed in two columns: Verification Status shows whether the Spool is “Successful” or “Failed” Failure Details Lists error messages. Click the Verify HVAC link label, and check the results in the Verification Status column of the grid
The Results Summary displays the verification result for the Spool list and indicates any required modification to make the list valid.
11.3
Modifying an HVAC Spool – A Worked Example
The spool content can be modified using the two options:
Add Spool Elements Adds element(s) to a spool in the list.
Remove Spool Elements Removes element(s) from a spool in the list.
Select B01_LEVEL02_AC-RETURN/HS/009 from the HVAC Spool list. This spool will modified in a way that the adjacent components i.e. straight, threeway piece and a second straight will be added to the selected spool Click the Add Spool Elements link label. This prompts the user to ‘Pick HVAC components to add to the selected spool’. Graphically pick the adjacent straight, threeway piece and a second straight from the 3D view. Once selected, press the Escape key. Selecting B01_LEVEL02_AC-RETURN/HS/006 from the list will now highlight the modified HVAC Spool.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
107
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 The HVAC must be verified again once spools have been modified. Click the Verify HVAC link label to make sure no errors are reported.
To remove elements the owning spool is selected in the list. Selecting the Remove Spool Elements link label prompts the user to ‘Pick HVAC components to remove from the selected spool’, select an item(s) graphically to remove. Press the Escape key to complete the selection. It may be necessary to use the Add Spool Elements function once again to spool elements that have been removed.
The system will attempt to maintain the existing adjacent spools automatically, however, it is important that the spools are deleted and regenerated to maintain any sequential numbering.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
108
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
11.5
HVAC Sketches
HVAC Sketches are orthogonal spool drawings. Once the HVAC spooling is complete, HVAC sketches can be produced using this design data.
HVAC Sketch Production is created using the Automatic Drawing Production utility in Draw and is covered in detail in the TM1831 – Automatic Drawing Production Training Guide.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
109
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
This page is intentionally left blank.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
110
www.aveva.com
CHAPTER 12 12
HVAC Equipment Nozzles
HVAC Equipment nozzles act as an interface point between pieces of equipment and the connecting HVAC ducting, the user can create, then position and orientate the HVAC Nozzle. In this chapter, equipment nozzles will be created on the existing equipment in the project and subsequently the HVAC Ductwork connected to these nozzles.
12.1
Creating HVAC Nozzles on Equipment Elements – A Worked Example
Clear the 3D view and then add the following to 3D view. HVAC Main Branch SUPPLY_LEVEL02-001 Structural Zone BUILDING_B01 Air Handling Unit :SKID B01-AHU-001 (member of ZONE-EQUIPMENT-AREA02B01)
Navigate to EQUI-B01-AHU-001_SKID in the Model Explorer. From the HVAC form, select Equipment Nozzles from the Categories list and then select Circular Nozzle from the Available Types list to display the HVAC Equipment Nozzle form. Set the Name(Ref) to /B01-AHU-001SUPPLY Click the Apply button. The nozzle has now been created and placed at the origin of the equipment. The form is also updated to the Modify mode. Set the Leave Direction to W and Leave ‘X’ Axis to N under the Modify Orientation section.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
111
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817 Using the Model Editor, position the nozzle in line with the duct as shown. Navigate to the branch SUPPLY_LEVEL02-001 and click the HVAC from the Modify group on the HVAC tab, the Modify Confirmation form will be displayed. Select the Main Branch radio button then click OK
On the HVAC Main Branch form Set the Head Start to ID Nozzle. Click the Apply button. The on screen prompt states ‘identify NOZZ’, select the newly created Nozzle from the 3D view. The Head of the branch will be automatically connected and moved to the origin of the nozzle. Click Cancel to close the form.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
112
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
A new Circular Male coupling will need to be created at the start of the branch. From the HVAC form, select Circular from the Categories list and then select Male Coupling from the Available Types list to display the Male Coupling form. Click the OK button.
As new implied tube has been introduced as a result of repositioning of Branch head, auto-fill the gaps of the ductwork with straights. Note the change in the design hierarchy.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
113
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
This page is intentionally left blank.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
128
www.aveva.com
APPENDIX E Appendix E – Three-way Component A three-way component enables users to connect one branch to another. A three-way component is required so that a side branch can be connected to the existing main branch. rd
The flow direction through the three-way component is controlled using the Arrive, Leave, 3 option list. Three options are provided; Standard Configuration, Flip Arrive/Leave, and Flip Arrive/P3. The flow directions produced by each option are demonstrated below.
Standard Configuration
Flip Arrive/Leave
Flip Arrive/P3
The Orientation of the three-way component is determined by the configuration selected and the Change Direction entered.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
129
www.aveva.com
AVEVA Everything3D (1.1) Heating, Ventilation & Air Conditioning Modelling TM-1817
This page is intentionally left blank.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
128
www.aveva.com
APPENDIX E Appendix E – Three-way Component A three-way component enables users to connect one branch to another. A three-way component is required so that a side branch can be connected to the existing main branch. rd
The flow direction through the three-way component is controlled using the Arrive, Leave, 3 option list. Three options are provided; Standard Configuration, Flip Arrive/Leave, and Flip Arrive/P3. The flow directions produced by each option are demonstrated below.
Standard Configuration
Flip Arrive/Leave
Flip Arrive/P3
The Orientation of the three-way component is determined by the configuration selected and the Change Direction entered.
© Copyright 2012 to current year. AVEVA Solutions Limited and its subsidiaries. All rights reserved.
129
www.aveva.com