ETAP 5.0 Protective Device Coordination
Copyright 2004 Operation Technology, Inc.
Agenda • OC Protective Device Coordination – Concepts & Applications
• STAR 5.0.0 Overview – Features & Capabilities • STAR Example 1
– Advance Topics • STAR Example 2
– PD Sequence of Operation – Device Libraries – ETAP ARTTS Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 2
Definition • Overcurrent Coordination – A systematic study of current responsive devices in an electrical power system.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 3
Objective • To determine the ratings and settings of fuses, breakers, relay, etc. • To isolate the fault or overloads.
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 4
Criteria • Economics • Available Measures of Fault • Operating Practices • Previous Experience
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 5
Design • Open only PD upstream of the fault or overload • Provide satisfactory protection for overloads • Interrupt SC as rapidly (instantaneously) as possible • Comply with all applicable standards and codes • Plot the Time Current Characteristics of different PDs Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 6
Analysis When: • New electrical systems • Plant electrical system expansion/retrofits • Coordination failure in an existing plant
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 7
Protection vs. Coordination • Coordination is not an exact science • Compromise between protection and coordination – Reliability – Speed – Performance – Economics – Simplicity Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 8
Protection • Prevent injury to personnel • Minimize damage to components – Quickly isolate the affected portion of the system – Minimize the magnitude of available short-circuit
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 9
Spectrum Of Currents • Load Current – Up to 100% of full-load – 115-125% (mild overload)
• Overcurrent – Abnormal loading condition (Locked-Rotor)
• Fault Current – Fault condition – Ten times the full-load current and higher Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 10
Coordination • Limit the extent and duration of service interruption • Selective fault isolation • Provide alternate circuits
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 11
Coordination C t
D B
A A C
D
B
I
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 12
Equipment • Motor • Transformer • Generator • Cable • Busway Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 13
Capability / Damage Curves 2
It
t
I2t
I2t
I22t
Motor Gen
Xfmr
Cable
I
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 14
Transformer Category ANSI/IEEE C-57.109
Minimumnameplate (kVA) Category Single-phase Three-phase I 5-500 15-500 II 501-1667 501-5000 1668-10,000 5001-30,000 III IV above 1000 above 30,000
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 15
Infrequent Fault Incidence Zones for Category II & III Transformers Source Transformer primary-side protective device (fuses, relayed circuit breakers, etc.) may be selected by reference to the infrequent-faultincidence protection curve Infrequent-Fault Incidence Zone*
Category II or III Transformer Fault will be cleared by transformer primary-side protective device Optional main secondary –side protective device. May be selected by reference to the infrequent-faultincidence protection curve Fault will be cleared by transformer primary-side protective device or by optional main secondaryside protection device Feeder protective device
Frequent-Fault Incidence Zone*
Fault will be cleared by feeder protective device Feeders
* Should be selected by reference to the frequent-fault-incidence protection curve or for transformers serving industrial, commercial and institutional power systems with secondary-side conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by reference to the infrequent-fault-incidence protection curve. Source: IEEE C57 Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 16
Transformer FLA
200
t (sec)
Thermal I2t = 1250
(D-D LL) 0.87
Infrequent Fault (D-R LG) 0.58
2
Frequent Fault
Mechanical K=(1/Z)2t Inrush
2.5
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Isc
25
I (pu)
Slide 17
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 18
Transformer Protection MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE PRIMARY SECONDARY Over 600 Volts Over 600 Volts 600 Volts or Below Transformer Rated Impedance
Circuit Breaker Setting
Fuse Rating
Circuit Breaker Setting
Fuse Rating
Circuit Breaker Setting or Fuse Rating
Not more than 6%
600 %
300 %
300 %
250%
125% (250% supervised)
More than 6% and not more than 10%
400 %
300 %
250%
225%
125% (250% supervised)
Table 450-3(a)
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
source: NEC
Slide 19
Protective Devices • Fuse • Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, …) • Thermal Magnetic • Low Voltage Solid State Trip • Electro-Mechanical • MCP • Overload Heater Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 20
Fuse • Non Adjustable Device • Continuous and Interrupting Rating • Voltage Levels • Characteristic Curves – Min. Melting – Total Clearing
• Application Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 21
Total Clearing Time Curve
Minimum Melting Time Curve
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 22
Current Limiting Fuse (CLF) • Limits the peak current of short-circuit • Reduces magnetic stresses (mechanical damage) • Reduces thermal energy
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 23
Peak Let-Through Amperes
Let-Through Chart 15% PF (X/R = 6.6) 230,000
300 A 100 A
12,500
60 A
5,200
100,000
Symmetrical RMS Amperes Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 25
Fuse Generally: • CLF is a better short-circuit protection • Non-CLF (expulsion fuse) is a better Overload protection
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 26
Selectivity Criteria Typically: • Non-CLF:
140% of full load
• CLF:
150% of full load
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 27
Molder Case CB • Thermal-Magnetic
Types
• Magnetic Only
• Frame Size
• Integrally Fused
• Trip Rating
• Current Limiting
• Interrupting Capability
• High Interrupting Capacity
• Voltage
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 28
Thermal Maximum
Thermal Minimum
Magnetic (instantaneous)
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 29
LVPCB • Voltage and Frequency Ratings • Continuous Current / Frame Size – Override (12 times cont. current)
• Interrupting Rating • Short-Time Rating (30 cycle) • Fairly Simple to Coordinate
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 30
LT PU
CB 2
CB 1
CB 2
LT Band
480 kV
ST PU
CB 1
IT If =30 kA ST Band
Motor Protection • Motor Starting Curve • Thermal Protection • Locked Rotor Protection • Fault Protection
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 32
Motor Overload Protection (NEC Art 430-32)
• Thermal O/L (Device 49) • Motors with SF not less than 1.15 – 125% of FLA
• Motors with temp. rise not over 40 – 125% of FLA
• All other motors – 115% of FLA Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 33
Locked Rotor Protection • Thermal Locked Rotor (Device 51) • Starting Time (TS < TLR) • LRA – LRA sym – LRA asym (1.5-1.6 x LRA sym) + 10% margin
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 34
Fault Protection (NEC Art 430-52) • Non-Time Delay Fuses – 300% of FLA
• Dual Element (Time-Delay Fuses) – 175% of FLA
• Instantaneous Trip Breaker – 800% of FLA*
• Inverse Time Breakers – 250% of FLA
*MCPs can be set higher Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 35
(49) 2 IT
tLR
O/L
MCP
(51)
ts Starting Curve
MCP (50)
LRAs
LRAasym
200 HP
Overcurrent Relay • Time-Delay (51 – I>) • Short-Time Instantaneous ( I>>) • Instantaneous (50 – I>>>) • Electromagnetic (induction Disc) • Solid State (Multi Function / Multi Level) • Application
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 37
Time-Overcurrent Unit • Ampere Tap Calculation – Ampere Pickup (P.U.) = CT Ratio x A.T. Setting – Relay Current (IR) = Actual Line Current (IL) / CT Ratio – Multiples of A.T. CT
IL
= IR/A.T. Setting = IL/(CT Ratio x A.T. Setting)
IR 51
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 39
Instantaneous Unit • Instantaneous Calculation – Ampere Pickup (P.U.) = CT Ratio x IT Setting – Relay Current (IR) = Actual Line Current (IL) / CT Ratio – Multiples of IT CT
IL
= IR/IT Setting = IL/(CT Ratio x IT Setting)
IR 50
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 40
Relay Coordination • Time margins should be maintained between T/C curves • Adjustment should be made for CB opening time • Shorter time intervals may be used for solid state relays • Upstream relay should have the same inverse T/C characteristic as the downstream relay (CO-8 to CO-8) or be less inverse (CO-8 upstream to CO-6 downstream) • Extremely inverse relays coordinates very well with CLFs Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 41
Fixed Points Points or curves which do not change regardless of protective device settings: • Motor starting curves • Transformer damage curves & inrush points • Cable damage curves • SC maximum fault points • Cable ampacities Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 42
Situation 4.16 kV CT 800:5
50/51
Relay: IFC 53
CB
Cable CU - EPR
1-3/C 500 kcmil
Isc = 30,000 A DS
5 MVA 6%
Calculate Relay Setting (Tap, Inst. Tap & Time Dial) For This System
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 43
Solution Transformer:
5,000kVA = 694 A 3 × 4.16kV 5 IR = IL × = 4.338 A 800
IL =
I Inrsuh = 12 × 694 = 8,328 A Set Relay:
IL IR R
CT
125% × 4.338 = 5.4 A TAP = 6.0 A TD = 1
(6/4.338 = 1.38)
Inst (50) = 8,328 ×
5 = 52.1 A => 55 A 800
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 44
Question What is ANSI Shift Curve?
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 45
Answer • For delta-delta connected transformers, with line-to-line faults on the secondary side, the curve must be reduced to 87% (shift to the left by a factor of 0.87) • For delta-wye connection, with single line-toground faults on the secondary side, the curve values must be reduced to 58% (shift to the left by a factor of 0.58) Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 46
Question What is meant by Frequent and Infrequent for transformers?
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 47
Answer Infrequent Fault Incidence Zones for Category II & III Transformers Source Transformer primary-side protective device (fuses, relayed circuit breakers, etc.) May be selected by reference to the infrequent-faultincidence protection curve Infrequent-Fault Incidence Zone*
Category II or III Transformer Fault will be cleared by transformer primary-side protective device Optional main secondary –side protective device. May be selected by reference to the infrequent-faultincidence protection curve Fault will be cleared by transformer primary-side protective device or by optional main secondaryside protection device Feeder protective device
Frequent-Fault Incidence Zone*
Fault will be cleared by feeder protective device Feeders
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 48
Question What T/C Coordination interval should be maintained between relays?
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 49
Answer B t
A
CB Opening Time + Induction Disc Overtravel (0.1 sec) + Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
I Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 50
Question What is Class 10 and Class 20 Thermal OLR curves?
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 51
Answer • Class 10 for fast trip, 10 seconds or less • Class 20 for, 20 seconds or less • There is also a Class 30 for long trip time
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 52
Answer
Copyright 2004 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
Slide 53