TABLE 9.5.1 9.5.1 Lightin Lighting g Power Power Dens Densiti ities es Using the Building Area Method Building Area Typea
LPD
(W/m2)
Automotive faci li ty
10
Convention center
13
Courthouse
13
Dining: bar lounge/lei sure
14
Dining: cafeteria/fast food
15
Dining: family
17
Dormit ory
11
Exercise center
11
Gymnasium
12
Health-care clinic
11
Hospital
13
H o te l
11
Library
14
Manufacturing facility
14
Motel
11
Moti on picture theat er
13
Multifami ly
8
Museum
12
Office
11
Parking garage
3
Penitentiary
11
Performing arts theater
17
P li
/fi
t ti
11
do not have to comply with the 80% partition height requirements. c. D et ete rm rmi ne ne th the interior lighting power allowance by using the columns designated Space-by-Space Method in Table 9.6.1. Multiply the floor area(s) of the space(s) times the allowed LPD for the space type that most closely represents the proposed use of the space(s). The product produc t is the lighting power allowance for the space(s). For space types not listed, selection of a reasonable equivalent equivalent category shall be permitted. d. The interior lighting power allowance is the sum of lighting power allowances of all spaces. Trade-offs among spaces are permitted provided that the total installed inte does not exceed the interior lighting rior lighting power does power allowance. 9.6.2 9.6.2 Additio Additional nal Inter Interior ior Lighti Lighting ng Power Power.. When using the Space-by-Space Method, an increase in the interior lighting power allowance is allowed for specific lighting functions. Additional power shall be allowed only if the s pecified pecified lighting is installed and automatically controlled, separately from the general lighting, to be turned off during no nbusiness hours. This additional power shall be used only for the specified luminaires and shall not be used for any other purpose. An increase in the interior lighting power allowance is i s permitted in the fo llowing ca ses: a.
For space spacess in which which lighti lighting ng is speci specifie fied d to be instal installed led in in addition to the general lighting for the purpose of decorative appearance, such as chandelier-type luminaries or sconces or for highlighting art or exhibits, provided that the additional lighting power shall not exceed 10.8 W/m2 of such spaces.
TABLE 9.6.1 Common Space Typesa
Lighting Power Densities Using the Space-by-Space Method LPD ,
m
W/
Building-Specific Space Types
2
LPD ,
m
Office—Enclosed
12
Office—Open Plan
12
Playing Area
15
Conference/Meeting/Multipurpose
14
Exercise Area
10
Classroom/Lecture/Training
15
For Penitentiary
Gymnasium/Exercise Center
Courthouse/Police Station/Penitentiary
14
Courtroom
20
14
Confinement Cells
10
For Hotel
12
Judges’ Chambers
14
For Performing Arts Theater
36
For Motion Picture Theater
12
Engine Room
9
10
Sleeping Quarters
3
Lobby
Audience/Seating Area
W/
2
Fire Stations
For Gymnasium
4
Post Office—Sorting Area
13
For Exercise Center
3
Convention Center—Exhibit Space
14
For Convention Center
8
Library
For Penitentiary
8
Card File and Cataloging
12
For Religious Buildings
18
Stacks
18
For Sports Arena
4
Reading Area
13
For Performing Arts Theater
28
For Motion Picture Theater
13
Emergency
29
For Transportation
5
Recovery
9
Atrium—First Three Floors
6
Nurses’ Station
11
Atrium—Each Additional Floor
2
Exam/Treatment
16
Hospital
TABLE 9.6.1
Lighting Power Densities Using the Space-by-Space Method (continued)
Common Space Typesa
LPD ,
m
W/
Building-Specific Space Types
2
Workshop
20
Sales Area [for accent lighting, see Section 9.6.2(b)]
18
LPD ,
m
W/
2
Religious Buildings Worship Pulpit, Choir
26
Fellowship Hall
10
Retail Sales Area [for accent lighting, see Section 9.6.3(c)]
18
Mall Concourse
18
Sports Arena Ring Sports Area
29
Court Sports Area
25
Indoor Playing Field Area
15
Warehouse Fine Material Storage
15
Medium/Bulky Material Storage
10
Parking Garage—Garage Area
2
Transportation
a
Airport—Concourse
6
Air/Train/Bus—Baggage Area
11
Terminal—Ticket Counter
16
In cases where both a common space type and a building-specific type are listed, the building specific space type shall apply.
Table 5>1: IES-Recommended Illumination Levels and LEEP-Allowed Lighting Power Density (Continued ) I. INTERIOR ILLUMINATION LIGHTING PO WER DENSITY LOCATIONS AND TASKS LEVEL (LUX) WATTS/SF WATTS/SQ. M.
Charting and mapping_______________________________________ Graphs Keylining Layout and artwork Photographs, moderate detail Health Ca re Facilities Ambulance (local) Anesthetizing Autopsy and morgue Autopsy, general Autopsy table ___________ ________________________ ________ Morgue, general Cardiac function laboratory Central sterile supply Inspection, general Inspection Work areas, general Processed storage Corridors
750 750 750 500 500
500 1000
0.5 2.2
5.4 23.7
500 5000 ♦
2.2 2.2 ♦
23.7 23.7 *
500
2.2
23.7
300 300 300 300 200
1.4 1.4 1.2 0.9 1.0
15.1 15.1 12.9 9.7 10.8
Table 5.1: IES-Recommended Illumination Levels and LEED-Allowed Lighting Power Density {Continued) ILLUMINATION LIGHTING POWER DENSITY I. INTERIOR LEVEL (LUX) LOCATIONS AND TASKS WATTS/SF WATTS/SQ. M. 10.8 100 1.0 Nursing areas, day 10.8 Nursing areas, night 300 1.0 23.7 500 2.2 Operating areas, delivery, recovery, and laboratory suite and service Critical care areas 23.7 500 2.2 General 1.5 16.1 300 Examination 2.2 23.7 1000 Surgical task lighting Handwashing 1000 500 Cystoscopy room Dental suite 2.2 23.7 500 General 2.2 23.7 500 Instrument tray 23.7 500 2.2 Oral cavity Recovery room 8.6 250 0.8 General 2.2 23.7 500 Dialysis unit, medical 50 Elevators 2.2 23.7 EKG and specimen room * * * General * Facilities not covered by LEED requirements
Table 5,1: lES-Recommended Illumination Levels and LEED-Ailowed Lighting Power Density ( Continued) I. INTERIOR ILLUMINATION LIGHTING POWER DENSITY LOCATIONS AND TASKS LEVEL (LUX) WATTS/SF WATTS/SQ. M.
General Endoscopy rooms General Culdoscopy Eye surgery Fracture room General Local Inhalation therapy Laboratories Specimen collecting Linens Sorting soiled linen Central (clean) linen room Sewing room, general Linen closet Lobby Locker rooms * Facilities not covered by LEED requirements.
500
1.6
17.2
300 300 300 1000 *
2.2
23.7
2.2 *
23.7 *
500 500 *
2.2 2.2 *
23.7 23.7 *
1000
2.2
23.7
300 300 750 300 300 300
0.6 0.6 0.6 0.6 1.2 0.6
6.5 6.5 6.5 6.5 12.9 6.5
r
Table 5.1: IES~Recoramended Illumination Levels and LEED-Allowed Lighting Power Density ( Continued ) ILLUMINATION LIGHTING POWER DENSITY I. INTERIOR LEVEL (LUX) LOCATIONS AND TASKS WATTS/SF WATTS/SQ. M. 1000 Medical illustration studio 11.8 500 1.1 Medical records
Nurseries General Observation and treatment Nursing stations General Desk Corridors, day Corridors, night Medication station Obstetric delivery suite Labor rooms General Local Delivery area Scrub, general General Delivery table Resuscitation
300 300
0.6 1.5
6.5 16.1
300 500 200 50 500 300
1.0 1.0 1.0 1.0 1.2 2.2
10.8 10.8 10.8 10.8 12.9 23.7
300 300 1000 1000 200 1000 1000 1000
2.2 2.2 2.2 2.2
23.7 23.7 23.7 23.7
Table 5.1: lES-Reeommended Illumination Levels and LEED-Allowed Lighting Power Density (
Table 5.1: IES~Recommended Illumination Levels and LEED-AIIowed Lighting Power Density {Continued) ILLUMINATION LIGHTING POWER DENSITY I. INTERIOR LEVEL (LUX) LOCATIONS AND TASKS WATTS/SF WATTS/SQ. M. Radiation therapy section 0.4 4.3 300 Genera!
Solarium General Local for reading Stairways Surgical suite Operating room, general Operating table Scrub room Instruments and sterile supply room Clean-up room, instruments Anesthesia storage Substerilizing room Surgical induction room Surgical holding area Toilets Utility room Waiting areas General Local for reading
200 300 150 500 1000 500 300 300 100 300 500 500 200 300 200 300
0.6
6.5
2.2 2.2 0.6
23.7 23.7 6,5
1.4 1.4 1.4 1.4
15.1 15.1 15.1 15.1
0.9
9.7
1.0 1.0
10.8 10.8