SPLN S3.001-3: 2012
5 6
7
ComunicationPort Local Configuration Terminal Interface Database configuration Protokol
8.9
:
ST / SC / MTRJ / LC
: : :
RJ-45 / RS-485 / RS-232 Upload dan download IEC 61850
Media Telekomunikasi Tabel 48. Spesifikasi Media Telekomunikasi
No 1 2 3 4 5
6
8.10 8.10.1
Deskripsi Data Transfer Speed CommunicationPort Communication Station Level Communication IED to Switch Communication Switch to switchbetween cubicle (indoor) Communication Switch to switch betweencubicle (outdoor)
: : : : :
Persyaratan IEC 61850 / Ethernet 100 MB/s, In front or rear, or both Electrical (SFTP) Fiber Optic Fiber Optic
:
Fiber Optic Armoured
Layout Layout Konfigurasi pasokan listrik ke panel SOGI
Gambar 27. Konfigurasi Pasokan Listrik ke Panel SOGI
108
SPLN S3.001-3: 2012
8.10.2 Layout Panel Kontrol dan Proteksi Layout Panel Kontrol dan Proteksi 150 kV Double Busbar Front View
Front View
Proteksi & Kontrol OHL
Ethernet Switch
Proteksi & Kontrol Trafo
Ethernet Switch
Ethernet Switch
Bus 1
IED BCU
IED MPU
BCU
Bus 2
Q1
IED MPU
IED BPU-1
Q2
Q1
Q2
AVR
m m 0 0 2 2
Q0
Q0
Q9
IED BPU
IED BPU-2
Q8
OHL
Test Switch
U C B
U P M
800 mm
Test Switch
Test Switch
U P B
U P M
1 U P B
Transformer
2 U P B
U C B
800 mm
R V A
800 mm
Gambar 28. L a y o u t Panel Kontrol dan Proteksi 150kV D o u b l e B r e ak e r
109
SPLN S3.001-3: 2012
8.10.3 L a y o u t Panel Kontrol dan Proteksi 150 kV One-Half Breaker Front View Proteksi Diameter
Ethernet Switch
Front View
Front View
Front View
Proteksi OHL
Proteksi& Kontrol Trafo
Proteksi BUSPRO
Ethernet Switch
CBF A
Ethernet Switch
IED MPU
Ethernet Switch
IED MPU
IED AVR
Ethernet Switch
BUSPRO BUS A
Bus A
Q0A
CBF AB
IED BPU
m m 0 0 2 2
IED B PU -1
IED BCU LV
m m 0 0 2 2
BUSPRO BUS B
Q0AB *) untuk bay IBT
CBF B
CCP
IED B PU -2
Q0B Bus B
CCP
Test Switch
A F B C
B A F B C 800mm
B F B C
Test Switch U P M
U P B
800mm
P C C
Test Switch U P M
1 U P B
2 U P B
Test Switch
P C C
800mm
R V A
Test Switch
BUSPRO BUS A
800mm
BUSPRO BUS B
800mm
Gambar 29. Layout Panel Kontrol dan Proteksi untuk One-Half B reaker
110
SPLN S3.001-3: 2012
8.10.4 Layout Panel Kontrol dan Proteksi 500 kV one-half breaker Front View
Front View
Proteksi Trafo / IBT
Proteksi Line
Ethernet Switch
Ethernet Switch
Ethernet Switch
Ethernet Switch
Bus A IED M PU-1
IED M PU-2
IED M PU-1
IED M PU-2
Q0A
IED BPU-1
IED BPU-2
IED MPU CCP-2
IED MPU CCP-1
Q0AB
0 0 m 2 m 2
IED MPU CCP -1
IED MPU CCP -2
Q0B 2
Bus B
Test Switch 1 U P M
1 U P B
Test Switch
Test Switch
1 P C C
1 U P M
800 mm
1 U P B
1 U P M
1 P C C
800 mm
Test Switch 1 U P M
1 P C C
800 mm
1 P C C
800 mm
Gambar 30. Layout Panel Proteksi Line & IBT 500 kV One-Half B reaker
Front View
Front View
Proteksi Busbar
Proteksi Diameter Ethernet Switch
CBF A
Ethernet Switch
Ethernet Switch
BUSBAR A
BUSBAR B
BUSPRO IED Main 1
Front View
Front View
BCU CB
BCU IBT + TC LV
Ethernet Switch
BCU CB A
Ethernet Switch
BCU IBT+ TC LV
Bus A
Q0A
BUSPRO IED Main 1
Q0AB CBF AB
BCU CB AB
m m 0 0 2 2
BUSPRO
BUSPRO IED Main 2
IED Main 2
Q0B
CBF B
BCU CB B
Test Switch
A F B C
B A F B C 800mm
B F B C
Test Switch 1 P B B
1 B A F B C
800 mm
Test Switch
Test Switch 2 P B B
2 B A F B C
A U C B
B A U C B
800 mm
800 mm
B U C B
Bus B
Test Switch T B I U C B
800 mm
Gambar 31. Layout Panel Kontrol dan Proteksi B u s b a r 500 kV One-Half Breaker
111
SPLN S3.001-3: 2012
8.10.5 Layout HMI Lokal 1800
1800 1
1
HMI 2
HMI 1 5
0 0 9
5 5a
3 5a
5b
5b
4
0 0 9
4
6
6
No
Description
1
Table
2
Chair
3
Laser Jet Printer
4
Monitor
5
Speaker Active (Tweeter)
5a
Speaker (L)
5b
S pe ak er ( R)
6
Keyboard and Mouse
7
Cable Hole
Gambar 32. L a y O u t HMI Lokal
HMI Lokal terdiri dari : a. b. c. d. e. f.
9
Dua buah meja Dua kursi ergonomis Dua buah monitor Dua buah Mouse Dua buah Keyboard Dua buah annunciator
Suku Cadang
Kontraktor harus menyiapkan suku cadang dalam masa pemeliharaan dan masa garansi guna keandalan operasi remote station. Suku cadang dibagi dalam : a.
Suku cadang jangka pendek yang dibutuhkan untuk operasi selama masa pemeliharaan dan masa garansi.
b.
Menyampaikan surat jaminan bahwa suku cadang yang sama/equivalen tersedia selama 10 (sepuluh) tahun.
10
Garansi
Kontraktor dan vendor harus bertanggung jawab apabila terdapat bug pada perangkat lunak yang dipergunakan dalam remote station. Bila ditemukan bug setelah masa pemeliharaan, kontraktor wajib memperbaiki bug tersebut tanpa diperlukan biaya tambahan, semua biaya yang ditimbulkan menjadi tanggung jawab kontraktor. Waktu perbaikan bug paling lama 2 (dua) bulan setelah pemberitahuan adanya bug oleh PT PLN
112
SPLN S3.001-3: 2012
(Persero), dengan syarat sistem berjalan normal pada saat proses perbaikan. Kesepakatan ini ditandatangani di atas meterai secukupnya oleh kontraktor dan vendor dengan sepengetahuan PT PLN (Persero). Garansi bug selama SOGI berfungsi dan garansi perangkat keras selama 5 tahun.
113
Pengelola Standardisasi : PT PLN (Persero) Pusat Penelitian dan Pengembangan Ketenagalistrikan Jl. Durentiga, Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762, www.pln-litbang.co.id