CONTENT BUILDING INTERFACES INTERFACES FOR ELEV ELEVA ATORS AND ESCALATORS
ELEV ELE VATORS : EN 81 81.1 .1 – 19 1998 98 + A3 A3-20 -2010 10
and now EN 81-20 the new code ESCALATORS
& MOVING WALKS :
EN 115-1 : 2008 + A1-2010
Company Proprietary & Confidential
THE NEW EN 81-20 & 81-50 August 7th 2014, new EN standards EN 81-20 & EN 81• August 50 were published giving the design requirements to comply with the Lifts Directive. They make make signif signific icant ant impr improveme ovement nt to the safet safety y of • They lifts by applying new or requirements for lift design.
improved
technical
From August August 31st 2017, all handed over units will have • From to comply with these new frame of standards.
•
2 Company Proprietary & Confidential
THE NEW EN 81-20 & 81-50 August 7th 2014, new EN standards EN 81-20 & EN 81• August 50 were published giving the design requirements to comply with the Lifts Directive. They make make signif signific icant ant impr improveme ovement nt to the safet safety y of • They lifts by applying new or requirements for lift design.
improved
technical
From August August 31st 2017, all handed over units will have • From to comply with these new frame of standards.
•
2 Company Proprietary & Confidential
THE NEW EN 81-20 & 81-50
-
-
3 Company Proprietary & Confidential
THE NEW EN 81-20 & 81-50
2014/08/07 Publication of new revised standard
2016/09/01 All units manufactured by OTIS will be EN 81-20/50 compliant
EN 81-1 / EN 81-2
2017/08/31 All units handed over to customers must be compliant with new code
EN 81-1 / EN 81-2 can no longer be used. All units handed over must be EN 81-20/50 compliant
EN 81-20 / EN 81-50
EN 81-20 / EN 81-50 Only
Both EN 81-1 / EN 81-2 & EN 81-20 /EN 81-50 can be used and units are compliant Company Proprietary & Confidential
4
WHAT’S THE CHANGE
Refuge spaces increased Additional warning labels on top of car to indicate the required stance in the emergency position for maintenance personnel Modification of the balustrade mechanical strength and size according to gap between hoistway wall and balustrade.
Brighter car light and emergency light Door protection system with light curtain Wider emergency exits Increased fire resistance of car body panels and car door Increased robustness for car body and car doors Increased car apron mechanical strength Prevention of car doors being opened away from landings Unintended Car Movement Protection (UCMP) device is now considered as a safety device of the elevator, according to the new lifts directive.
5 Company Proprietary & Confidential
WHAT’S THE CHANGE
Inspection speed limited to 0.30 m/s Improved lighting in shaft (50 lux at 1 m on top of car and pit, 20 lux minimum on other locations & car top emergency light). New standards addressed for electrical protection. Changed responsibilities for shaft ventilation. Increased robustness for panels of glass shaft.
Modification of door lock position
Increased robustness for doors panels
Refuge spaces increased
Improved mechanical strength of counterweight screen
Buffer deceleration rate modification
New pit ladder definition
Access by door at pit level when pit is deeper than 2.5m
Pit control station
Company Proprietary & Confidential
6
WHAT’S NEW FOR THE PASSENGER Mains improvements for
Improved from 50 lux to 100 lux at 1 m above floor level. Feel safer with better lighting.
Mains improvements for
On car roof or side panels: Assistance to entrapped passenger in car is easier and safer both for mechanics and passengers.
5 lux for 1 hour duration. In case of entrapment, passengers don’t stay in the dark. Reduces risk of fire inside the car. Non-contact light curtain mechanism. No more Photocell based mechanism. Reduces risk of passenger being struck while entering or exiting the car.
For glass shafts: Reduce risk of injury in case of shaft glass break and fall into the shaft. Reduce risk of injury & falling into shaft during an emergency rescue when the elevator is not at a landing operation. 7
Guide rail for instance. Better comfort and ride quality. Company Proprietary & Confidential
OTIS SOLUTION FOR COMPLIANCE Impacts of new standards on
Impacts of new standards on
.
2 examples: - Common button on inspection control station - Deterrent device
If the distance between the wall & the interior of the balustrade handrail is r, instead of a 700 mm balustrade for a distance lower than 500 mm.
.
. From September 1 st 2016, one year in advance.
OTIS’ major asset is the allowing to avoid the opening at top of shaft.8
Company Proprietary & Confidential
,
SHAFT : GENERAL REQUIREMENT Height between floors The rule for no more than 11m between floors is unchanged, except for Fire Fighting lifts which must have not more than 7m between floors. Ventilation Due to different rules for ventilation found within the Building Regulations in each European country, it is not possible for the standard to give guidance on this. Therefore the ventilation of this building space should be treated as any other and becomes the responsibility of the building designer. However, the manufacturer should specify the heat output of the equipment to be dealt with.
Company Proprietary & Confidential
SHAFT : GENERAL REQUIREMENT Where there are accessible spaces under the pit a safety gear must be provide on the counterweight. It is no longer permissible to use a “solid pier” as a means of protection.
Where the pit is more than 2.5m deep, the access to the pit must be by a door at pit floor level. It is not acceptable for an engineer to climb down a ladder more than 2.5m without some means of fall protection. This will have an enormous effect on the design of the building.
Company Proprietary & Confidential
SHAFT : STRENGTH
All glass used in the well must be laminated. The previous requirement was only where the glass was considered as accessible, but now it is anywhere in the well.
There are new requirements for strength of walls, doors and pit floor.
Force
Area
Deflection
Well walls (other than glass)
1000N
0,3m x 0,3m
≤ 1mm permanent ≤ 15mm elastic
Glass well walls
1000N
0,3m x 0,3m
No permanent deformation
Access , inspection and emergency doors in well
1000N
0,3m x 0,3m
≤ 15mm elastic
Pit floor o
This should withstand loads from guides, equipment mounted on the guides and “push through” forces caused by building shrinkage . This will lead to now guide rail fixing calculations and new forces to the pit floor. Company Proprietary & Confidential
SHAFT : ACCESS TRAP DOORS Doors for access, inspection and rescue – Inspection “traps” deleted and replaced with access or inspection “doors”.
✗
✔
– Door sizes Access
doors to well = 2m high x 0,6m wide Emergency doors in well = 1,8m high x 0,5m wide Inspection doors in well = 0,5m high x 0,5m wide
Company Proprietary & Confidential
SHAFT : PROTECTION IN THE WELL All screens
There are new requirements for strength and perforation size. (See Support Engineering for more details)
Shaft Division Screen
This has now been changed from 500mm from the side of the car to the nearest moving part, to 500mm from the inside of the car roof balustrade to the nearest moving part .
Headroom A: Distance ≥ 0,50 B: Distance ≥ 0,50 C: Distance ≥0,50 D: Distance ≥ 0,30 E: Distance ≤ 0,40 m X: Height of refuge spaces
: Highest parts on the car roof : Car : Refuge space(s)
Height above any area considered as a standing area (0,12m2 must be the same as the refuge space height.)
Company Proprietary & Confidential
SHAFT : PROTECTION IN THE WELL Headroom – One refuge space for each person on the car roof. – All refuge spaces must be of the same type. – Sign on car roof stating how many refuge spaces and what type – Sign on CWT giving dimension to buffer under normal operation.
Type
1
Posture
Pictogram
Standing
2 Crouching
Key for pictograms : Black colour : Yellow colour : Black colour
Company Proprietary & Confidential
Horizontal dimensions of the refuge space
Height of the refuge space
(m x m)
(m)
0,40 x 0,50
2,00
0,50 x 0,70
1,00
SHAFT : PROTECTION IN THE WELL Pit Type
– One refuge space for each person in the pit. – All refuge spaces must be of the same type. – Sign in pit stating how many refuge spaces and what type
Posture
Pictogram
Horizontal dimensions of the refuge space (m x m)
Height of the refuge space (m)
1
Standing
0,40 x 0,50
2,00
2
Crouching
0,50 x 0,70
1,00
Laying
0,7 x 1,0
0,5
3
Key for pictograms : Black colour : Yellow colour : Black colour
Company Proprietary & Confidential
SHAFT : PROTECTION IN THE WELL Access to the pit New requirements for pit access ladders and to provide them with a safety contact where necessary. The permissible type of ladder are now described in the standard, see examples below: CHAIN OR ROPE FOR PREVENTING REMOVAL FROMTHE PIT
1
2
1
2
“Movable” ladder fastened (1) in the pit and can be placed in climbing position (2).
Ladder fixed in the pit (1) and always placed in the climbing position (2).
Fixation of ladder feet for preventing tripping over
Company Proprietary & Confidential
2
SHAFT : LIGHTING The requirements for well have been aligned with the interpretation given under EN 81-1. New requirements are highlighted in red.
Lighting Area
Well
Access to Well or Machinery Spaces
Requirement from EN81-1/2
Requirement from EN81-1 Interpretation
50 lux @ 1m from car roof 50 lux @ 1m from pit floor Intermediate lamps Lamps at 0.5m from highest and lowest points Permanently lit
---
---
Requirement from EN81-20 50 lux @ 1m from car roof 50 lux @ 1m from pit floor 20 lux @ all other areas excluding shadows
20 lux throughout the well ---
---
50 lux
Limits of application •
Well lighting now under EN81 rules.
•
The national requirements apply to whole lighting & socket outlet circuits of the machine room and the pulley room. Company Proprietary & Confidential
MACHINERY SPACES : LIGHTING Lighting Area
Requirement from EN81-1/2
Requirement from EN 81-1 Interpretation
Requirement from EN81-20
Machine Room
200 lux @ floor level
Machinery Space
200 lux @ floor level
@ places where persons can stand, work or move between working areas ---
Machinery Cabinet Emergency and Test panel Pulley Room
200 lux @ floor level
---
50 lux @ device
200 lux @ floor level
200 lux @ places where persons can work 50 lux @ places where persons move between working areas 200 lux @ places where persons can work 50 lux @ places where persons move between working areas 200 lux @ places where persons can work 200 lux @ device
100 lux @ pulleys
---
Company Proprietary & Confidential
200 lux @ places where persons can work 50 lux @ places where persons move between working areas
CAR & LANDING: LIGHTING The requirements for car lighting have been improved to 100 lux and an emergency lamp added to the car roof. New requirements are highlighted in red.
Lighting Area Requirement from EN81-1/2
Requirement from EN81-1 Interpretation
Requirement from EN81-20
Landings Car
50 lux @ floor
---
50 lux @ floor
50 lux @ floor and controls
Car Emergency
1 w for 1 hour
Car Roof Emergency
---
@ floor (> than 100mm from walls and at controls) 1 lux for 1 hour @ alarm button and any instructions ---
100 lux @ controls and 1m above floor > 100mm from wall 5 lux for 1 hour @ alarm button and 1m from floor in centre of car 5 lux for 1 hour @ alarm button and 1m from floor in centre of car roof
Company Proprietary & Confidential
CAR & LANDING: SAFETY Unlocking mechanisms are to be limited in height to; Vertical Plane
= 2,0m maximum height
Horizontal Plane
= 2.7m maximum height with extended length unlocking key.
Non contact door protection required on all power doors (safety edges).
Company Proprietary & Confidential
LIFT CAR : LOADING Goods Lifts / Handling Devices Either: The weight of handling devices are included in the rated load; or The weight of handling devices shall be considered separately from the rated load: Handling devices are not transported with the load; The car sling, the car safety gear, the guide rails, the machine brake, traction, hydraulic ram, the UCM protection means, etc, shall be based on the total load of rated load plus weight of handling devices If due to loading and un-loading the maximum levelling accuracy is exceeded a mechanical device shall limit downward movement of the car to 20mm
Company Proprietary & Confidential
LIFT CAR: FINISHES Car Design Car internal finishes to be of limited combustibility to EN 13501-1. This is a very specific set of requirements and will apply to cars lined out by “others”. Car lighting 100 lux normal lighting (increased from 50 lux) 5 lux emergency lighting inside car 5 lux emergency lighting on car roof
Mirrors used inside the car to be of safety glass to EN 12600
Company Proprietary & Confidential
LIFT CAR: BALUSTRADE > 500 500
300
0 0 7
> 300
≤ 150
No balustrade required but needs toe board 100mm high
Balustrade Required Height ≥ 700 mm Company Proprietary & Confidential
0 0 1 1
≤ 150
Balustrade Required Height ≥ 1100 mm
ESCALATORS & MOVING WALKS BUILDING INTERFACES FOR ELEVATORS AND ESCALATORS
ELEVATORS : EN 81.1 – 1998 + A3-2010
and now EN 81-20 the new code ESCALATORS
& MOVING WALKS :
EN 115-1 : 2008 + A1-2010
Company Proprietary & Confidential
EN115 : ANGLE OF INCLINATION 5.2.2 ANGLE OF INCLINATION The angle of inclination of the escalator shall not exceed 30° , but for rises not exceeding 6m and a nominal speed not exceeding 0.50mps the angle of inclination is permitted to be increased up to 35° (see in the Figure 2 below) The angle of inclination of Moving walks shall not exceed 12°.
25 Company Proprietary & Confidential
EN115 : SUPPORTING STRUCTURE Clause 5.2.5 : Supporting structure shall be designed to support dead weight of the escalator or moving walk plus rated load of 5000 N/m 2. It shall be calculated in accordance with EN 1993-1-1. Note : Load Carrying area = (nominal width z1 (see figure below) of the escalator or moving walk) x (distance / 1 between the support) (see figure 2). Based on the rated load, the maximum calculated or measured deflection shall not exceed 1/750 of the distance/ 1 between the supports.
26 Company Proprietary & Confidential
EN115 : HANDLING CAPACITY H.1 Maximum capacity For traffic flow planning, the maximum number of persons that can be carried by an escalator or moving walk in 1 h is given in Table H.1:
27/100 Company Proprietary & Confidential
EN115 : CLEAR HEIGHT NEED A.2.1 Clear height of 2,30 m shall also be applied to the unrestricted area.
Company Proprietary & Confidential
EN115 : USE OF BOLLARDS - SAFETY I.1 Use of shopping trolleys and baggage carts on escalators: The use of both shopping trolleys and baggage carts on escalators is unsafe and shall not be permitted. The principle reasons why the use of these products is considered to be unsafe are foreseeable misuse, overloading and width restriction.
To prevent the people from carrying the Wheel chair and trolleys on Escalators or Moving walks we can have bollards in front of the entrance side of these units as shown in the attached picture.
29 Company Proprietary & Confidential
EN115 : BUILDING INTERFACE A.2.5 Unrestricted area shall be available to accommodate persons.
Company Proprietary & Confidential
EN115 : BUILDING INTERFACE additional
EN115-1:2008+A1:2010
A.2.7 Where it is possible for people to come into contact with the outer edge of a handrail at a landing and can be drawn into a hazardous situation, such as toppling over a balustrade, appropriate preventative measures shall be taken (e.g. increasing the height of fixed balustrade by at least 100 mm above handrail level and positioned between 80 mm and 120 mm from the outer edge of the handrail).
Company Proprietary & Confidential
EN115 : CAUTION SIGNS EN115:1995
EN115-1:2008+A1:2010
Small children must be held firmly! Stand facing the direction of travel, keep feet away from sides! Dogs (pets) must be carried! Hold the handrail!
Push chairs not permitted!